AN ACT CONCERNING SMALL HOT WATER HEATERS.  
 
SUMMARY 
This bill exempts certain hot water heaters from the state Safety 
Code for Boilers and Hot Water Heaters. The exemption applies to 
heaters (1) approved by a nationally recognized testing agency and 
equipped with adequate safety devices, including a temperature and 
pressure release valve; (2) with a nominal capacity of up to 10 gallons 
and a heat input of up to 20,000 BTUs (British thermal units) per hour; 
and (3) installed in any occupancy. 
The law already exempts hot water heaters meeting the first 
criterion listed above if they (1) have a capacity of up to 120 gallons 
and a heat input of no more than 200,000 BTUs per hour, (2) are solely 
for hot water supply carrying a pressure of up to 160 PSI (pounds per 
square inch), and (3) operate at a temperature of up to 210 degrees 
Fahrenheit. However, this exemption does not apply to heaters in 
schools, day care centers, hospitals, nursing or boarding homes, 
churches, or public buildings. 
Generally, the Safety Code for Boilers and Hot Water Heaters 
regulates boiler and hot water heater design, construction, installation, 
repair, use, and operation. Among other things, it requires that boilers 
and hot water heaters subject to the code be registered with the 
Department of Administrative Services and inspected by a boiler 
inspector (CGS ยงยง 29-231 to -244). 
EFFECTIVE DATE:  Upon passage 
COMMITTEE ACTION 
Public Safety and Security Committee 
Joint Favorable  2021HB-06395-R000085-BA.DOCX 
 
Researcher: TA 	Page 2 	3/18/21 
 
Yea 23 Nay 0 (03/04/2021)