17 | | - | Section 1. (Effective from passage) The Commissioner of Energy and 1 |
---|
18 | | - | Environmental Protection, in consultation with the Public Utilities 2 |
---|
19 | | - | Regulatory Authority and the Commissioner of Economic and 3 |
---|
20 | | - | Community Development, shall conduct a study concerning energy 4 |
---|
21 | | - | efficiency performance standards for artificial intelligence data centers. 5 |
---|
22 | | - | Such study shall consider (1) best practices for energy efficiency in such 6 |
---|
23 | | - | data centers, (2) energy management systems that may be implemented 7 |
---|
24 | | - | by such data centers, (3) the use of renewable energy resources to offset 8 |
---|
25 | | - | greenhouse gas production by such data centers, (4) the ability of such 9 |
---|
26 | | - | data centers to participate in demand response programs, and (5) 10 |
---|
27 | | - | limitations on the use of diesel backup generators to prohibit peak 11 |
---|
28 | | - | shaving or load shedding by such data centers. Not later than February 12 |
---|
29 | | - | 1, 2026, the commissioner shall submit a report, in accordance with the 13 |
---|
30 | | - | provisions of section 11-4a of the general statutes, to the joint standing 14 |
---|
31 | | - | committee of the General Assembly having cognizance of matters 15 |
---|
32 | | - | relating to energy and technology. 16 |
---|
| 24 | + | Section 1. (NEW) (Effective October 1, 2025) (a) For the purposes of this 1 |
---|
| 25 | + | section: 2 |
---|
| 26 | + | (1) "Artificial intelligence" has the same meaning as provided in 3 |
---|
| 27 | + | section 51-10e of the general statutes; 4 |
---|
| 28 | + | (2) "Artificial intelligence data center" or "data center" means a facility 5 |
---|
| 29 | + | that is developed, acquired, constructed, rehabilitated, renovated, 6 |
---|
| 30 | + | repaired or operated to house a group of networked computer servers 7 |
---|
| 31 | + | in one physical location or multiple contiguous locations to centralize 8 |
---|
| 32 | + | the storage, management and dissemination of data and information 9 |
---|
| 33 | + | pertaining to artificial intelligence that requires an energy load of not 10 |
---|
| 34 | + | less than one megawatt of uninterrupted capacity; 11 |
---|
| 35 | + | (3) "Commissioner" means the Commissioner of Energy and 12 |
---|
| 36 | + | Environmental Protection; 13 |
---|
| 37 | + | Raised Bill No. 1292 |
---|
| 38 | + | |
---|
| 39 | + | |
---|
| 40 | + | |
---|
| 41 | + | LCO No. 4310 2 of 5 |
---|
| 42 | + | |
---|
| 43 | + | (4) "Energy reuse factor" means a calculation of waste heat reused 14 |
---|
| 44 | + | divided by total energy consumption; 15 |
---|
| 45 | + | (5) "Power usage effectiveness" means a calculation of an artificial 16 |
---|
| 46 | + | intelligence data center's total energy consumption divided by the total 17 |
---|
| 47 | + | energy consumption of its information technology equipment; 18 |
---|
| 48 | + | (6) "Renewable energy factor" means a calculation of an artificial 19 |
---|
| 49 | + | intelligence data center's total renewable energy consumption divided 20 |
---|
| 50 | + | by its total energy consumption; 21 |
---|
| 51 | + | (7) "Total renewable energy" means the sum of total renewable 22 |
---|
| 52 | + | energy certificates, total renewable energy consumption from power 23 |
---|
| 53 | + | purchasing agreements and total renewable energy consumption from 24 |
---|
| 54 | + | on-site renewable energy generating resources or power supplies; 25 |
---|
| 55 | + | (8) "Waste heat reused" means any heat that is used or reused outside 26 |
---|
| 56 | + | the boundary of an artificial intelligence data center and that substitutes, 27 |
---|
| 57 | + | partly or entirely, energy needed outside the boundary of such data 28 |
---|
| 58 | + | center; and 29 |
---|
| 59 | + | (9) "Water usage effectiveness" means a calculation of an artificial 30 |
---|
| 60 | + | intelligence data center's total water input divided by the total energy 31 |
---|
| 61 | + | consumption of its information technology equipment. 32 |
---|
| 62 | + | (b) Not later than July 1, 2026, and quarterly thereafter, any owner or 33 |
---|
| 63 | + | operator of an artificial intelligence data center shall submit a report to 34 |
---|
| 64 | + | the commissioner that contains at a minimum the following information 35 |
---|
| 65 | + | for each such data center: 36 |
---|
| 66 | + | (1) Basic information relating to such data center, including: (A) The 37 |
---|
| 67 | + | name of such data center; (B) the owner or operator of such data center; 38 |
---|
| 68 | + | (C) the address of such data center; (D) the nature or purpose of such 39 |
---|
| 69 | + | data center; and (E) the month and year such data center commenced 40 |
---|
| 70 | + | operation; 41 |
---|
| 71 | + | (2) Information related to energy and water usage of such data center, 42 |
---|
| 72 | + | Raised Bill No. 1292 |
---|
| 73 | + | |
---|
| 74 | + | |
---|
| 75 | + | |
---|
| 76 | + | LCO No. 4310 3 of 5 |
---|
| 77 | + | |
---|
| 78 | + | including: (A) The total energy consumption in kilowatt-hours, 43 |
---|
| 79 | + | including the use of electricity, fuels and other energy sources used for 44 |
---|
| 80 | + | cooling; (B) the name of the electric distribution company serving such 45 |
---|
| 81 | + | data center and any electric service agreements between such utility and 46 |
---|
| 82 | + | such data center; (C) any on-site power supply, including (i) any 47 |
---|
| 83 | + | primary power on site and emergency backup power supply, and (ii) 48 |
---|
| 84 | + | any permit information such as permit numbers, capacity, tier level, fuel 49 |
---|
| 85 | + | type, total permitted emissions for such data center and any other 50 |
---|
| 86 | + | relevant information; (D) the total energy consumption of information 51 |
---|
| 87 | + | technology equipment in kilowatt-hours measured as the value of the 52 |
---|
| 88 | + | combined annual energy consumption at every uninterruptible power 53 |
---|
| 89 | + | system connected to information technology equipment; (E) the total 54 |
---|
| 90 | + | water input in cubic meters that includes all water volumes that enter 55 |
---|
| 91 | + | such data center's boundary that are used for the functions of such data 56 |
---|
| 92 | + | center, including information technology, security, power and 57 |
---|
| 93 | + | environment; and (F) the source of water for such data center, including 58 |
---|
| 94 | + | a municipal water supply, groundwater, surface water and whether 59 |
---|
| 95 | + | water from such sources is potable or reclaimed. If an artificial 60 |
---|
| 96 | + | intelligence data center utilizes more than one water source, the owner 61 |
---|
| 97 | + | or operator of such data center shall provide information regarding 62 |
---|
| 98 | + | water usage from each source as a percentage of total water usage; 63 |
---|
| 99 | + | (3) Performance calculations and indicators for such data center, 64 |
---|
| 100 | + | including the energy reuse factor, power usage effectiveness, renewable 65 |
---|
| 101 | + | energy factor and water usage effectiveness; 66 |
---|
| 102 | + | (4) Sustainability indicators for such data center, including: (A) The 67 |
---|
| 103 | + | average set point information technology equipment intake air 68 |
---|
| 104 | + | temperature in degrees Fahrenheit, which shall be measured as the 69 |
---|
| 105 | + | average set point temperature in all of such data center's computer 70 |
---|
| 106 | + | rooms over a twelve-month period; (B) the average waste heat 71 |
---|
| 107 | + | temperature in degrees Fahrenheit, which shall be measured as the 72 |
---|
| 108 | + | temperature of the fluid used to cool any information and 73 |
---|
| 109 | + | communication technology equipment, averaged over a twelve-month 74 |
---|
| 110 | + | period across every measurement point which shall be measured at the 75 |
---|
| 111 | + | Raised Bill No. 1292 |
---|
| 112 | + | |
---|
| 113 | + | |
---|
| 114 | + | |
---|
| 115 | + | LCO No. 4310 4 of 5 |
---|
| 116 | + | |
---|
| 117 | + | point where heated fluid enters a heat exchanger in such data center's 76 |
---|
| 118 | + | computer rooms; (C) the amount of total renewable energy in kilowatt-77 |
---|
| 119 | + | hours; and (D) the amount of waste heat reused in kilowatt-hours; and 78 |
---|
| 120 | + | (5) Any other information as required by the commissioner. 79 |
---|
| 121 | + | (c) Any information reported to the commissioner pursuant to 80 |
---|
| 122 | + | subsection (b) of this section shall be expressly excluded from any 81 |
---|
| 123 | + | exemption provided in section 1-210 of the general statutes. 82 |
---|
| 124 | + | (d) Not later than January 1, 2027, the commissioner shall, with the 83 |
---|
| 125 | + | assistance of any state agency as determined by the commissioner, 84 |
---|
| 126 | + | design, implement and maintain a publicly accessible Internet web site 85 |
---|
| 127 | + | to serve as a state-wide clearinghouse for information relating to water 86 |
---|
| 128 | + | and energy usage of all artificial intelligence data centers operating in 87 |
---|
| 129 | + | the state. 88 |
---|
| 130 | + | (e) Any owner or operator of an artificial intelligence data center shall 89 |
---|
| 131 | + | notify the commissioner of any substantial change in operations or 90 |
---|
| 132 | + | technologies that would require an update to the information required 91 |
---|
| 133 | + | in subsection (b) of this section not less than sixty days prior to making 92 |
---|
| 134 | + | such change. 93 |
---|
| 135 | + | (f) The commissioner shall adopt regulations, in accordance with the 94 |
---|
| 136 | + | provisions of chapter 54 of the general statutes, to establish energy and 95 |
---|
| 137 | + | water efficiency performance standards for artificial intelligence data 96 |
---|
| 138 | + | centers. Such regulations shall: (1) Prioritize cost-effectiveness, 97 |
---|
| 139 | + | technological feasibility and alignment with the state's greenhouse gas 98 |
---|
| 140 | + | emission reduction targets adopted pursuant to section 22a-200a of the 99 |
---|
| 141 | + | general statutes and the state water plan adopted pursuant to section 100 |
---|
| 142 | + | 22a-352 of the general statutes, (2) consider best practices for energy and 101 |
---|
| 143 | + | water usage effectiveness, energy and water management systems and 102 |
---|
| 144 | + | the use of renewable energy resources, and (3) require new artificial 103 |
---|
| 145 | + | intelligence data centers and substantial alterations to existing data 104 |
---|
| 146 | + | centers to incorporate load-management and load-shifting capabilities, 105 |
---|
| 147 | + | including the ability to participate in demand response programs. 106 |
---|
| 148 | + | Raised Bill No. 1292 |
---|
| 149 | + | |
---|
| 150 | + | |
---|
| 151 | + | |
---|
| 152 | + | LCO No. 4310 5 of 5 |
---|
| 153 | + | |
---|