District Of Columbia Council Bill PR25-0149 Compare Versions

Only one version of the bill is available at this time.
OldNewDifferences
11
22 MurietBOWSER
33 Mayor
44 March20,2023
55 TheHonorablePhilMendelson
66 Chairman
77 CounciloftheDistrictofColumbia
88 JohnA.WilsonBuilding
99 1350PennsylvaniaAvenue,NW,Suite504
1010 Washington,DC20004
1111 DearChairmanMendelson:
1212 EnclosedforconsiderationandapprovalbytheCounciloftheDistrictofColumbiaisthe
1313 proposedresolutionentitledthe“UndergroundStorageTanksInfractionsScheduleofFines
1414 EmergencyApprovalResolutionof2023”andanaccompanyingemergencydeclaration
1515 resolution.
1616 Theproposedresolutionswouldapproveaproposedfinalrulemakingthatwouldestablish
1717 ascheduleoffinesforviolationsofrulesrelatedtoundergroundstoragetanksinTitle16
1818 (Consumers,CommercialPractices,andInfractions),Chapter40(DDOEInfractions)ofthe
1919 DistrictofColumbiaMunicipalRegulationstoensurethatthemaintenanceofunderground
2020 storagetanksisundertakeninamannerthatprotectspublichealthandsafetyandthe
2121 environment.
2222 LurgetheCounciltotakepromptandfavorableactionontheenclosedlegislation.
2323 Sincfely,
2424 MurélBower 21
2525 22
2626 23
2727 24
2828 25
2929 26
3030 27
3131 28
3232 29
3333 30
3434 31
3535 Ce
3636 ChairmanPhilMendelson
3737 attherequestoftheMayor
3838 APROPOSEDRESOLUTION
3939 INTHECOUNCILOFTHEDISTRICTOFCOLUMBIA.
4040 Toapprove,onanemergencybasis,theproposedfinalrulestoestablishascheduleofcivil
4141 infractionsforviolationsoftheUndergroundStorageTankManagementActof1990.
4242 RESOLVED,BYTHECOUNCILOFTHEDISTRICTOFCOLUMBIA,Thatthis
4343 resolutionmaybecitedasthe“UndergroundStorageTanksInfractionsScheduleofFines
4444 EmergencyApprovalResolutionof2023”.
4545 Sec.2,Pursuanttosection104(a)(1)oftheDepartmentofConsumerandRegulatory
4646 AffairsCivilInfractionsActof1985,effectiveOctober5,1985(D.C.Law6-42;D.C.Official
4747 Code§2-1801.04(a)(1)),theCouncilapprovestheproposedrulemakingadoptedbythe
4848 DepartmentofEnergyandtheEnvironment,whichwaspublishedintheD.C.Registeron
4949 December4,2020,at67DCR14224,andthefinalrulemakingadoptedbytheDepartmentof
5050 EnergyandtheEnvironment,whichwaspublishedintheD.C.RegisteronOctober29,2021at
5151 68DCR11423,toestablishascheduleofcivilinfractionsforviolationsoftheDistrictof
5252 ColumbiaUndergroundStorageTankManagementActof1990,effectiveMarch8,1991
5353 (D.C.Law8-242;D.C.OfficialCode§8-113.01etseq.).
5454 Sec.3.Transmittal.
5555 32
5656 33
5757 34
5858 35
5959 36
6060 37
6161 38
6262 39
6363 40
6464 TheSecretarytotheCouncilshalltransmitacopyofthisresolution,uponitsadoption,to
6565 theMayor,theDirectoroftheDepartmentofEnergyandEnvironment,andtheAdministratorof
6666 theOfficeofDocumentsandAdministrativeIssuances.
6767 Sec.4.Fiscalimpactstatement.
6868 TheCounciladoptsthefiscalimpactstatementoftheChiefFinancialOfficerasthefiscal
6969 impactstatementrequiredbysection4aoftheGeneralLegislativeProceduresActof1975,
7070 approvedOctober16,2006(120Stat.2038;D.C.OfficialCode§1-301.47a).
7171 Sec.5.Effectivedate.
7272 Thisresolutionshalltakeeffectimmediately. 2
7373
7474 GOVERNMENT OF THE DISTRICT OF COLUMBIA
7575 O
7676 FFICE OF THE ATTORNEY GENERAL
7777
7878
7979 BRIAN L. SCHWALB PRIVILEGED AND CONFIDENTIAL ATTORNEY GENERAL ATTORNEY-CLIENT COMMUNICATION
8080
8181
8282
8383 LEGAL COUNSEL DIVISION
8484
8585
8686 MEMORANDUM
8787
8888
8989 TO: Tommy Wells
9090
9191 Director
9292 Office of Policy and Legislative Affairs
9393
9494
9595 FROM: Megan D. Browder
9696 Deputy Attorney General
9797 Legal Counsel Division
9898
9999 DATE: March 13, 2023
100100
101101 SUBJECT: Legal Sufficiency Review – Draft “ Underground Storage Tanks Infractions Schedule
102102 of Fines Approval Emergency Resolution of 2023” and Accompanying Emergency
103103 Declaration Resolution
104104
105105 (AE-19-754 C)
106106 _____________________________________________________________________________________
107107
108108 This is to Certify that this Office has reviewed the above- referenced draft
109109 legislation and found it to be legally sufficient. If you have any questions in this regard, please do
110110 not hesitate to call me at (202) 724- 5524.
111111
112112
113113
114114
115115 _________________________________
116116 Megan D. Browder
117117
118118
119119
120120
121121 1
122122
123123 DEPARTMENT OF ENERGY AND ENVIRONMENT
124124 NOTICE OF FINAL RULEMAKING
125125
126126 Underground Storage Tank Infractions
127127
128128 The Director of the Department of Energy and Environment (“DOEE”), pursuant to the authority
129129 set forth in Section 107 of the District Department of the Environment Establishment Act of
130130 2005, effective February 15, 2006 (D.C. Law 16- 51; D.C. Official Code § 8-151.07); the District
131131 of Columbia Underground Storage Tank Management Act of 1990, effective March 8, 1991
132132 (D.C. Law 8-242; D.C. Official Code § 8-113.01 et seq.) (“UST Act”); Sections 11 and 21 of the
133133 Water Pollution Control Act of 1984, effective March 16, 1985 (D.C. Law 5- 188; D.C. Official
134134 Code §§ 8- 103.10 & 8-103.20); the Department of Consumer and Regulatory Affairs Civil
135135 Infractions Act of 1985, effective October 5, 1985 (D.C. Law 6- 42; D.C. Official Code §§ 2-
136136 1801.01 et seq.); and Mayor’s Order 2006- 61, dated June 14, 2006, hereby gives notice of the
137137 adoption of the following amendments to Section 4008 of Chapter 40 (Department of the
138138 Environment (DDOE) Infractions) of Title 16 (Consumers, Commercial Practices, and Civil
139139 Infraction) of the District of Columbia Municipal Regulations (“ DCMR”).
140140 Section 10(g) of the U ST Act (D.C. Official Code § 8-113.09(g)) authorizes DOEE to impose a
141141 civil fine as an alternative sanction for any violation of the UST Act or the underground storage
142142 tank regulations published at 20 DCMR Chapters 55- 67 and 70 (“UST regulations”). Civil fine
143143 amounts are determined in accordance with the schedule of fines in 16 DCMR Chapter 32, which
144144 establishes classes of infractions and associated fine amounts. The class of infraction for each
145145 violation of a DOEE regulation is established in 16 DCMR Chapter 40. 16 DCMR § 4008
146146 establishes the class of infraction for each violation of the UST Act and UST regulations.
147147 On February 21, 2020, DOEE published a Notice of Final Rulemaking in the D.C. Register , at 67
148148 DCR 1778, amending the UST regulations. The amendment s incorporated new requirements of
149149 the 2015 amendments to the federal underground storage tank regulations at 40 CF R Part 280, as
150150 well as updates to other District requirements. This rulemaking amends 16 DCMR § 4008 to
151151 make the underground storage tank infractions consist ent with the amendments to the UST
152152 regulations.
153153 A Notice of Proposed Rulemaking was published in the D.C. Regi ster on December 4, 2020, at
154154 67 DCR 14224 to update the schedule of fines in light of the amendment to the UST regulations.
155155 DOEE received no comments on the proposed rule during the thirty (30) day comment perio d.
156156 DOEE is now finalizing the rules with the following technical corrections:
157157
158158 • Typographical and grammatical e rrors were corrected in subsections:
159159  4008.3(c) (clarified that the responsible party must in vestigate a suspected release
160160 and confirm whether a release has occurred within seven days) ;
161161  4008
162162 (w) (replaced “QA/QZ Plan” with “quality assurance and quality control
163163 plan”);
164164
165165 2
166166
167167  4008.3(z) (added “and” to “beginning implementation of Corrective Action Plan
168168 prior to approval ‘and’ without meeting specified requirements for doing so”);
169169  4008.4(a) (deleted “30” and replaced with “60”);
170170  4008.6(a) (deleted “BOCA National” and replaced with “ District of Columbia”
171171 and added “The District of C olumbia Municipal Regulations”)
172172  4008.7(f) (revised “or” to “and” in “failure to replace metal piping that is in
173173 contact with earthen materials that does not meet the requirements of 20 DCMR
174174 §§ 5802.1 ‘and’ 5802.2, with new piping that satisfies the requirements of 20
175175 DCMR § 5704”);
176176  4008.8(v), (x), 4008.9(f) , 4008.9(y ), 4008.10(t), (x), 4008.11(c) , (i), (k), (l)
177177 (replaced “30 days” with “thirty (30) days”);
178178  4008.9(b) (revised sentence structure for consistency with other provisions (added
179179 “failure to”));
180180  4008.9(c) (replaced “failure to conduct an annual test” with “failure to annually
181181 test,” added “automatic line” detector, and replaced “requirements” with
182182 “instructions”);
183183  4008.9(i) (clarified that this provision applies when there is a suspected release);
184184  4008.9(n) (replaced “90 days” with “ninety (90) days”);
185185  4008.9(o) ( replaced “7 days” with “within seven (7) days”);
186186  4008.9(z) (deleted “abandoned” and added “ closed-in-place,” replaced
187187 “permanently” closed with “temporarily” closed);
188188  4008.10(g) (replaced “20 days” with “twenty (20) days” and replaced “Director”
189189 with “Department”);
190190  4008.
191191 (s) (replaced “of designated” with “to ensure that all” and added “ receive
192192 required training and retraining”);
193193  4008.13(u) (replaced “reduced in eff ectiveness” with “less effective”);
194194  4008.14(z) (deleted “begin procedures to,” deleted “at the end of 12 months ,”
195195 replaced “ is” with “has been,” and added “for twelve (12) months”);
196196  4008.15(h) (replaced “at end of one year of implementation” with “at the end of
197197 each year of implementation”); and
198198  4008.16(b) (revised “and” to “or” in “failure to timely notify owner by certified
199199 mail if guarantor no longer meets the requirements of the financial test of §§ 6704
200200 or 6705 ‘or’ 6703.3”).
201201
202202  Citations were added or corr ected in subsections 4008.3(d) (added references to 20
203203 DCMR §§ 5902.7 and 6004.8), 4008.3(e) ( replaced reference to 20 DCMR §§ 6203.9
204204 through 6212 with “ Chapter 62”), and 4008.3(x) (added reference to 29 CFR §
205205 1910.120).
206206
207207 In updating the schedule of fines, the class es of infraction for requirements in regulations that
208208 were not amended by the February 2020 final rulemaking on the UST regulations have not been
209209 altered, except that a violation of 20 DCMR § 6101.9 for failure to properly empty, clean, and
210210 fill a tank with inert material for closure-in-place has been reclassi fied as a Class 2 infraction to
211211
212212 3
213213
214214 be consistent with other similar requirements to properly empty and clean a tank prior to a
215215 change-in-service or closure.
216216 1
217217
218218
219219 I
220220 n accordance with section 104(a)(1) of the D epartment of Consumer and Regulatory Affa irs
221221 Civil Infractions Act of 1985, effective October 5, 1985 (D.C. Law 6-42; D.C. Official Code § 2-
222222 1801.04(a)(1)), the Mayor transmitted the proposed final rules to the Council for its re view and
223223 approval on December --, 2022, pursuant to the Underground Storage Tanks Infractions
224224 Schedule of Fines Emergency Approval Resolution of 2022 (Prop. Res. 24-XXX).
225225 2
226226 The
227227 proposed final rules were approved by the Council on December --, 2022.
228228 T
229229 he Director of DOEE took final action to adopt this rulemaking on December --, 2022, and the
230230 rules shall become effective upon publication of this notice in the D.C. Register.
231231 Chapter 40, DEPARTMENT OF THE ENVIRONMENT (DDO E) INFRACTIONS, of
232232 Title 16 DCMR, CONSUM ERS, COMMERICIAL PRACTICES, AND CIVIL
233233 INFRACTIONS, is amended as follow s:
234234 Section 4008, UNDERGROUND STORAGE TANK IN FRACTIONS, is amended to read
235235 as follows:
236236 4008 UNDERGROUND STORAGE TANK INFRACTIONS
237237 4008.1 In addition to §§ 4008.2, 4008.3, and 4008.4, viola tion of any of the following
238238 provisions shall be a Class 1 infraction:
239239
240240 (a) D.C. Official Code § 8-113.09(c ) (continuing work stopped by a
241241 Department order);
242242
243243 (b) 20 DCMR § 5502.2 (installing an underground storage tank (UST) system
244244 listed in 20 DCMR § 5502.1(a), (b), or ( c) that fails to meet specified
245245 requirements);
246246
247247 (c) 20 DCMR § 5507.3 (installing an UST sy stem with field-constructed
248248 tanks or airport hydrant system that fails to comply with the regulations);
249249
250250 (d) 20 DCMR § 5507.7 (failure to upgrade an UST system with field-
251251 constructed tanks or airport hydrant system in accordance with specified
252252 requirements);
253253
254254
255255 1
256256 16 DCMR § 4008.13 provides that a violation of 20 DCMR § 6101.8 (failure to empty, clean, and fill tank with an
257257 inert solid mat erial and comply with 20 DCMR §§ 5600.14 and 6101 when a tank removal variance is granted) shall
258258 be a Class 3 violation. The proposed amendments to the UST regulations would move this requirement to 20
259259 DCMR § 6101.9.
260260 2
261261 On October 29, 2021, a Notice of Final Rulemaking was inadvertentl y published in the D.C. Register, at 68 DCR
262262 11423, prior to D.C. Council approval. That Notice of Final Rulemaking was rescinded by a Notice of Rescission of
263263 Final Rulemaking published in the D.C. Register on September 16, 2022, at 69 DCR 11279.
264264
265265 4
266266
267267 (e) 20 DCMR § 5601.9 (depositing or dispensing regulated substance into a
268268 UST for which registration has been denied);
269269
270270 (f) 20 DCMR § 5602.1 (failure to submit specified information and
271271 documentation as required);
272272
273273 (g) 20 DCMR § 5700.1 (failure of petroleum U ST system to meet specified
274274 performance standards or requirements for upgrade);
275275
276276 (h) 20 DCMR § 5700.2 (failu re of hazardous substance UST system insta lled
277277 after November 12, 1993 to meet performance st andards set forth in 20
278278 DCMR § 5702);
279279
280280 (i) 20 DCMR § 5700.8 (failure of metal tanks and attached metal piping
281281 conveying regulated substances to be designed, constructed, and installed
282282 in a manner that will prevent corrosion);
283283
284284 (j) 20 DCMR § 5701.1 (failure of petroleum UST to meet specified
285285 construction and material requi rements);
286286
287287 (k) 20 DCMR § 5701.2 (failure of petroleum steel tank to be cathodically
288288 protected as specified);
289289
290290 (l) 20 DCMR § 5701.8 (failure of motor fuel dispenser sys tem to contain
291291 under-dispenser containment as specified);
292292
293293 (m) 20 DCMR § 5702.1 (failure of hazardous substance UST to meet specified
294294 construction and material requirements);
295295
296296 (n) 20 DCMR § 5702.2 (failure of haz ardous substance steel tank to b e
297297 cathodically protected as specified);
298298
299299 (o) 20 DCMR § 5703.1 (failure of heating oil UST to meet specified
300300 construction and m aterial requirements);
301301
302302 (p) 20 DCMR § 5703.2 (failure of heating oil steel tank to be cathodically
303303 protected as specified);
304304
305305 (q) 20 DCMR § 5704.2 (failure of UST system piping to meet specified
306306 construction and material requirements);
307307
308308 (r) 20 DCMR § 5704.3 (failu re of steel UST piping to be cathodically
309309 protected as specified);
310310
311311 (s) 20 DCMR § 5705.1 (failure to use sp ill prevention equipment);
312312
313313
314314 5
315315
316316 (t) 20 DCMR § 5705.2 (failure to ensure that a new or upgraded UST system
317317 has sufficient volume to contain all regulated substances and that transfer
318318 is continuously monitored in accordance with 20 DCMR § 5900.3);
319319
320320 (u) 20 DCMR § 5800.1 (fa ilure of petroleum UST system to comply with
321321 specified upgrade requirements, performance standards, pe rmanent closure
322322 requirements, or corrective action requirements);
323323
324324 (v) 20 DCMR § 5800.2 (failure to ensure that all components connected to an
325325 existing petroleum UST system are operating and that all inoperative
326326 components are removed);
327327
328328 (w) 20 DCMR § 5800.3 (depositing a regulated substance into a petroleum
329329 UST that has not met upgrade requirements in 20 DCMR § 5800.1);
330330
331331 (x) 20 DCMR § 5800.4 (failure of hazardous substance UST system to
332332 comply with specifi ed performance standards, permanent closure
333333 requirements, or co rrective action requirements);
334334
335335 (y) 20 DCMR § 5803.1 (failure to comply with UST system spill and overfill
336336 prevention equipment requirements, in accordance with 20 DCMR §
337337 5705); or
338338
339339 (z) 20 DCMR § 5900.10 (failure to report, investigate, or clean up spi lls or
340340 overfills, in accordance with 20 DCMR Chapter 62).
341341
342342 4008.2 In addition to §§ 4008.1, 4008.3, and 4008.4, violation of any of the following
343343 provisions shall be a Class 1 infraction:
344344
345345 (a) 20 DCMR § 6000.1 (failure to provide release detection method(s) that
346346 meet the requirements of 20 DCMR § 6000);
347347
348348 (b) 20 DCMR § 6000.3 (failure to comply with release detection requirements
349349 for all pressurized piping, in accordance with 20 DCMR § 6004) ;
350350
351351 (c) 20 DCMR § 6000.5 (rel ease detection system incapable of detecting a
352352 release from all portions of the tank and connected underground piping);
353353
354354 (d) 20 DCMR § 6000.7 (failure of release detection method to meet applicable
355355 performance requirements of 20 DCMR §§ 6004 through 6013);
356356
357357 (e) 20 DCMR § 6000.9 (failure of release detection metho d to be capable of
358358 detecting leak rate or quantity with specifi ed probability of detection);
359359
360360 (
361361 f) 20 DCMR § 6000.11 (failure to repair or replace leak detection system
362362 within 45 days in accordance with 20 DCMR Chapter 60);
363363
364364 6
365365
366366
367367 (g) 20 DCMR § 6000.13 (failure to notify Department of suspected release, in
368368 accordance with 20 DCMR Ch apter 62);
369369
370370 (h) 20 DCMR § 6002.1 (failure to provide release detection for a hazardous
371371 substance UST system that meets the requirements of 20 DCMR § 6002);
372372
373373 (i) 20 DCMR § 6002.2 (failure of hazardous substance UST system to use
374374 secondary containment with interstitial monitoring in accord with 20
375375 DCMR § 6011);
376376
377377 (j) 20 DCMR § 6003.1 (failure to provide release detection for a petroleum
378378 UST system, in accordanc e with 20 DCMR § 6003);
379379
380380 (k) 20 DCMR § 6003.2 (failure of release detection methods to meet
381381 requirements of 20 DCMR §§ 6005 th rough 6012);
382382
383383 (l) 20 DCMR § 6004.2 (failure of release detection method for petrole um
384384 UST system piping to meet the requirements of 20 DCMR § 6004);
385385
386386 (m) 20 DCMR § 6004.3 (failure of petroleu m UST piping that conveys
387387 regulated substances under pressure to be equipped with an automatic line
388388 leak detector);
389389
390390 (n) 20 DCMR § 6100.7 (failure to comply with the release detection
391391 requirements in 20 DCMR Chapter 62 when UST system is temporarily
392392 closed);
393393
394394 (o) 20 DCMR § 6100.8 (failure to immediately comply with the req uirements
395395 of 20 DCMR § 6100.9 and the applicable requirements of 20 DCMR
396396 Chapter 62 if a release is suspected or confirmed during the period when
397397 UST is temporarily closed);
398398
399399 (p) 20 DCMR § 6101.12 (failure to begin corrective action in accordance with
400400 20 DCMR Chapter 62 if contamination is discovered during closure
401401 assessment or by any other manner);
402402
403403 (q) 20 DCMR § 6101.13 (stockpiling of contaminated soils on site or failure
404404 to properly store, treat, or dispose of soil);
405405
406406 (r) 20 DCMR § 6101.14 (returning untreated contaminated soils to the
407407 excavation pit or using the soils on-site);
408408
409409 (s) 20 DCMR § 6201.1 (failure to take immediate action to contain and clean
410410 up any spill or overfill of a regulated substance from an UST system);
411411
412412
413413 7
414414
415415 (t) 20 DCMR § 6201.2 (failure to immediately repo rt to the Department and
416416 to the Fire Chief any spill or overfill where there is danger of fire or
417417 explosion);
418418
419419 (u) 20 DCMR § 6201.3 (failure to immediately contain and clean up a spill or
420420 overfill of petroleum that is less than 25 gallons and to immediately notify
421421 the Department if the cleanup cannot be completed within 24 hour s);
422422
423423 (v) 20 DCMR § 6201.4 (failure to r eport to the D epartment within 24 hours a
424424 petroleum release that is more than 25 gallons a nd to begin corrective
425425 action, in accordance with the appli cable provisions of 20 DCMR Chapter
426426 62);
427427
428428 (w) 20 DCMR § 6201.5 (failure to immediately report a ny spill or over fill of a
429429 hazardous substance to the Department, the Fire Chief, and the D.C.
430430 Homeland Security and E mergency Management Agency, immediately
431431 contain and clean up the spill or overfill, and begin corrective action in
432432 accordance with the applicable provisions of 20 DCMR Chapter 62 if the
433433 cleanup cannot be completed within 24 hours);
434434
435435 (x) 20 DCMR § 6201.6 (failure to report to the National Response Center
436436 where a spill or overfill of a hazardous substance results in release to the
437437 environment that equals or exceeds its reportable quantity under CERCLA
438438 (40 CFR Part 302));
439439
440440 (y) 20 DCMR § 6202.1 (failure to notify the Department within 24 hours of a
441441 suspected release from an US T); or
442442
443443 (z) 20 DCMR § 6202.2 (failure to notify UST owner or operator immediately
444444 and the Department within 24 hours if a release is known or if reason
445445 exists to know of or suspect a release from an UST).
446446
447447 4008.3 In addition to §§ 4008.1, 4008.2, and 4008.4, violation of any of the following
448448 provisions shall be a Class 1 infraction:
449449
450450 (a) 20 DCMR § 6202.4 (knowingl y allowing a release from an UST system to
451451 continue withou t undertaking repair as soon as pos sible);
452452
453453 (b) 20 DCMR § 6202.5 (failure to timely report to the Department and to
454454 follow procedures in 20 DCMR § 6203 for any of the conditions
455455 specified);
456456
457457 (c) 20 DCMR § 6202.6 (failure of a re sponsible party to immediately
458458 investigate a suspected rel ease and confirm w hether a release has
459459 occurred within seven days);
460460
461461
462462 8
463463
464464 (d) 20 DCMR § 6203.1 (failure to conduct systems tests in accordance with
465465 tightness testing requirements of 20 DCMR §§ 5902.7, 6004.8, and 6007
466466 when a release is suspected);
467467
468468 (e) 20 DCMR § 6203.2 (failure to repair, replace, or upgrade an UST system
469469 and beg in corrective action in accordance with 20 DCMR Chapter 62 if
470470 test results indicate a release has occurred);
471471
472472 (f) 20 DCMR § 6203.4 (failure to conduct a site investigation as set forth in
473473 20 DCMR §§ 6203.5 through 6203.7 if a release exists or is suspected
474474 based on test results or on visual or analytical data of environmental
475475 contamination);
476476
477477 (g) 20 DCMR § 6203.5 (failure to test for a release where cont amination is
478478 most likely to be present at an UST si te);
479479
480480 (h) 20 DCMR § 6203.8 (failure to perform specified initial r esponse actions
481481 upon confirmation of a release);
482482
483483 (i) 20 DCMR § 6203.10 (failure to take specified initia l abatement actions);
484484
485485 (j) 20 DCMR § 6203.11 ( failure to remedy hazards posed by excavated or
486486 exposed contaminated soils and comply with all applicable laws an d
487487 regulations if remedies include treatment or disposal of soils);
488488
489489 (k) 20 DCMR § 6203.13 (failure to determine whether free product is present
490490 and begin free product removal as soon as practicable, in accordance with
491491 20 DCMR § 6204);
492492
493493 (l) 20 DCMR § 6204.1 (failure to remove measurable free product to the
494494 maximum extent practicable in accordance with schedule approved by the
495495 Department);
496496
497497 (m) 20 DCMR § 6204.3 ( failure to remove free product in a manner that
498498 minimizes the spread of contamination by using appropriate recovery
499499 techniques);
500500
501501 (n) 20 DCMR § 6204.4 (failure to recover and dispose of free product in a
502502 manner that properly treats, discharges, recycles, or disposes of recovery
503503 byproducts in compliance with all applicable laws and regulations);
504504
505505 (o) 20 DCMR § 6204.6 (failure to en sure that flammable substances are
506506 handled in a manner that will prevent fire a nd explosion);
507507
508508 (p) 20 DCMR § 6205.1 (failure to perform Comprehensive Site Assessment in
509509 the time and manner set forth in 20 DCMR § 6205);
510510
511511 9
512512
513513
514514 (q) 20 DCMR § 6205.2 (failure to submit a Co mprehensive Site Assessment
515515 in a form satisfactory to the Department within 60 days of subm ission of a
516516 work plan);
517517
518518 (r) 20 DCMR § 6206.2 (failure to comply with specified requirements before
519519 initiating a risk-based decision-making process);
520520
521521 (s) 20 DCMR § 6207.1 (failure to submit a Corrective Action Plan required
522522 by Department, according to a schedule and format established by the
523523 Department);
524524
525525 (t) 20 DCMR § 6207.2 (failure to submit and modify a s necessary a
526526 Corrective Action Plan that provides for adequa te protection of human
527527 health and the environment);
528528
529529 (u) 20 DCMR § 6207.3 (failure of Corrective Action Plan to propose
530530 corrective action option as s pecified);
531531
532532 (v) 20 DCMR § 6207.5 (failure of Corrective Action P lan to provide for
533533 proper disposal of contaminated soils and to prohibit placement of
534534 contaminated soils back into the ground);
535535
536536 (w) 20 DCMR § 6207.6 (failure t o prepare, prior to any site activities, a site-
537537 specific quality assurance and quality control plan that covers all actions
538538 proposed in the Corrective A ction Plan and complies with guidelines of
539539 the Department);
540540
541541 (x) 20 DCMR § 6207.7 (failure to prepare and submit to the Department a
542542 site-specific Health and Safety Plan that that meets the requirements of 29
543543 CFR § 1910.120, in conjunction with the Corrective Action Pl an);
544544
545545 (y) 20 DCMR § 6207.9 (beginning soil and groundwater remediation prior to
546546 approval of Corrective Action Plan without meeting specified
547547 requirements for doing so); or
548548
549549 (z) 20 DCMR § 6207.10 (beginnin g implementation of Corrective Action
550550 Plan prior to approval of plan and without meeting specified requirements
551551 for doing so).
552552
553553 4008.4 In addition to §§ 4008.1, 4008.2, and 4008.3, violation of an y of the following
554554 provisions shall be a Class 1 infract ion:
555555
556556 (a) 20 DCMR § 6207.11 (failure to begin implementation of approved
557557 Corrective Action Plan within 60 days or other perio d approved by the
558558 Department);
559559
560560 10
561561
562562
563563 (b) 20 DCMR § 6207.14 (implementing modificati ons to the Corrective
564564 Action Plan which have not been approved by the Department );
565565
566566 (c) 20 DCMR § 6207.15 (failure to take additional corrective action responses
567567 as required by the Department);
568568
569569 (d) 20 DCMR § 6300.1 (failure to provide entry to a Department inspector);
570570 or
571571
572572 (e) 20 DCMR § 6301.3 ( failure to cooperate fully with ins pections,
573573 monitoring, or testing, as well as req uests for document submission,
574574 testing, or monitoring).
575575
576576 4008.5 In addition to §§ 4008.6, 4008.7, 4008.8, 4008.9, 4008.10, and 4008.11, violation
577577 of any of the following provisions shall be a Class 2 infraction:
578578
579579 (a) 20 DCMR § 5507.4 (failure to notify the Department of an UST system
580580 with field-constructed tanks or airport hydrant system);
581581
582582 (b) 20 DCMR § 5507.9 (failure to inspect an UST system with field-
583583 constructed tanks or airport hydrant system as required);
584584
585585 (c) 20 DCMR § 5507.10 (failure of UST system with a field-constructed tank
586586 less than or equal to fifty thousand (50,000) gallons to meet the release
587587 detection requirements of Chapter 60);
588588 (d) 20 DCMR § 5507.11 (failure of UST system with a field -constructed tank
589589 greater than fifty thousand (50,000) gallons to meet s pecified release
590590 detection requirements);
591591
592592 (e) 20 DCMR § 5507.12 (failure of UST system piping associated with a
593593 field-constructed tank or airport hydrant system to meet specified release
594594 detection requirements);
595595
596596 (f) 20 DCMR § 5507.13 (failure to assess the excavation zone and properly
597597 close an UST system with field-constructed tanks or airport hydrant
598598 system that was previously closed- in-place, removed, or temporarily
599599 closed, as directed);
600600
601601 (g) 20 DCMR § 5600.1 (failure to submit required UST notification);
602602
603603 (h) 20 DCMR § 5600.2 (failure to file timely closure notification form
604604 following permanent closure of an UST syste m by removal or closure-in-
605605 place);
606606
607607
608608 11
609609
610610 (i) 20 DCMR § 5600.3 (failure to properly complete require d UST
611611 notification form);
612612
613613 (j) 20 DCMR § 5600.5 (failure to submit an UST facility notification for each
614614 separate UST facility);
615615
616616 (k) 20 DCMR § 5600.6 (failure to sign US T notification form and certify
617617 compliance with specified requirements);
618618
619619 (l) 20 DCMR § 5600.7 (fa ilure to ha ve specified person sign the UST facility
620620 notification form);
621621
622622 (m) 20 DCMR § 5600.8 (failure to provide timely notification following
623623 discovery of previously unknown UST);
624624
625625 (n) 20 DCMR § 5600.9 (failure to inform UST owner or lessee of notification
626626 requirements of 20 DCMR § 5600);
627627
628628 (o) 20 DCMR § 5600.10 (failure to ens ure proper certification of compliance
629629 with requirements of 20 DCMR § 5801 for upgrade or modification of
630630 UST system);
631631
632632 (p) 20 DCMR § 5601.7 (depositing a regulated substance into an UST without
633633 first confirming that current registration certificate is prese nt at facility and
634634 that facility is not on prohibited delivery list);
635635
636636 (q) 20 DCMR § 5601.8 ( dispensing or permitting dispensing of regulated
637637 substance from an UST that has not satisfied registration requirements);
638638
639639 (r) 20 DCMR § 5603.1 (failure to provide required advance written notice of
640640 each installation, removal, closure-in-place, repair, or upgrade of an UST
641641 system);
642642
643643 (s) 20 DCMR § 5603.2 (failure to provide notic e of the exact time and date of
644644 the installation, removal, closure-in-place, repair, or upgrade of an UST
645645 system at least 24 hours in advance to schedule site inspection);
646646
647647 (t) 20 DCMR § 5603.3 (failure to pro vide timely notice of emergency
648648 removal or repair to Department and Fire Chief);
649649
650650 (u) 20 DCMR § 5603.4 (failure to timely submit plans, design, and
651651 specifications for installation or upgrade of an UST system in accordance
652652 with 20 DCMR § 6500);
653653
654654 (v) 20 DCMR § 5603.5 (failure to obtain Department approval of plans,
655655 design, and specifications before applying for a co nstruction permit);
656656
657657 12
658658
659659
660660 (w) 20 DCMR § 5603.7 (failure to timely provide required notice of tank
661661 tightness test to Fire Chief in cases of suspected release);
662662
663663 (x) 20 DCMR § 5604.1 (failure to timely provide required notice of the
664664 existence or removal of any UST to p rospective buyer of real property);
665665
666666 (y) 20 DCMR § 5604.2 (failure to inform prospective buyers of commercial
667667 property of prior use of property that suggests the existence of an UST of
668668 which the seller has actual knowledge); or
669669
670670 (z) 20 DCMR § 5606.3 (third party inspector having a financial interest in the
671671 facility or UST system).
672672
673673 4008.6 In addition to §§ 4008.5, 4008.7, 4008.8, 4008.9, 4008.10, and 4008.11, violation
674674 of any of the following provisions shall be a Cl ass 2 infraction:
675675
676676 (a) 20 DCMR § 5700.7 (failure of each UST system located within 100 feet of
677677 a subsurface transit structure to meet the requirements of the District of
678678 Columbia Fire Prevention Code, the District of Columbia Municipal
679679 Regulations, and the National Fire Protection Association 130);
680680
681681 (b) 20 DCMR § 5700.10 (failure for the owner or operator of an UST that is
682682 more than 30 years old to remove the tank from the ground in accordance
683683 with 20 DCMR Chapter 61 within five (5) years of the regulations
684684 becoming effective);
685685
686686 (c) 20 DCMR § 5700.11 (failure of the ow ner or operator of an UST that is
687687 more than 30 years old to perform a tightness test within one (1) year of
688688 the date the regulations become effective and, in case of test failure, to
689689 remove the UST w ithin one (1) year from the date of the test);
690690
691691 (d) 20 DCMR § 5701.3 (failure to operate and maintain cathodic pr otection
692692 system in new petroleum UST, in accordance with 20 DCMR § 5901);
693693
694694 (e) 20 DCMR § 5701.4 (failure to meet requirements for design, constructio n,
695695 and installation of secondary containment systems in a new petroleum
696696 UST);
697697
698698 (f) 20 DCMR § 5701.5 (failure, if continuous monitoring methods are not
699699 used, to test each secondary containment system every three (3) years to
700700 ensure the interstitial area is liq uid-tight);
701701
702702 (
703703 g) 20 DCMR § 5701.6 (failure to meet requirements for design, construction,
704704 and installation of double -walled tanks in a new petroleum UST);
705705
706706
707707 13
708708
709709 (h) 20 DCMR § 5701.7 (failure to meet requirements for design, c onstruction,
710710 and installation of external li ner systems (including vaults) in a new
711711 petrole um UST);
712712
713713 (i) 20 DCMR § 5702.3 (failure to operate and maintain each cathod ic
714714 protection system in a hazardous substance UST system, in accordance
715715 with 20 DCMR § 5901);
716716
717717 (j) 20 DCMR § 5702.4 (failure to meet requirements for design, construction,
718718 and installation of double-walled tanks in a new hazardous substance
719719 UST);
720720
721721 (k) 20 DCMR § 5703.3 (failure to operate and maintain each cathodic
722722 protection system in a new heating oil UST system in accordance with 20
723723 DCMR § 5901);
724724
725725 (l) 20 DCMR § 5703.4 (failure to meet requirements for design, construction,
726726 and installation of secondary cont ainment systems in a new heating oil
727727 UST system);
728728
729729 (m) 20 DCMR § 5703.5 (failure, if continuous monitoring m ethods are not
730730 used, to test each secondary containment system every three years to
731731 ensure the inters titial area is liquid-tight in a new heating oil UST system);
732732
733733 (n) 20 DCMR § 5703.6 (failure to meet requirements for design, construction,
734734 and installation of double-walled tanks in a new heating oi l UST system);
735735
736736 (o) 20 DCMR § 5703.7 (failure to meet r equirements for design, construction,
737737 and installation of ext ernal liner systems (including vaults) in a new
738738 heating oil UST system);
739739
740740 (p) 20 DCMR § 5704.1 (failure of UST piping that is in contact with earth en
741741 materials to be designed, constructed, and protected from corros ion as
742742 specified);
743743
744744 (q) 20 DCMR § 5704.4 (failure to operate and maintain cathodic protection
745745 system in UST piping, in accordance with 20 DCMR § 5901);
746746
747747 (r) 20 DCMR § 5704.5 (failure to meet requiremen ts for design and
748748 construction of secondary containment systems in UST piping as set forth
749749 in 20 DCMR § 5701.4);
750750
751751 (s) 20 DCMR § 5705.3 (failure to use overfill prevention equipment that
752752 meets specified requirement s);
753753
754754
755755 14
756756
757757 (t) 20 DCMR § 5705.4 (using flow r estrictors in vent lines as the only method
758758 of overfill prevention when the overfill prevention is installed or replaced
759759 after the date the regulations become effective);
760760
761761 (u) 20 DCMR § 5705.5 (failure to use an automatic shutoff valve to comply
762762 with 20 DCMR § 5705.3 in tanks that are susceptible to over-
763763 pressurization);
764764
765765 (v) 20 DCMR § 5705.7 (failure of spill prevention equipment to have a
766766 minimum capacity of ten (10) gallons);
767767
768768 (w) 20 DCMR § 5706.1 (failure to install an UST system as s pecified);
769769
770770 (x) 20 DCMR § 5706.2 (failure to ensur e that each UST installation is
771771 performed by or supervised by an UST System Technician as set forth in
772772 20 DCMR Chapter 65);
773773
774774 (y) 20 DCMR § 5706.3 (failure to complete all work listed in the
775775 manufacturer’s installation checklist for each UST installation); or
776776
777777 (z) 20 DCMR § 5706.4 (failure to submit a soil sampling report before
778778 installation and obtain inspection and approval by the Department prior to
779779 placement of backfill for completion of installation).
780780
781781 4008.7 In addition to §§ 4008.5, 4008.6, 4008.8, 4008.9, 4008.10, and 4008.11, violation
782782 of any of the following provisions shall be a Class 2 infraction:
783783
784784 (a) 20 DCMR § 5706.5 (failure to perform a tank tightness test upon
785785 installation of an UST system prior to its use);
786786
787787 (b) 20 DCMR § 5801.5 (failure, if internal lining is the sole method of
788788 corrosion protection for an UST, to inspect the lining at least once a year
789789 for the conditions listed in 20 DCMR § 5801.4(a)-(c));
790790
791791 (c) 20 DCMR § 5801.6 (failure to follow specified requirements for tank
792792 linings that have failed inspections);
793793
794794 (d) 20 DCMR § 5802.1 (failure to cathodi cally protect metal piping that is in
795795 contact with earthen materials, i n accordance with code of practice);
796796
797797 (e) 20 DCMR § 5802.2 (failure to cathodically protect metal piping that is in
798798 contact with earthen materials, in accordance with requirements of 20
799799 DCMR §§ 5704.3 and 5704.4);
800800
801801 (
802802 f) 20 DCMR § 5802.3 (failure to re place metal piping that is in contact with
803803 earthen materials that does not meet the requirements of 20 DCMR §§
804804
805805 15
806806
807807 5802.1 and 5802.2, with new piping that s atisfies the requirements of 20
808808 DCMR § 5704);
809809
810810 (g) 20 DCMR § 5804.1 (failure to perform a tank tightness test as set forth in
811811 20 DCMR § 6007 upon completion of an UST system upgrade and prior
812812 to placing the UST sy stem in operation);
813813
814814 (h) 20 DCMR § 5900.1 (failure to ensure that releases due to spilling or
815815 overfilling do not occur and to follow an approved co de of practice);
816816
817817 (i) 20 DCMR § 5900.2 (failure to ensure that the available tank volume is
818818 greater than the volume of product to be transferred to the tank befo re
819819 each transfer is made);
820820
821821 (j) 20 DCMR § 5900.3 (failure to ensure that each transfer operation is
822822 monitored constantly to prevent overfilling or spilling and is performed in
823823 accordance with the UST manufacturer’s specificat ions);
824824
825825 (k) 20 DCMR § 5900.4 (failure to hold de livery nozzles open manually where
826826 product is transferred by means of pressurized delivery);
827827
828828 (l) 20 DCMR § 5900.5 (failure to install a visible and audible vent alarm
829829 device where product is transferred by means of pressurized delivery);
830830
831831 (m) 20 DCMR § 5900.6 (failure to discontinue delivery where vent alarm
832832 indicates an obstruction to the vent);
833833
834834 (n) 20 DCMR § 5900.7 (fa ilure to keep spill prevention equipment clean and
835835 dry);
836836
837837 (o) 20 DCMR § 5900.8 (failure to ensure that all fill lines for the UST system
838838 are clearly marked to indicate the size of tank and t ype of regulated
839839 substance in accordance with specified methods);
840840
841841 (p) 20 DCMR § 5900.9 (marking pipes or other openings in a way that could
842842 be associated with a regulated substance if they are not used for the
843843 transfer of that substance);
844844
845845 (q) 20 DCMR § 5900.11(a) (failure to comply, for UST systems in use on or
846846 before the date the U ST regulations become effective, with the regulations
847847 of 20 DCMR § 5900.12 through 15 no later than October 13, 2021);
848848
849849 (r) 20 DCMR § 5900.11(b) ( failure to comply, for UST systems brought into
850850 use after the UST regulations become effective, with t he regulations of 20
851851 DCMR § 5900.12 through 15 upon installation);
852852
853853
854854 16
855855
856856 (s) 20 DCMR § 5900.12 (failure to test all spill prevention equipment and
857857 containment sumps once every three (3) years for liquid tightness i n
858858 accordance with 20 DCMR § 5900.14);
859859
860860 (t) 20 DCMR § 5900.14 (fai lure to conduct liquid tightness tests in
861861 accordance with one of the criteria provided in § 5900.14);
862862
863863 (u) 20 DCMR § 5900.15 (failure to in spect ove rfill prevention equipment at
864864 least once eve ry three (3) years to ensure that overfill equipment will
865865 activate at the level specified in 20 DCMR § 5705.3);
866866
867867 (v) 20 DCMR § 5901.1 (failure of a steel tan k UST syst em or a steel -
868868 fiberglass-reinforced plastic composite UST system with corrosion
869869 protection to comply with requirements of 20 DCMR § 5901);
870870
871871 (w) 20 DCMR § 5901.2 (failure to operate and maintain each corrosion
872872 protection system to continuously provide corro sion protection);
873873
874874 (x) 20 DCMR § 5901.3 (failure to have cathodic protection system inspected
875875 by a qualified cathodic protection tester within six (6) months of
876876 installa tion and every three (3) years thereafter);
877877
878878 (y) 20 DCMR § 5901.4 (failure to conduct cathodic prot ection testing in
879879 accordance with criteria set forth in an approved code of practice); or
880880
881881 (z) 20 DCMR § 5901.5 (failure to inspect UST system with an impr essed
882882 current cathodic protection system every sixty ( 60) days).
883883
884884 4008.8 In addition to §§ 4008.5, 4008.6, 4008.7, 4008.9, 4008.10, and 4008.11, violation
885885 of any of the following provisions shall be a Class 2 infraction:
886886
887887 (a) 20 DCMR § 5901.6 (failure to maintain specified operational records of
888888 cathodic protection for an UST system, in accordance with 20 DCMR §
889889 5602);
890890
891891 (b) 20 DCMR § 5901.7 (failure to co nduct annual inspection of U STs that use
892892 internal lining as the sole method of corrosion protection in accordance
893893 with 20 DCMR § 5801.5);
894894
895895 (c) 20 DCMR § 5901.8 (failure to permanently c lose a UST that fails the
896896 annual inspection and cannot be repaired in accor dance with the closure
897897 processes of 20 DCMR § 6101);
898898
899899 (
900900 d) 20 DCMR § 5902.1 (failure to ensure that repairs to an UST system are
901901 made using the proper materials and techniques and that repairs will
902902 prevent releases);
903903
904904 17
905905
906906
907907 (e) 20 DCMR § 5902.2 (failure to follow a code of p ractice in complying with
908908 repair or replacement requirements for an UST system);
909909
910910 (f) 20 DCMR § 5902.5 (failure t o replace metal pipe sections or fittings that
911911 have released a regulated substance or that constitute a threat of release, in
912912 accordance with 20 DCMR § 5704);
913913
914914 (g) 20 DCMR § 5902.6 (failure to replace non-corrodible or fiberglass pipes
915915 and fittings, or flexible pipes that have released a regulated substance or
916916 that constitute a threat of release, in accordance with 20 DCMR § 5704);
917917
918918 (h) 20 DCMR § 5902.7 (failure to perform a tightness test in accordance with
919919 an approved code of practice within thirty (30) days of completing a repair
920920 to secondary containment or containment sumps used for interstitial
921921 monitoring and before pl acing the tank back in service );
922922
923923 (i) 20 DCMR § 5902.8 (failure to perform a tightness test in accordance with
924924 20 DCMR § 6007 within thi rty (30) days of completing a repair to a tank
925925 or piping and before placing the tank back in service);
926926
927927 (j) 20 DCMR § 5902.9 (fa ilure to test the cathodic protection system in
928928 accordance with 20 DCMR §§ 5901.3 through 5901.5 within six (6)
929929 months following repair);
930930
931931 (k) 20 DCMR § 5902.10 (failure to maintain repair records for ten ( 10) years,
932932 or for the remaining operating lif e of repaired UST, whichever is longer);
933933
934934 (l) 20 DCMR § 5902.11 (failure to ensure that an UST system repair is
935935 carried out or supervised by a certified UST System Technician);
936936
937937 (m) 20 DCMR § 5902.14 (failure to test or inspect spill or overfill equipment
938938 in accordance with 20 DCMR § 5900 within thirty (30) da ys of a repair);
939939
940940 (n) 20 DCMR § 5903.1 ( failure to use a n UST system that is made of or lined
941941 with materials that are compatible with the substance stored in the UST
942942 system);
943943
944944 (o) 2
945945 0 DCMR § 5903.3 (failure to demonstr ate compatibility between a UST
946946 system and the regulated substance it contains);
947947
948948 (p) 20 DCMR § 5904.1 (failure to conduct a walkthrough inspection no later
949949 than October 13, 2021);
950950
951951 (q) 20 DCMR § 5904.2 (failure to conduct walkthrough inspections every
952952 thirty (30) days in accordance with specified requirements);
953953
954954 18
955955
956956
957957 (r) 20 DCMR § 5904.3 (failure to conduct annual walkthrough inspections in
958958 accordance with specified requirements);
959959
960960 (s) 20 DCMR § 6000.4 (failure to complete closure requirements of 20
961961 DCMR Chapter 61 when release detection method in compliance with 20
962962 DCMR Chapter 60 cannot be applied);
963963
964964 (t) 20 DCMR § 6000.12 (failure to notify Department within twenty-four (24)
965965 hours and to comply with temporary closure requirements of 20 DCMR §
966966 6100 if release detection system is not repaired or replaced within forty-
967967 five (45) day s of improper performance);
968968
969969 (u) 20 DCMR § 6000.14 ( failure to operate and maintain the release detectio n
970970 system and test electronic and mechanical components in accordance with
971971 approved criteria);
972972
973973 (v) 20 DCMR § 6002.3 (failure to check seconda ry containment systems for
974974 evidence of a release at least ev ery thirty (30) days);
975975
976976 (w) 20 DCMR § 6002.4 (failure to test the secondary containment system
977977 every three (3) years to ensure the interstitial area is liquid-tight, or to use
978978 continuous monitoring methods);
979979
980980 (x) 20 DCMR § 6003.3 (failure to monitor tanks for re leases at least once
981981 every thirty (30) days using specified methods);
982982
983983 (y) 20 DCMR § 6003.6 (failure of owner or operator of a petroleum UST,
984984 excepting those exempted, to check for evidence of a release at least onc e
985985 every thirty (30) days using interstitial m onitoring); or
986986
987987 (z) 20 DCMR § 6003.7 ( failure to test the secondary containment system
988988 every three (3) years to ensure the interstitial area is liquid-tight, or to use
989989 continuous monitoring methods).
990990
991991 4008.9 In addition to §§ 4008.5, 4008.6, 4008.7, 4008.8, 4008.10, and 4008.11, violation
992992 of any of the following provisions shall be a Class 2 infraction:
993993
994994 (a) 20 DCMR § 6004.1 (failure to regularly monitor petroleum UST system
995995 underground piping, in accordance with 20 DCM R § 6004);
996996
997997 (
998998 b) 20 DCMR § 6004.4 (failure to use automatic line leak detectors that meet
999999 specified standards);
10001000
10011001
10021002 19
10031003
10041004 (c) 20 DCMR § 6004.5 (failure to annually test for the proper operation of the
10051005 automatic line leak detector in accordance with the manufacturer’s
10061006 instructions);
10071007
10081008 (d) 20 DCMR § 6004.6 (failure to perform an annual line tightness test for
10091009 underground piping that conveys regulated substances under pressure, in
10101010 accordance with 20 DCMR § 6004.8, or to conduct monthly monitoring of
10111011 piping, in accordance with 20 DCM R § 6004.10);
10121012
10131013 (e) 20 DCMR § 6004.7 (failure to per form a line tightness test every three (3)
10141014 years for underground pipi ng that conveys regulated substances under
10151015 suction, in accordance with 20 DCMR § 6004.8, or to c onduct monthly
10161016 monitoring of piping, in accord ance with 20 DCMR § 6004.10);
10171017
10181018 (f) 20 DCMR § 6004.11 (failure to check secondary containment systems on
10191019 underground pi ping installed or replaced after February 8, 2007, for
10201020 evidence of a release at least every thirty (30) days using interstitial
10211021 monitoring );
10221022
10231023 (g) 20 DCMR § 6005.3 (failure to conduct product inventory control monthly
10241024 in specified manner);
10251025
10261026 (h) 20 DCMR § 6006.1 (failure to conduct manual tank gauging in accordance
10271027 with 20 DCMR § 6006);
10281028
10291029 (i) 20 DCMR § 6006.6 (fa ilure to follow requirements of 20 DCMR Chap ter
10301030 62 for a suspected release following a specified variation in liquid level
10311031 measurements);
10321032
10331033 (j) 20 DCMR § 6013.6 (failure to comply with any conditions imposed by the
10341034 Department upon approval of an alternative release detection method);
10351035
10361036 (k) 20 DCMR § 6100.2 (failure to comply with the requirements of 20 DCM R
10371037 § 6100 when an UST system is temporarily closed);
10381038
10391039 (l) 20 DCMR § 6100.6 (failure to empty UST of product in accordance with
10401040 20 DCMR § 6100.9 during temporary closure of UST sy stem);
10411041
10421042 (m) 20 DCMR § 6100.7 (failu re to comply with release detection requirements
10431043 in accordan ce with 20 DCMR Chapter 60 during temporary closure of
10441044 UST system);
10451045
10461046 (n) 20 DCMR § 6100.9(a) -(c) (failure to empty UST system, open vent lines,
10471047 and cap and secure all other lines, pumps, manways and ancillary
10481048 equipment within ni nety (90) days after an UST system is temporarily
10491049 closed);
10501050
10511051 20
10521052
10531053
10541054 (o) 20 DCMR § 6100.9(d) (fa ilure to submit required contractor certification
10551055 form within seven (7) days after completing requirements for temporary
10561056 closure of an UST system);
10571057
10581058 (p) 20 DCMR § 6101.1 (failure to comply with 20 DCMR § 6101 when an
10591059 UST system is permanently closed or undergoes a change-in-service);
10601060
10611061 (q) 20 DCMR § 6101.2 (failure to submit UST activity notification form no
10621062 less than two (2) weeks before beginning a permanent closure or a change-
10631063 in-service);
10641064
10651065 (r) 20 DCMR § 6101.4 (fai lure to properly empty and clean the tank prior to
10661066 each change-in-service);
10671067
10681068 (s) 20 DCMR § 6101.5 (failure to properly empty and clean UST system prior
10691069 to removing it from the ground);
10701070
10711071 (t) 20 DCMR § 6101.6 (failure to remove from the ground an UST system
10721072 that is t o be closed permanently, unless the Department grant s a variance
10731073 pursuant to 20 DCMR § 6101.7);
10741074
10751075 (u) 20 DCMR § 6101.9 (failure to empty, clean, and fill tank with an inert
10761076 solid material and comply with 20 D CMR § 5500.05 when a tank removal
10771077 variance is grante d);
10781078
10791079 (v) 20 DCMR § 6101.10 (failure to conduct a closure assessment of the
10801080 excavation zone prior to permanent closure or a change-of-service of an
10811081 UST system);
10821082
10831083 (w) 20 DCMR § 6101.11 (failure to consider specified factors when selecting
10841084 sample types, sample locations, and measurement methods for the closure
10851085 assessment and to comply with other requirements of the Department for
10861086 number of samples or location of borings or wells);
10871087
10881088 (x) 20 DCMR § 6101.15 (failure to eva luate the excavation zone in
10891089 accordance with specified requirements in the case of a release of a
10901090 regulated substance);
10911091
10921092 (y) 20 DCMR § 6101.16 (failure to submit a closure assessm ent report,
10931093 including a closure not ification form, within thirty (30) days after
10941094 completing the permanent closure or change-in-service); or
10951095
10961096 (z) 20 DCMR § 6102 (failure to assess the excavation zone and properly close
10971097 an UST system that was previously closed -in-place, removed, or
10981098 temporarily closed, as directed).
10991099
11001100 21
11011101
11021102
11031103 4008.10 In addition to §§ 4008.5, 4008.6, 4008.7, 4008.8, 4008.9, and 4008.11, violation
11041104 of any of the following provisions shall be a Class 2 infraction:
11051105
11061106 (a) 20 DCMR § 6202.3 (failure to include required information in notification
11071107 of release or suspected release) ;
11081108
11091109 (b) 20 DCMR § 6203.6 (failure to consider appropriate selection factors and
11101110 to comply with Departmental directives and protocols for s ample types,
11111111 sample locations, and measurement methods);
11121112
11131113 (c) 20 DCMR § 6203.12 (failure to condu ct initial site assessment to evaluate
11141114 on-site conditions in accordance with specified requirements and any
11151115 applicable protocols of the Department);
11161116
11171117 (d) 20 DCMR § 6205.4 (failure to conduct site assessment activities in
11181118 accordance with an appropriate health a nd safety plan and make plan
11191119 available for inspection);
11201120
11211121 (e) 20 DCMR § 6207.12 (failure to provide the D epartment with an
11221122 opportunity to inspect the site at i ts request prior to implementation of the
11231123 Corrective Action Plan);
11241124
11251125 (f) 20 DCMR § 6210.8 (failure to remove all equipment, drums, and waste
11261126 and ensure that all wells are properly abandoned within six (6) months
11271127 following notice of no further action or case closure);
11281128
11291129 (g) 20 DCMR § 6301.4 (failure to submit records, documents, or other
11301130 information within twenty (20) days of a request, or other t ime frame
11311131 specified by the Department);
11321132
11331133 (h) 20 DCMR § 6500.1 ( failure of any individual who performs UST system
11341134 activities in the District to be a certified or to be supervised on-site by a
11351135 certified individual );
11361136
11371137 (i) 20 DCMR § 6500.2 (failure of individua l performing or supervising UST
11381138 installation, upgrade, retrofit, or repair to be a certified UST System
11391139 Technician);
11401140
11411141 (j) 20 DCMR § 6500.3 (failure of individual performing or supervising UST
11421142 system closure-in-place or removal to be a certified UST System
11431143 Technician or UST Closure Specialist);
11441144
11451145 (k) 20 DCMR § 6500.4 (failure of individual pe rforming a tightness test to be
11461146 a certified UST System Tester);
11471147
11481148
11491149 22
11501150
11511151 (l) 20 DCMR § 6500.5 (failure of an UST system owner or operator to ensure
11521152 that any UST system activity is performed by, or is sub ject to the
11531153 continuous on- site supervision of, a pe rson certified to perform or
11541154 supervise the activity under 20 DCMR Chapter 65);
11551155
11561156 (m) 20 DCMR § 6500.7 (failure of a business that performs UST system
11571157 activities in the District to be licensed by the Dep artment and to employ
11581158 individuals certified to perform each of the U ST system activities for
11591159 which the business is licensed);
11601160
11611161 (n) 20 DCMR § 6500.9 (transferring an UST system certification or license);
11621162
11631163 (o) 20 DCMR § 6502.1 (failure to designate at least one Class A, one Class B,
11641164 and one Class C operator for each act ive UST facility);
11651165
11661166 (p) 20 DCMR § 6502.2 (dispensing or storing a regulated substance when
11671167 Class A, B, and C operators have not been designated and trained as
11681168 required by 20 DCMR §§ 6502 and 6503);
11691169
11701170 (q) 20 DCMR § 6502.6 (failure of trained operators to be readily avai lable to
11711171 respond to suspected or confirmed releases, other unus ual operating
11721172 conditions, emergencies, or equipment failures);
11731173
11741174 (r) 20 DCMR § 6502.7 (failure to prominentl y display at the facility
11751175 emergency contact information and emergency procedures for users of
11761176 unmanned facilities);
11771177
11781178 (s) 20 DCMR § 6503.1 (failure to ensur e that all operators receive required
11791179 training and retraining);
11801180
11811181 (t) 20 DCMR § 6503.2 (failure of Class A and Class B operators for a
11821182 petroleum UST system to complete required retraining within thirty (30)
11831183 days of being notified that an UST system is out of compliance);
11841184
11851185 (u) 20 DCMR § 6503.3 (failure of Class A operator to complete required
11861186 training);
11871187
11881188 (v) 20 DCMR § 6503.4 ( failure of Class B operator to complete required
11891189 training);
11901190
11911191 (w) 20 DCMR § 6503.5 (failure of Class C operator to complete required
11921192 training);
11931193
11941194 (x) 20 DCMR § 6503.7 (failure to train a replacement Class A or B operator
11951195 within thirty (30) days of the operat or assuming duties);
11961196
11971197
11981198 23
11991199
12001200 (y) 20 DCMR § 6503.8 (failure to train Class C operators prior to assuming
12011201 duties as a Cl ass C operator); or
12021202
12031203 (z) 20 DCMR § 6503.9 (failure of training providers to obtain written
12041204 approval from the Department prior to delivering training courses for
12051205 Class A, B, and C operators).
12061206
12071207 4008.11 In addition to §§ 4008.5, 4008.6, 4008.7, 4008.8, 4008.9, 4008.10, and 4008.12,
12081208 violation of any of the fo llowing provisions shall be a Class 2 infraction:
12091209
12101210 (a) 20 DCMR § 6503.10 (failure to maintain documentation that designated
12111211 Class A, B, and C operators h ave received the required training and
12121212 retraining for as lo ng as they remain designated);
12131213
12141214 (b) 20 DCMR § 6700.8 (failure to immediately file a c ertification of financial
12151215 responsibility for an existing UST in accordance with 20 DCMR §
12161216 5500.4);
12171217
12181218 (c) 20 DCMR § 6700.9 (failure to file a certification of financ ial
12191219 responsib ility with the Department within thirty (30) days after installation
12201220 of a new UST or changing the substance stored to petroleum);
12211221
12221222 (d) 20 DCMR § 6700.10 (failure to demonstrate minimu m required per-
12231223 occurrence amount of financial responsibility for specified petroleum
12241224 USTs);
12251225
12261226 (e) 20 DCMR § 6700.11 (failure to demons trate minimum required per-
12271227 occurrence amount of financial responsibility for petroleum USTs not
12281228 covered by 20 DCM R § 6700.10);
12291229
12301230 (f) 20 DCMR § 6700.12 (failure to demonstrate minimum required annual
12311231 aggregate amount of financial responsibility);
12321232
12331233 (g) 20 DCMR § 6700.16 (fai lure to meet new financial responsibility
12341234 requirements on anniversary of effective date of f inancial responsibility
12351235 mechanism, following acquisition or installation of additional USTs);
12361236
12371237 (h) 20 DCMR § 6701.1 (failure to utilize mechanism(s) listed in 20 DCMR §§
12381238 6703 through 6710 to demonstrate financial responsibility);
12391239
12401240 (i) 20 DCMR § 6701.6 (failure to obtain alternate assurance of financial
12411241 responsibility within thirty (30) days after the own er receives notice of any
12421242 condition set forth in 20 DCMR § 6701.6(a) -(d));
12431243
12441244
12451245 24
12461246
12471247 (j) 20 DCMR § 6701.7 (failure to update certification of financial
12481248 responsibility within thi rty (30) days of change in financial assurance
12491249 mechanism);
12501250
12511251 (k) 20 DCMR § 6702.8 (failure to s ubmit current evidence of financial
12521252 responsibility within thirty (30) days after identifying an UST release
12531253 required to be reported under 20 DCMR § 6201 or § 6202);
12541254
12551255 (l) 20 DCMR § 6702.9 (failure to submit current evidence of financial
12561256 responsibility within thirty (30) days af ter receiving notice of the
12571257 incapacity of a pro vider of assurance under 20 DCMR § 6701.6);
12581258
12591259 (m) 20 DCMR § 6702.10 (failure to submit evidence of financial assurance or
12601260 other relevant information as required by the Department);
12611261
12621262 (n) 20 DCMR § 6703.4 (failure to obtain alternative assurance within
12631263 specified time period whe n no longer meeting requirements of financial
12641264 tests of self-insurance set forth in 20 DCMR §§ 6704 or 6705);
12651265
12661266 (o) 20 DCMR § 6703.5 (failure to provide reports of financial condition as
12671267 required by Department or failure to timely obtain alternate assura nce
12681268 following notification by Department );
12691269
12701270 (p) 20 DCMR § 6703.6 (failure to notify the Department of the failure to
12711271 timely obtain alternate assurance as required under 20 DCMR §§ 6703.4
12721272 or 6703.5);
12731273
12741274 (q) 20 DCMR § 6706.1 (failure to comply with criteria in 20 DCMR § 6706
12751275 when obtaining a guarantee to meet financial responsibility requirements
12761276 of 20 DCMR § 6700);
12771277
12781278 (r) 20 DCMR § 6707.1 (failure to comply with requirements of 20 DCMR §
12791279 6707 when obtaining liability insurance to meet financial responsibility
12801280 requirements of 20 DCMR § 6700);
12811281
12821282 (s) 20 DCMR § 6708.1 (failure to comply with requirements of 20 DCMR §
12831283 6708 when obtai ning a surety or performance bond to mee t financial
12841284 responsibility requirements of 20 DCMR § 6700);
12851285
12861286 (t) 20 DCMR § 6709.1 (failure to comply with requirements of 20 DCMR §
12871287 6709 when obtaining a letter of credit to meet financial responsibility
12881288 requirements of 20 DCMR § 6700);
12891289
12901290 (u) 20 DCMR § 6710.1 (failure to comply with requirements of 20 DCMR §
12911291 6710 when establishing a trust fund to meet financial responsibilit y
12921292 requirements of 20 DCMR § 6700);
12931293
12941294 25
12951295
12961296
12971297 (v) 20 DCMR § 6714.4 (failure to send a copy of each notice of cancellation
12981298 or termination of financial assurance to the Department in accordance with
12991299 20 DCMR § 5500.4 at the same time that notice is sent to the owner);
13001300
13011301 (w) 20 DCMR § 6714.5 (failure to obtain alternative financial assurance
13021302 coverage within sixty (60) days after receipt of notice of cancellation or
13031303 non-renewal of financial assurance);
13041304
13051305 (x) 20 DCMR § 6714.6 (failure to submit notification and required
13061306 information following the failure to obtain alternate coverage within sixty
13071307 (60) days after receipt of a notice of termination);
13081308
13091309 (y) 20 DCMR § 6715.1 (failure to provi de proper and timely notification of
13101310 commence ment of bankruptcy proceedings and to submit appropria te
13111311 forms listed in 20 DCMR §§ 6702.4 through 6702.7 documenting
13121312 financial responsibility); or
13131313
13141314 (z) 20 DCMR § 6715.5 (failure to provide notification of failure to obtain
13151315 alternate coverage within thirty (30) days af ter notification of bankruptcy
13161316 or incapacity).
13171317
13181318 4008.12 In addition to §§ 4008.13, 4008.14, 4008.15, and 4008.16, violation of any of the
13191319 following provisions shall be a Class 3 infraction:
13201320
13211321 (a) 20 DCMR § 5502.3 (failure to maintain records demonstrating compliance
13221322 for systems exempted from corrosion protection requirements);
13231323
13241324 (b) 20 DCMR § 5601.1 (failure to register an UST in accordance with 20
13251325 DCMR § 5601);
13261326
13271327 (c) 20 DCMR § 5601.5 (failure to renew the registra tion for each UST before
13281328 November 30 of each calendar year);
13291329
13301330 (d) 20 DCMR § 5601.10 (failure of seller of UST to provide requi red
13311331 notifications);
13321332
13331333 (e) 20 DCMR § 5602.2 (failure to provide information under 20 DCMR §§
13341334 5602.1(b), (c), (d), and (f), 6204.7, and 6205.3 to the Dist rict Fire Chief);
13351335
13361336 (f) 20 DCMR § 5602.3 (failur e to maintain specified records and information
13371337 at the UST fa cility);
13381338
13391339 (g) 20 D
13401340 CMR § 5602.4 (failure to maintain specified records for required
13411341 period and have records immediately available for inspection);
13421342
13431343
13441344 26
13451345
13461346 (h) 20 DCMR § 5602.5 (failure to keep records required under 20 DCMR §
13471347 5602.3(d) either at the UST location or at another location where the
13481348 records can be viewed by a person in the District);
13491349
13501350 (i) 20 DCMR § 5602.6 (f ailure to deliver permanent closure records that
13511351 cannot be kept at the facility or an alt ernative location in the District to the
13521352 Department);
13531353
13541354 (j) 20 DCMR § 5602.7 (failure to maintain records for required period);
13551355
13561356 (k) 20 DCMR § 5603.6 (failure to provide notic e at least twenty-four hours in
13571357 advance of the time an d date of any tank tightness test);
13581358
13591359 (l) 20 DCMR § 5706.6 (failure to ensure that UST System Technici an
13601360 completes certification of compliance on UST notification form);
13611361
13621362 (m) 20 DCMR § 5801.1 (failure to upgrade steel tanks in accordance with an
13631363 approved code of practice);
13641364
13651365 (n) 20 DCMR § 5801.2 (failure t o submit plans and obtain approval from the
13661366 Department before upgradin g an existing tank to stage I vapor recovery);
13671367
13681368 (o) 20 DCMR § 5801.3 (failure to comply with specified requirements for
13691369 upgrading an UST by internal lining);
13701370
13711371 (p) 20 DCMR § 5801.4 (failure to inspect the interior of a lined tank within
13721372 ten (10) years after lining or every five (5) years thereafter, in order to
13731373 ensure the lining is structurally sound, fr ee of corrosion holes, and
13741374 performing in accordance with original design specifications);
13751375
13761376 (q) 20 DCMR § 5801.7 (upgrading a tank by cathodic protection without
13771377 meeting the requirements of 20 DCMR § § 5701.2 and 5701.3, and without
13781378 following specified methods for ensuring the integrity of the ta nk);
13791379
13801380 (r) 20 DCMR § 5801.8 (upgrading a tank by both internal l ining and cathodic
13811381 protection without meeting the requirements of 20 DC MR §§ 5902,
13821382 5701.2, and 5701.3);
13831383
13841384 (s) 20 DCMR § 5902.12 (failure to ensure that certified UST System
13851385 Technician completes certification of compliance on UST notification
13861386 form);
13871387
13881388 (t) 2
13891389 0 DCMR § 5903.2 ( failure to notify the Department at least thi rty (30)
13901390 days prior to changing the product stored in a UST to a regulated
13911391 substance containing greater than ten percent (10%) ethanol or greater
13921392 than twenty percent (20%) biodiesel);
13931393
13941394 27
13951395
13961396
13971397 (u) 20 DCMR § 5903.4 (failure to maintain records of compliance with 20
13981398 DCMR §§ 5903.2 and 5903.3 when storing regulated substances);
13991399
14001400 (v) 20 DCMR § 5904.6 (failure to prepare required records following a
14011401 walkthrough inspection);
14021402
14031403 (w) 20 DCMR § 5904.7 (failure to maintain records of walkthrough
14041404 inspections for ten (10) ye ars);
14051405
14061406 (x) 20 DCMR § 6000.6 ( failure to install, calibrate, operate, and maintain
14071407 each release detection system in accordance with the manufacturer’s
14081408 instructions);
14091409
14101410 (y) 20 DCMR § 6000.8 (failure to provide written performance claims before
14111411 installing a release detection system); or
14121412
14131413 (z) 20 DCMR § 6001.1 (failure to properly maintain records demonstrating
14141414 compliance with 20 DCMR Chapter 60).
14151415
14161416 4008.13 In addition to §§ 4008.12, 4008.14, 4008.15, and 4008.16, violation of any of the
14171417 following provisions shall be a Class 3 infraction:
14181418
14191419 (a) 20 DCMR § 6001.2 (failure to maintain for at least ten ( 10) years written
14201420 performance claims for release detection systems);
14211421
14221422 (b) 20 DCMR § 6001.3 (failure to maintain for at least ten (10) years the
14231423 results of any sampling, testing, or monitoring conducted under 20 D CMR
14241424 Chapter 60);
14251425
14261426 (c) 20 DCMR § 6001.4 (failure to retain results of tank tightness testing until
14271427 the next te st of the UST system);
14281428
14291429 (d) 20 DCMR § 6001.5 (failure to maintain written documentation of all
14301430 calibration, maintenance, and repai r of release detection equipment for at
14311431 least three (3) years);
14321432
14331433 (e) 20 DCMR § 6001.6 (failure to retain for at least ten ( 10) years all
14341434 schedules of required calibration and ma intenance provided by the release
14351435 detection equipment manufacturer);
14361436
14371437 (f) 20 DCMR § 6001.7 (failure, after October 13, 2021, of an owner or
14381438 operator using groundwater or vapor monitoring to maintain records
14391439 signed by a qualified professional of site assessments conducted pursuant
14401440 to 20 DCMR §§ 6009.7 or 6010.7);
14411441
14421442
14431443 28
14441444
14451445 (g) 20 DCMR § 6005.3 (failure to conduct product inventory control monthly
14461446 in the manner specified in 20 DCMR § 6005.3(a) -(f));
14471447
14481448 (h) 20 DCMR § 6006.3 (failure to conduct manual tank gauging weekly);
14491449
14501450 (i) 20 DCMR § 6006.4 (failure to properly take tank liquid l evel
14511451 measurements and record measur ements on approved form);
14521452
14531453 (j) 20 DCMR § 6006.5 (failure to use proper manual tank gauging
14541454 equipment);
14551455
14561456 (k) 20 DCMR § 6007.3 (failure to us e a tank tightness test that meets
14571457 specified requirements);
14581458
14591459 (l) 20 DCMR § 6008.1 (failure to use automatic tank gauging equipment that
14601460 meets requirements of 20 DCM R § 6008);
14611461
14621462 (m) 20 DCMR § 6008.2 (failure to ensure proper installation of tank gauging
14631463 probe);
14641464
14651465 (n) 20 DCMR § 6008.3 (failure to use automatic product level monitor test
14661466 that meets specified requirements);
14671467
14681468 (o) 20 DCMR § 6008.4 (failure to install tanks horizontally without tank tilt if
14691469 automatic tank gauging is used);
14701470
14711471 (p) 20 DCMR § 6008.5 (failure to inspect automatic tank gauging system at
14721472 least every thirty (30) days);
14731473
14741474 (q) 20 DCMR § 6008.6 (failure of automatic tank gauging equipment to m eet
14751475 the inventory control requirements of 20 DCMR § 6005.3);
14761476
14771477 (r) 20 DCMR § 6008.7 (failure of the owner or operator to test for loss of
14781478 product using one of the provided modes);
14791479
14801480 (s) 20 DCMR § 6009.2 (fa ilure to use proper backfill materials);
14811481
14821482 (t) 20 DCMR § 6009.3 ( failure of stored regulated substance or tracer
14831483 compound to have sufficient volatility);
14841484
14851485 (u) 20 DCMR § 6009.4 (vapor measurement rendered inoperative or less
14861486 effective due to ground water, rainfall, soil moisture, or other known
14871487 interference);
14881488
14891489 (v) 20 DCMR § 6009.5 (ba ckground contamination in the excavation zone
14901490 interfering with the vapor monitoring method);
14911491
14921492 29
14931493
14941494
14951495 (w) 20 DCMR § 6009.6 (failure to use vapor monitor that is properly designed
14961496 and operated);
14971497
14981498 (x) 20 DCMR § 6009.7 (failure to a ssess the excavation zone as required
14991499 before using vapor monitoring);
15001500
15011501 (y) 20 DCMR § 6009.8 (failure to clearly and properly mark and secure
15021502 monitoring wells); or
15031503
15041504 (z) 20 DCMR § 6010.1 (failure to test and monitor for regulated substances in
15051505 the ground water or in the tank excavation zone in accorda nce with 20
15061506 DCMR § 6010).
15071507
15081508 4008.14 In addition to §§ 4008.12, 4008.13, 4008.15, and 4008.16, violation of any of the
15091509 following provisions shall be a Class 3 infr action:
15101510
15111511 (a) 20 DCMR § 6010.2 (failure of the regulated substan ce stored to be
15121512 immiscible in water and have a specific gravity of less than one);
15131513
15141514 (b) 20 DCMR § 6010.3 (ground water more than twenty (20) feet from the
15151515 ground surface or hydraulic conductivity of the soils less than one
15161516 hundredth of a centimeter per second (0.01 cm/sec) if testing or
15171517 monitoring for regulated substances in ground water);
15181518
15191519 (c) 20 DCMR § 6010.4 (failure to design slotted portion of monitoring well
15201520 casing to prevent migration of natural soils or filter pack into the well and
15211521 to allow entry of regulated substance on the water table into the well);
15221522
15231523 (d) 20 DCMR § 6010.5 (failure to seal monitoring wells from the ground
15241524 surface to the top of the filter pack);
15251525
15261526 (e) 20 DCMR § 6010.6 (failure of monitoring wells or devices to intercept the
15271527 excavation zone or be as close to the excavation zone as is technically
15281528 feasible);
15291529
15301530 (f) 20 DCMR § 6010.7 (failure to assess the excavation zone as required
15311531 before using groundwater monitoring) ;
15321532
15331533 (g) 20 DCMR § 6010.8 (failure to use continuous monitoring devices or
15341534 manual methods capable of detecting at least one eighth (1/8) inch of free
15351535 regulated substan ce);
15361536
15371537 (h) 20 DCMR § 6010.9 (failure to clearly mark and secure each monitoring
15381538 well to avoid unauthorized access or tampering);
15391539
15401540
15411541 30
15421542
15431543 (i) 20 DCMR § 6011.2 (failure of an owner or operator of a UST system
15441544 installed or replaced after February 8, 2007 to check for a releas e at least
15451545 once every thirty (30) days using interstitial monitoring);
15461546
15471547 (j) 20 DCMR § 6011.3 (failure to install an interstitial monitoring system that
15481548 can detect a leak from any portion of the tank or piping system that
15491549 routinely carries a regulated substance);
15501550
15511551 (k) 20 DCMR § 6011.4 (failure to properly maintain the vacuum in vacuum
15521552 monitoring);
15531553
15541554 (l) 20 DCMR § 6011.5 (failure to follow the requirements of 20 DCM R
15551555 Chapter 62 if vacuum falls below five (5) inches of mercury);
15561556
15571557 (m) 20 DCMR § 6011.6 (failure to gain prior De partment approval before re-
15581558 instituting a vacuum more frequently than once every three (3) months);
15591559
15601560 (n) 20 DCMR § 6011.7 (failure to use sampling or testing method for a
15611561 double-walled UST sys tem capable of detect ing a release through the
15621562 inner wall);
15631563
15641564 (o) 20 DCMR § 6011.8 (failure to use an automated device capable of
15651565 detecting a release between the inner wall and the internally fitted liner
15661566 and to use a liner that is compatible with the substance stored);
15671567
15681568 (p) 20 DCMR § 6011.9 (failure of secondary barrier within the excavation
15691569 zone to meet specified requirements);
15701570
15711571 (q) 20 DCMR § 6011.10 (failure to use sampling or testing method capable of
15721572 detecting a release between the UST system and the secondary ba rrier
15731573 within the excavation zone);
15741574
15751575 (r) 20 DCMR § 6011.11 (use of testing or sampling method that is rendered
15761576 inoperative or less effective due to ground water, rainfall, soil moisture, or
15771577 other known interference );
15781578
15791579 (s) 20 DCMR § 6011.12 (failure to assess the si te for an UST system with a
15801580 secondary barrier within the excavation zone to ensure that the secondary
15811581 barrier is always above the groundwater and not in a twenty- five (25) year
15821582 floodplain);
15831583
15841584 (t) 2
15851585 0 DCMR § 6011.13 ( failure to clearly mark and secure monitoring w ells
15861586 for each UST system with a secondary barrier within the excavation zone
15871587 to avoid unauthorized access or tampering);
15881588
15891589
15901590 31
15911591
15921592 (u) 20 DCMR § 6011.15 (failure to repair, upgra de, or close a leaking inner or
15931593 outer tank wall or liner as specified in 20 DCMR § 6203);
15941594
15951595 (v) 20 DCMR § 6012.2 (failure to conduct monthly statistical inventory
15961596 reconciliation in accorda nce with 20 DCMR § 6012.2(a)-(c));
15971597
15981598 (w) 20 DCMR § 6012.3 (failure to verify the accuracy of a statistical inventory
15991599 reconciliation method in accordance with 20 DCMR §§ 6012.2 and
16001600 6000.9);
16011601
16021602 (x) 20 DCMR § 6012.4 (failure to obta in independent third party certification
16031603 that a statistical inventory reconciliation method is accurate and maintain
16041604 evaluation records for te n (10) ye ars);
16051605
16061606 (y) 20 DCMR § 6100.5 (failure to submit temporary closure notification form
16071607 at least thirty (30) days before an UST system is temporarily closed); or
16081608
16091609 (z) 20 DCMR § 6100.10 (failure to permanently close an UST system in
16101610 accordance with 20 DCMR § 6101 after an UST system has been
16111611 temporarily closed for twelve (12) months).
16121612
16131613 4008.15 In addition to §§ 4008.12, 4008.13, 4008.14, and 4008.16, violation of any of the
16141614 following provisions shall be a Class 3 infractio n:
16151615
16161616 (a) 20 DCMR § 6103.1 (failure to maintain re cords of compliance with
16171617 closure requirements in accordance with 20 DCMR § 5602);
16181618
16191619 (b) 20 DCMR § 6103.2 (failure t o properly maintain closu re assessment
16201620 results for at least ten ( 10) years after completion of permanent closure or
16211621 change-in-service);
16221622
16231623 (c) 20 DCMR § 6103.3 (failure to deliver records demonstrating comp liance
16241624 with 20 DCMR Chapter 61 to the Department after ten (10) years);
16251625
16261626 (d) 20 DCMR § 6203.14 (failure to submit initial site a ssessment report and
16271627 any applicable monthly status report within s ixty (60) days after release
16281628 confirmation, or failure to submit a wo rk plan for future site activities);
16291629
16301630 (
16311631 e) 20 DCMR § 6204.7 (failure to prepare and submit a status report on the
16321632 removal of any free product in accordance with 20 DCMR § 5500.4);
16331633
16341634 (f) 20 DCMR § 6204.8 (failure to submi t a status report within sixty (60) days
16351635 of release confirmation and then once every quarter until the Depar tment
16361636 determines the free product removal is complete);
16371637
16381638
16391639 32
16401640
16411641 (g) 20 DCMR § 6207.13 (failure to monitor, evaluate, and timely report the
16421642 results of corrective action pla n implementation);
16431643
16441644 (h) 20 DCMR § 6207.16 (failure to evaluate the effectiveness of the corr ective
16451645 action plan at the end of each year of implementation);
16461646
16471647 (i) 20 DCMR § 6210.2 (failure to maintain for at least three (3) years all
16481648 records and reports documenting the transport and disposal of wastes
16491649 generated at an UST site while the c orrective action plan is being carried
16501650 out);
16511651
16521652 (j) 20 DCMR § 6500.6 (failure of certified UST System Technician, Closure
16531653 Specialist, or Tester to carry and make available for inspection the
16541654 identification card or ce rtificate issued by t he Department at all times
16551655 while conducting the applicable U ST activity);
16561656
16571657 (k) 20 DCMR § 6500.8 (failure of business licensed to perform UST system
16581658 activities to provide list of employees who are not certified but who
16591659 perform supervised on-site UST activities);
16601660
16611661 (l) 20 DCMR § 6500.10 (failure to surre nder certification or license to the
16621662 Department within ten (10) business days after closur e or termination of a
16631663 business);
16641664
16651665 (m) 20 DCMR § 6502.3 (failure of a Class A operator to meet all req uirements
16661666 or duties, as provided under 20 DCMR § 6502.3(a) -(c));
16671667
16681668 (n) 20 DCMR § 6502.4 (failure of a Class B operator to meet all requirements
16691669 or duties, as provided under § 6502.4(a)-(c));
16701670
16711671 (o) 20 DCMR § 6502.5 (failure of a Class C operator to meet all requirements
16721672 or duties, as provided under § 6502.5(a)-(c));
16731673
16741674 (p) 20 DCMR § 6502.9 (failure to maintain requir ed list of designated
16751675 operators);
16761676
16771677 (q) 20 DCMR § 6502.10 (failure to keep a copy of the requisite
16781678 documentation on site and available for inspection at the UST facility);
16791679
16801680 (r) 2
16811681 0 DCMR § 6502.11 (failure to conspicuously post Class C operator and
16821682 owner contact in formation at unstaffed facilities);
16831683
16841684 (s) 20 DCMR § 6702.1 (failure to maintain a copy of each financial assurance
16851685 mechanism until released from financial responsibility requirements under
16861686 20 DCMR § 6700.5 or § 6700.6);
16871687
16881688
16891689 33
16901690
16911691 (t) 20 DCMR § 6702.2 ( failure to make available to the Department upon
16921692 request, records of financial assurance maintained off-site);
16931693
16941694 (u) 20 DCMR § 6702.3 (failure to maintain a copy of the appropriate
16951695 assurance instrument in the prescribed form);
16961696
16971697 (v) 20 DCMR § 6702.4 (failure to maintain a c opy of chief financial officer’s
16981698 letter of assurance when using a financial test of self-insurance or
16991699 guarantee);
17001700
17011701 (w) 20 DCMR § 6702.5 (failure to maintain a copy of signed standby trus t
17021702 fund agreement when using a guarantee, surety bond, or letter of credit );
17031703
17041704 (x) 20 DCMR § 6702.6 (fa ilure to maintain a copy of signed insurance policy
17051705 or risk retention group coverage policy and endorsement or cert ificate of
17061706 insurance);
17071707
17081708 (y) 20 DCMR § 6702.7 (failure to maintain copy of certification of financial
17091709 responsibility in prescribed form); or
17101710
17111711 (z) 20 DCMR § 6706.4 (failure to properly demonstrate to the owner within
17121712 one hundred twenty (120) days after the close of each financial reporting
17131713 year that the guarantor meets the financial t est criteria of 20 DCMR §§
17141714 6704 or 6705).
17151715
17161716 4008.16 In addition to §§ 4008.12, 4008.13, 4008.14, and 4008.15, violation of any of the
17171717 following provisions shall be a Class 3 i nfraction:
17181718
17191719 (a) 20 DCMR § 6706.5 (failure to timely notify the owner by certified mai l
17201720 before cancellation or non-r enewal of the guarantee if the guarantor fails
17211721 to meet the requirements of the financial test at the end of any financial
17221722 reporting year);
17231723
17241724 (b) 20 DCMR § 6706.6 (failure to timely notify owner by certified mail if
17251725 guarantor no longer meets the requirements of the financial test of §§ 6704
17261726 or 6705 or 6703.3);
17271727
17281728 (c) 20 DCMR § 6711.1 (failure of an owner using any of the financi al
17291729 responsibility mechanisms authorized under 20 DCMR §§ 6706, 6708, or
17301730 6709 to establish a standby trust fund when the mechanism is acquired) ;
17311731
17321732 (
17331733 d) 20 DCMR § 6711.2 (failure of a standby trust fund to have trustee with
17341734 authority to act as a trustee and whose trust operations are regulated and
17351735 examined by an agency of the federal government or the District of
17361736 Columbia);
17371737
17381738
17391739 34
17401740
17411741 (e) 20 DCMR § 6711.3 (failure of standby trust agreement or trust agreement
17421742 to be in the prescribed form and accompanied by certification of
17431743 acknowledgement in the prescribed form);
17441744
17451745 (f) 20 DCMR § 6712.1 (failure to place funds in standby trust as required by
17461746 the Department);
17471747
17481748 (g) 20 DCMR § 6712.2 (failure to place funds in standby trust as required by
17491749 the Department);
17501750
17511751 (h) 20 DCMR § 6713.1 (failure to timely replenish the value of financial
17521752 assurance or acquire another financial assurance mechanism if amount in a
17531753 standby trust is reduced below full amount of coverage required);
17541754
17551755 (i) 20 DCMR § 6714.2 (termination of guarantee, surety bond, or letter of
17561756 credit prior to one hundred twenty (120) days following own er’s receipt of
17571757 notice of termination);
17581758
17591759 (j) 20 DCMR § 6714.3 (termination of insurance or risk retention group
17601760 coverage prior to sixty (60) days following owner’s receipt of notice of
17611761 termination or, in the case of non-pa yment of premiums or
17621762 misrepresentat ion, prior to ten (10) days following owner or operator’ s
17631763 receipt of notice of termination); or
17641764
17651765 (k) 20 DCMR § 6715.2 (failure of guarantor to provide proper and timely
17661766 notification to owner of bankruptcy proceeding as required under terms of
17671767 the guarantee specified in 20 DCMR § 6706).
17681768
17691769 4008.17 Violation of any of the following provisions shall be a Class 4 infract ion:
17701770
17711771 (a) 20 DCMR § 5601.6 (failure to pos t a copy of the current UST registration
17721772 certificate in a visible location at the facility at all times); or
17731773
17741774 (b) Violation of any provision of the District of Columbia Underground Tank
17751775 Management Act of 1990, effective March 8, 1991, as amended (D.C.
17761776 Law 8-242; D.C. Official Code §§ 8-113.01 to 8-113.12), or the District of
17771777 Columbia Underground Storage Tank Regulat ions, 20 DCMR Chapters
17781778 55-67, which is not cite d elsewhere in this section, shall be a Class 4