As Introduced 136th General Assembly Regular Session H. B. No. 139 2025-2026 Representative Hall, T. Cosponsors: Representatives Robb Blasdel, Williams, Johnson, Brennan, Santucci A B I L L To enact section 3737.834 of the Revised Code to require specified testing of fire hydrant systems. BE IT ENACTED BY THE GENERAL ASSEMBLY OF THE STATE OF OHIO: Section 1. That section 3737.834 of the Revised Code be enacted to read as follows: Sec. 3737.834. (A) The state fire marshal shall ensure that the inspection, testing, and maintenance of fire hydrant systems in the state are conducted in accordance with this section, the rules adopted as part of the state fire code, and the recommended standards by the national fire protection association. (B) The fire marshal shall require any person or entity responsible for maintaining a fire hydrant system to periodically test that system. Fire hydrant systems shall be maintained in an operative condition at all times and shall be repaired where defective. Additions, repairs, alterations, and servicing shall comply with all approved standards. Records of 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 H. B. No. 139 Page 2 As Introduced tests, repairs, and regular maintenance shall be retained for not less than one year after the subsequent test, repair, or maintenance, as applicable, and shall be available for inspection by the fire marshal. (C) At minimum, the fire hydrant systems and the associated service mains and water tanks shall be periodically inspected, tested, and maintained at the following intervals: (1) Fire hydrants of all types shall be inspected annually and after each operation. A flow test and general maintenance for the fire hydrant shall be conducted annually. (2) Fire service main piping shall be inspected annually and a flow test shall be conducted every five years. (3) Fire service main piping strainers shall be inspected and receive general maintenance care after each use. 18 19 20 21 22 23 24 25 26 27 28 29 30 31