Pennsylvania 2025-2026 Regular Session

Pennsylvania Senate Bill SB591 Latest Draft

Bill / Introduced Version

                             
PRINTER'S NO. 599 
THE GENERAL ASSEMBLY OF PENNSYLVANIA
SENATE BILL 
No.591 
Session of 
2025 
INTRODUCED BY DUSH, STEFANO AND FARRY, APRIL 9, 2025 
REFERRED TO TRANSPORTATION, APRIL 9, 2025 
AN ACT
Amending Title 74 (Transportation) of the Pennsylvania 
Consolidated Statutes, providing for installation of dry 
hydrants.
The General Assembly of the Commonwealth of Pennsylvania 
hereby enacts as follows:
Section 1.  Title 74 of the Pennsylvania Consolidated 
Statutes is amended by adding a chapter to read:
CHAPTER 97
INSTALLATION OF DRY HYDRANTS
Sec.
9701.  Definitions.
9702.  Dry hydrant installation required.
§ 9701.  Definitions.
The following words and phrases when used in this chapter 
shall have the meanings given to them in this section unless the 
context clearly indicates otherwise:
"Bridge."  A State-owned, new or existing bridge under the 
jurisdiction of the department.
"Department."  The Department of Transportation of the 
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19 Commonwealth.
"Historic resource."  A building or structure, including a 
covered bridge, which:
(1)  has been in existence for more than 100 years, 
including partial or complete reconstruction of a building or 
structure originally erected at least 100 years ago; or
(2)  has been listed on the National Register of Historic 
Places or the Pennsylvania Register of Historic Places.
"Occupied structure."  Any structure, vehicle or place 
adapted for overnight accommodation of an individual or for 
carrying on business within the structure, vehicle or place, 
whether or not an individual is actually present.
§ 9702.  Dry hydrant installation required.
(a)  Requirement.--If a bridge that crosses a body of water 
is built, modified or rehabilitated, the department shall 
install a dry hydrant if an installation site exists that meets 
all of the conditions specified under subsection (b) 	. 
(b)  Conditions.--The requirement imposed on the department 
under subsection (a) shall only apply if all of the following 
conditions are met:
(1)  The body of water in which the dry hydrant will be 
installed is able to provide 250 gallons per minute for a 
continuous two-hour period during a 50-year drought or freeze 
at a vertical lift of 18 feet.
(2)  The dry hydrant will be located within 25 feet of an 
all-weather roadway and will be accessible to fire protection 
equipment.
(3)  The dry hydrant will be located within 800 feet of 
at least one inhabited, occupied structure or historical 
resource.
20250SB0591PN0599 	- 2 - 
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30 (4)  The installation of the dry hydrant would improve 
the fire prevention or fire suppression capabilities of the 
community as determined by the Fire Suppression Rating 
Schedule or a similar criteria on the effective date of this 
paragraph.
(c)  Multiple locations.--If there are multiple locations 
that  meet all of the conditions specified under subsection (b) 	,  
the department shall install the dry hydrant at the location 
which is closest to the roadway.
Section 2.  This act shall take effect in 60 days.
20250SB0591PN0599 	- 3 - 
1
2
3
4
5
6
7
8
9
10