Utah 2025 2025 Regular Session

Utah House Bill HB0313 Substitute / Bill

Filed 02/26/2025

                    02-26 21:36	2nd Sub. (Gray) H.B. 313
Thomas W. Peterson proposes the following substitute bill:
1 
State Construction and Electrical Standards Amendments
2025 GENERAL SESSION
STATE OF UTAH
Chief Sponsor: Thomas W. Peterson
Senate Sponsor: Calvin R. Musselman
2 
 
3 
LONG TITLE
4 
General Description:
5 
This bill modifies the State Construction Code.
6 
Highlighted Provisions:
7 
This bill:
8 
▸ amends the State Construction Code to:
9 
● align with updated standards in the International Residential Code (IRC); and
10 
● align with the updated standards in the National Electric Code (NEC);
11 
▸ includes a coordination clause to make the amendments to Section 15A-3-202 in this bill
12 
supersede the amendments to Section 15A-3-202 in H.B. 175, Housing Construction
13 
Amendments; and
14 
▸ makes technical changes.
15 
Money Appropriated in this Bill:
16 
None
17 
Other Special Clauses:
18 
This bill provides a coordination clause.
19 
Utah Code Sections Affected:
20 
AMENDS:
21 
15A-2-103, as last amended by Laws of Utah 2024, Chapter 505
22 
15A-3-105, as last amended by Laws of Utah 2024, Chapter 505
23 
15A-3-202, as last amended by Laws of Utah 2024, Chapter 505
24 
15A-3-206, as last amended by Laws of Utah 2024, Chapter 505
25 
15A-3-601, as last amended by Laws of Utah 2024, Chapter 15
26 
Utah Code Sections affected by Coordination Clause:
27 
15A-3-202, as last amended by Laws of Utah 2024, Chapter 505
28 
 
29 
Be it enacted by the Legislature of the state of Utah:
2nd Sub. H.B. 313 2nd Sub. (Gray) H.B. 313	02-26 21:36
30 
Section 1.  Section 15A-2-103 is amended to read:
31 
15A-2-103 . Specific editions adopted of construction code of a nationally
32 
recognized code authority.
33 
(1) Subject to the other provisions of this part, the following construction codes are
34 
incorporated by reference, and together with the amendments specified in Chapter 3,
35 
Statewide Amendments Incorporated as Part of State Construction Code, and Chapter 4,
36 
Local Amendments Incorporated as Part of State Construction Code, are the
37 
construction standards to be applied to building construction, alteration, remodeling, and
38 
repair, and in the regulation of building construction, alteration, remodeling, and repair
39 
in the state:
40 
(a) the 2021 edition of the International Building Code, including Appendices C and J,
41 
issued by the International Code Council;
42 
(b) the 2021 edition of the International Residential Code, issued by the International
43 
Code Council;
44 
(c) Appendix AQ of the 2021 edition of the International Residential Code, issued by the
45 
International Code Council;
46 
(d) the 2021 edition of the International Plumbing Code, issued by the International
47 
Code Council;
48 
(e) the 2021 edition of the International Mechanical Code, issued by the International
49 
Code Council;
50 
(f) the 2021 edition of the International Fuel Gas Code, issued by the International Code
51 
Council;
52 
(g) the [2020] 2023 edition of the National Electrical Code, issued by the National Fire
53 
Protection Association;
54 
(h) the 2021 edition of the International Energy Conservation Code, issued by the
55 
International Code Council;
56 
(i) the 2021 edition of the International Existing Building Code, issued by the
57 
International Code Council;
58 
(j) subject to Subsection 15A-2-104(2), the HUD Code;
59 
(k) subject to Subsection 15A-2-104(1), Appendix AE of the 2021 edition of the
60 
International Residential Code, issued by the International Code Council;
61 
(l) subject to Subsection 15A-2-104(1), the 2005 edition of the NFPA 225 Model
62 
Manufactured Home Installation Standard, issued by the National Fire Protection
63 
Association;
- 2 - 02-26 21:36	2nd Sub. (Gray) H.B. 313
64 
(m) subject to Subsection (3), for standards and guidelines pertaining to plaster on a
65 
historic property, as defined in Section 9-8a-302, the U.S. Department of the Interior
66 
Secretary's Standards for Rehabilitation and Guidelines for Rehabilitating Historic
67 
Buildings;[ and]
68 
(n) the residential provisions of the 2021 edition of the International Swimming Pool
69 
and Spa Code, issued by the International Code Council; and
70 
(o) Modular Building Institute Standards 1200 and 1205, issued by the International
71 
Code Council, except as modified by provisions of this title governing modular units.
72 
(2) Consistent with Title 65A, Chapter 8, Management of Forest Lands and Fire Control,
73 
the Legislature adopts the 2006 edition of the Utah Wildland Urban Interface Code,
74 
issued by the International Code Council, with the alternatives or amendments approved
75 
by the Utah Division of Forestry, Fire, and State Lands, as a construction code that may
76 
be adopted by a local compliance agency by local ordinance or other similar action as a
77 
local amendment to the codes listed in this section.
78 
(3) The standards and guidelines described in Subsection (1)[(n) ] (m) apply only if:
79 
(a) the owner of the historic property receives a government tax subsidy based on the
80 
property's status as a historic property;
81 
(b) the historic property is wholly or partially funded by public money; or
82 
(c) the historic property is owned by a government entity.
83 
Section 2.  Section 15A-3-105 is amended to read:
84 
15A-3-105 . Amendments to Chapters 10 through 12 of IBC.
85 
(1) In IBC, Section 1010.2.4, number (2), the following is added at the end of the sentence:
86 
"Blended assisted living facilities shall comply with Section 1010.2.14.1."
87 
(2) A new IBC Section 1010.2.14.1 is added as follows: "1010.2.14.1 Blended assisted
88 
living facilities. In occupancy Group I-1, Condition 2 or Group I-2, a Type-II assisted
89 
living facility licensed by the Department of Health and Human Services for residents
90 
with Alzheimer's or dementia, and having a controlled egress locking system to prevent
91 
operation from the egress side shall be permitted to also house residents without a
92 
clinical need for their containment where all of the following provisions are met:
93 
(a) locks in the means of egress comply with all IBC requirements for controlled egress
94 
doors;
95 
(b) all residents without a clinical need for their containment shall have the keys, codes,
96 
or other means necessary to exit the facility, in a manner that is determined by the
97 
facility operator and communicated to the resident or their legal representative;
- 3 - 2nd Sub. (Gray) H.B. 313	02-26 21:36
98 
(c) residents or their legal representative acknowledge in writing that they understand
99 
and agree to living in a facility where egress is controlled; and
100 
(d) the number of residents housed in a smoke compartment with controlled egress shall
101 
not be greater than 30."
102 
(3) In IBC, Section 1011.5.2, exception 3 is deleted and replaced with the following: " 3.  In
103 
Group R-3 occupancies, within dwelling units in Group R-2 occupancies, and in Group
104 
U occupancies that are accessory to a Group R-3 occupancy, or accessory to individual
105 
dwelling units in Group R-2 occupancies, the maximum riser height shall be 8 inches
106 
(203 mm) and the minimum tread depth shall be 9 inches (229 mm).  The minimum
107 
winder tread depth at the walk line shall be 10 inches (254 mm), and the minimum
108 
winder tread depth shall be 6 inches (152 mm).  A nosing not less than 0.75 inch (19.1
109 
mm) but not more than 1.25 inches (32 mm) shall be provided on stairways with solid
110 
risers where the tread depth is less than 10 inches (254 mm)."
111 
(4) In IBC, Section 1011.11, a new exception 6 is added as follows: " 6.  In occupancies in
112 
Group R-3, as applicable in Section 101.2 and in occupancies in Group U, which are
113 
accessory to an occupancy in Group R-3, as applicable in Section 101.2, handrails shall
114 
be provided on at least one side of stairways consisting of four or more risers."
115 
(5) In IBC, Section 1025, is deleted.
116 
(6) In IBC, Section 1104.4, exception 1.5 is deleted.
117 
The following section is affected by a coordination clause at the end of this bill.
118 
Section 3.  Section 15A-3-202 is amended to read:
119 
15A-3-202 . Amendments to Chapters 1 through 5 of IRC.
120 
(1) In IRC, Section R101.2, Exception, the words "where provided with an automatic
121 
sprinkler system complying with Section P2904" are deleted.
122 
(2) In IRC, Section R101.2, Exception, the words "6. A triplex or fourplex of no more than
123 
two levels with 2-hour fire-resistance-rated vertical shared wall assemblies tested in
124 
accordance with ASTM E119 or UL263, 1-hour fire-resistance-rated horizontal floor
125 
assemblies tested in accordance with ASTM E119 or UL263, and independent egress for
126 
each unit." are added.
127 
[(2)] (3) In IRC, Section R102, a new Section R102.7.2 is added as follows: "R102.7.2
128 
Physical change for bedroom window egress.  A structure whose egress window in an
129 
existing bedroom is smaller than required by this code, and that complied with the
130 
construction code in effect at the time that the bedroom was finished, is not required to
131 
undergo a physical change to conform to this code if the change would compromise the
- 4 - 02-26 21:36	2nd Sub. (Gray) H.B. 313
132 
structural integrity of the structure or could not be completed in accordance with other
133 
applicable requirements of this code, including setback and window well requirements."
134 
[(3)] (4) In IRC Section R105.2, under Building, the following changes are made:
135 
(a) Number 3 is deleted and replaced with the following: "3. Retaining walls retaining
136 
less than 4 feet (1219mm) of unbalanced fill, unless supporting a surcharge or
137 
requiring design per Section R404.4."
138 
(b) Number 10 is deleted and replaced with the following: "10. Decks that are not more
139 
than 30 inches (762mm) above grade at any point and not requiring guardrails, that
140 
do not serve exit door required by Section R311.4."
141 
[(4)] (5) In IRC, Section R105.2, a new exception is added: "11. Grade level, non-connected
142 
conex boxes, less than 350 square feet, used for storage only."
143 
[(5)] (6) In IRC, Section R108.3, the following sentence is added at the end of the section:
144 
"The building official shall not request proprietary information."
145 
[(6)] (7) In IRC, Section 109.1.5, is deleted and replaced with the following: "R109.1.5
146 
Other inspections. In addition to the inspections listed in R109.1.1 through R109.1.4, the
147 
building official shall have the authority to inspect the proper installation of insulation.
148 
R109.1.5.1 Weather-resistant exterior wall envelope inspections. An inspection shall be
149 
made of the weather-resistant exterior wall envelope as required by Section R703.1 and
150 
flashings as required by Section R703.4 to prevent water from entering the
151 
weather-resistive barrier.R109.1.5.2 Fire-resistance-rated construction inspection. Where
152 
fire-resistance-rated construction is required between dwelling units or due to location
153 
on property, the building official shall require an inspection of such construction after
154 
lathing or gypsum board or gypsum panel products are in place, but before any plaster is
155 
applied, or before board or panel joints and fasteners are taped and finished."
156 
[(7)] (8) In IRC, Section R202, the following definition is added: "ACCESSORY
157 
DWELLING UNIT: A habitable living unit created within the existing footprint of a
158 
primary owner-occupied single-family dwelling."
159 
[(8)] (9) In IRC, Section R202, the definition for "Approved" is modified by adding the
160 
words "or independent third-party licensed engineer or architect and submitted to the
161 
building official" after the word "official."
162 
[(9)] (10) In IRC, Section R202, the definition for "Approved Agency" is modified by
163 
replacing the word "and" with "or."
164 
[(10)] (11) In IRC, Section 202, the definition for "Approved Source" is modified by adding
165 
the words "or licensed engineer or architect" after the word "official."
- 5 - 2nd Sub. (Gray) H.B. 313	02-26 21:36
166 
[(11)] (12) In IRC, Section R202, the following definition is added: "CERTIFIED
167 
BACKFLOW PREVENTER ASSEMBLY TESTER: A person who has shown
168 
competence to test Backflow prevention assemblies to the satisfaction of the authority
169 
having jurisdiction under Utah Code, Subsection 19-4-104(4)."
170 
[(12)] (13) In IRC, Section R202, the definition of "Cross Connection" is deleted and
171 
replaced with the following: "CROSS CONNECTION.  Any physical connection or
172 
potential connection or arrangement between two otherwise separate piping systems,
173 
one of which contains potable water and the other either water of unknown or
174 
questionable safety or steam, gas, or chemical, whereby there exists the possibility for
175 
flow from one system to the other, with the direction of flow depending on the pressure
176 
differential between the two systems (see "Backflow, Water Distribution")."
177 
[(13)] (14) In IRC, Section 202, the following definition is added: "DUAL SOURCE
178 
CONNECTION. A pipe that is installed so that either the nonpotable (i.e. secondary)
179 
irrigation water or the potable water is connected to a pressurized irrigation system at
180 
one time, but not both at the same time; or a pipe that is installed so that either the
181 
potable water or private well water is connected to a residence at one time, but not both
182 
at the same time. The potable water supply line shall be protected by a reduced pressure
183 
backflow preventer."
184 
[(14)] (15) In IRC, Section 202, the following definition is added: "ENERGY STORAGE
185 
SYSTEM (ESS). One or more devices, assembled together, that are capable of storing
186 
energy for supplying electrical energy at a future time."
187 
[(15)] (16) In IRC, Section 202, in the definition for gray water a comma is inserted after the
188 
word "washers"; the word "and" is deleted; and the following is added to the end: "and
189 
clear water wastes which have a pH of 6.0 to 9.0; are non-flammable; non-combustible;
190 
without objectionable odors; non-highly pigmented; and will not interfere with the
191 
operation of the sewer treatment facility."
192 
[(16)] (17) In IRC, Section R202, the definition of "Potable Water" is deleted and replaced
193 
with the following: "POTABLE WATER.  Water free from impurities present in
194 
amounts sufficient to cause disease or harmful physiological effects and conforming to
195 
the Utah Code, Title 19, Chapter 4, Safe Drinking Water Act, and Title 19, Chapter 5,
196 
Water Quality Act, and the regulations of the public health authority having jurisdiction."
197 
[(17)] (18) In IRC, Figure R301.2 (3), is deleted and replaced with R301.2 (3) as follows:
198 	"TABLE R301.2 (3)199 
GROUND SNOW LOADS FOR SELECTED LOCATIONS IN UTAH
- 6 - 02-26 21:36	2nd Sub. (Gray) H.B. 313
200 	City/Town County Ground Snow Load (lb/ft2)Elevation (ft)201 
Beaver	Beaver 35	5886
202 
Brigham City Box Elder 42	4423
203 
Castle Dale Emery 32	5669
204 
Coalville Summit 57	5581
205 
Duchesne Duchesne 39	5508
206 
Farmington Davis 35	4318
207 
Fillmore Millard 30	5138
208 
Heber City Wasatch 60	5604
209 
Junction Piute 27	6030
210 
Kanab	Kane 25	4964
211 
Loa	Wayne 37	7060
212 
Logan	Cache 43	4531
213 
Manila	Daggett 26	6368
214 
Manti	Sanpete 37	5620
215 
Moab	Grand 21	4029
216 
Monticello San Juan 67	7064
217 
Morgan	Morgan 52	5062
218 
Nephi	Juab 39	5131
219 
Ogden	Weber 37	4334
220 
Panguitch Garfield 41	6630
221 
Parowan Iron 32	6007
222 
Price	Carbon 31	5558
223 
Provo	Utah 31	4541
224 
Randolph Rich 50	6286
225 
Richfield Sevier 27	5338
226 
St. George Washington 21	2585
227 
Salt Lake City Salt Lake 28	4239
- 7 - 2nd Sub. (Gray) H.B. 313	02-26 21:36
228 	Tooele	Tooele 35	5029229 
Vernal	Uintah 39	5384
230 
Note: To convert lb/ft2 to kN/m2, multiply by 0.0479. To convert feet to meters, multiply by 0.3048.1.
Statutory requirements of the Authority Having Jurisdiction are not included in this state ground snow
load table.
2. For locations where there is substantial change in altitude over the city/town, the load applies at and
below the cited elevation, with a tolerance of 100 ft (30 m).
3. For other locations in Utah, see Bean, B., Maguire, M., Sun, Y. (2018), "The Utah Snow Load
Study," Utah State University Civil and Environmental Engineering Faculty Publications, Paper 3589,
http://utahsnowload.usu.edu/, for ground snow load values."
231 
[(18)] (19) In IRC, Section R301.6, is deleted and replaced with the following: "R301.6
232 
Utah Snow Loads.  The snow loads specified in Table R301.2(5b) shall be used for the
233 
jurisdictions identified in that table.  Otherwise, for other locations in Utah, see Bean,
234 
B., Maguire, M., Sun, Y. (2018), "The Utah Snow Load Study," Utah State University
235 
Civil and Environmental Engineering Faculty Publications, Paper 3589,
236 
http://utahsnowload.usu.edu/, for ground snow load values."
237 
[(19)] (20) In IRC, Section R302.2, the following sentence is added at the end of the
238 
paragraph: "When an access/maintenance agreement or easement is in place, plumbing,
239 
mechanical ducting, schedule 40 steel gas pipe, and electric service conductors including
240 
feeders, are permitted to penetrate the common wall at grade, above grade, or below
241 
grade."
242 
[(20)] (21) In IRC, Section R302.3, a new exception 3 is added as follows: "3. Accessory
243 
dwelling units separated by walls or floor assemblies protected by not less than 1/2-inch
244 
(12.7 mm) gypsum board or equivalent on each side of the wall or bottom of the floor
245 
assembly are exempt from the requirements of this section."
246 
[(21)] (22) In IRC, Section R302.5.1, the last sentence is deleted.
247 
[(22)] (23) In IRC, Section R302.13, is deleted.
248 
[(23)] (24) In IRC, Section R303.4, the following exception is added: "Exception: Dwelling
249 
units tested in accordance with Section N1102.4.1.2 (R402.4.1.2) which has an air
250 
tightness of 3.0 ACH (50) or greater do not require mechanical ventilation."
251 
[(24)] (25) In IRC, Section R310.1, all words in the last sentence after "or to a yard or
252 
court", are deleted, and Exception 3 of this section is deleted.
253 
[(25)] (26) In IRC, Section R310.7, in the exception, the words "or accessory dwelling
- 8 - 02-26 21:36	2nd Sub. (Gray) H.B. 313
254 
units" are added after the words "sleeping rooms".
255 	[(26)] (27) IRC, Sections R311.7.45 through R311.7.5.3, are deleted and replaced with the256 
following: "R311.7.45.1 Stair treads and risers. R311.7.5.1 Riser height.  The maximum riser257 
height shall be 8 inches (203 mm).  The riser shall be measured vertically between leading258 
edges of the adjacent treads.  The greatest riser height within any flight of stairs shall not259 
exceed the smallest by more than 3/8 inch (9.5 mm).260 
      R311.7.5.2 Tread depth.  The minimum tread depth shall be 9 inches (228 mm).  The261 
tread depth shall be measured horizontally between the vertical planes of the foremost262 
projection of adjacent treads and at a right angle to the tread's leading edge.  The greatest tread263 
depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm).264 
Winder treads shall have a minimum tread depth of 10 inches (254 mm) measured as above at265 
a point 12 inches (305 mm) from the side where the treads are narrower.  Winder treads shall266 
have a minimum tread depth of 6 inches (152 mm) at any point.  Within any flight of stairs, the267 
greatest winder tread depth at the 12-inch (305 mm) walk line shall not exceed the smallest by268 
more than 3/8 inch (9.5 mm).269 
      R311.7.5.3 Nosing.  The radius of curvature at the leading edge of the tread shall be no270 
greater than 9/16 inch (14.3 mm).  A nosing not less than 3/4 inch (19 mm) but not more than271 
1 1/4 inches (32 mm) shall be provided on stairways with solid risers.  The greatest nosing272 
projection shall not exceed the smallest nosing projection by more than 3/8 inch (9.5 mm)273 
between two stories, including the nosing at the level of floors and landings.  Beveling of274 
nosing shall not exceed 1/2 inch (12.7 mm).  Risers shall be vertical or sloped from the275 
underside of the leading edge of the tread above at an angle not more than 30 degrees (0.51276 
rad) from the vertical.  Open risers are permitted, provided that the opening between treads277 
does not permit the passage of a 4-inch diameter (102 mm) sphere.278 
      Exceptions.279 
      1.  A nosing is not required where the tread depth is a minimum of 10 inches (254 mm).280 
      2.  The opening between adjacent treads is not limited on stairs with a total rise of 30281 
inches (762 mm) or less."
282 
[(27)] (28) In IRC, Section R312.2, is deleted.
283 
[(28)] (29) In IRC, Sections R313.1 through R313.2.1, are deleted and replaced with the
284 
following: "R313.1 Design and installation.  When installed, automatic residential fire
285 
sprinkler systems for townhouses or one- and two-family dwellings shall be designed
286 
and installed in accordance with Section P2904 or NFPA 13D."
287 
[(29)] (30) In IRC, Section R314.2.2, the words "accessory dwelling units," are added after
- 9 - 2nd Sub. (Gray) H.B. 313	02-26 21:36
288 
the words "Where alterations, repairs."
289 
[(30)] (31) In IRC, Section R315.2.2, the words "accessory dwelling units," are added after
290 
the words "Where alterations, repairs."
291 
[(31)] (32) In IRC, Section 315.3, the following words are added to the first sentence after
292 
the word "installed": "on each level of the dwelling unit and."
293 	[(32)] (33) A new IRC, Section R328.12, is added as follows:
294 
      "R328.12 Signage. A sign located on the exterior of the dwelling shall be installed at a
295 
location approved by the authority having jurisdiction which identifies the battery chemistry
296 
included in the ESS. This sign shall be of sufficient durability to withstand the environment
297 
involved and shall not be handwritten."
298 
[(33)] (34) In IRC, Section 403.1.3.5.3, an exception is added as follows: "Exception:
299 
Vertical steel in footings shall be permitted to be located while concrete is still plastic
300 
and before it has set. Where vertical steel resists placement or the consolidation of
301 
concrete around steel is impeded, the concrete shall be vibrated to ensure full contact
302 
between the vertical steel and concrete."
303 
[(34)] (35) In IRC, Section R403.1.6, a new Exception 3 is added as follows: "3.  When
304 
anchor bolt spacing does not exceed 32 inches (813 mm) apart, anchor bolts may be
305 
placed with a minimum of two bolts per plate section located not less than 4 inches (102
306 
mm) from each end of each plate section at interior bearing walls, interior braced wall
307 
lines, and at all exterior walls."
308 
[(35)] (36) In IRC, Section R403.1.6.1, a new exception is added at the end of Item 2 and
309 
Item 3 as follows: "Exception: When anchor bolt spacing does not exceed 32 inches
310 
(816 mm) apart, anchor bolts may be placed with a minimum of two bolts per plate
311 
section located not less than 4 inches (102 mm) from each end of each plate section at
312 
interior bearing walls, interior braced wall lines, and at all exterior walls."
313 
[(36)] (37) In IRC, Section R404.1, a new exception is added as follows: "Exception: As an
314 
alternative to complying with Sections R404.1 through R404.1.5.3, concrete and
315 
masonry foundation walls may be designed in accordance with IBC Sections 1807.1.5
316 
and 1807.1.6 as amended in Section 1807.1.6.4 and Table 1807.1.6.4 under these rules."
317 
[(37)] (38) In IRC, Section R405.1, a second exception is added as follows: "Exception:
318 
When a geotechnical report has been provided for the property, a drainage system is not
319 
required unless the drainage system is required as a condition of the geotechnical report.
320 
The geotechnical report shall make a recommendation regarding a drainage system."
321 
[(38)] (39) In IRC, Section R506.2.3, the words "10-mil (0.010 inch; 0.25 mm)" are deleted
- 10 - 02-26 21:36	2nd Sub. (Gray) H.B. 313
322 
and replaced with "6-mil (0.006 inch; 0.152 mm)" and the words "conforming to ASTM
323 
E1745 Class A requirements" are deleted.
324 
(40) In IRC, Section 507.2.1, Wood materials. The following sentence is added after the
325 
words, "in accordance with section R317," "field applied weather resistant barrier
326 
applied to the top of untreated material,".
327 
Section 4.  Section 15A-3-206 is amended to read:
328 
15A-3-206 . Amendments to Chapters 36, 37, 39, and 44 and Appendix F of IRC.
329 
(1) In IRC, Section E3601.6.2, a new exception is added as follows: "Exception: An
330 
occupant of an accessory dwelling unit is not required to have access to the disconnect
331 
serving the dwelling unit in which they reside."
332 
(2) IRC, Section E3606.5, is deleted.
333 	(3) IRC, Section E3601.7, is deleted and replaced with the following:
334 
"3601.7 Maximum number of disconnects. The service disconnecting means shall consist of
335 
not more than six switches or six sets of circuit breakers mounted in a single enclosure or in a
336 
group of separate enclosures."
337 
(4) In IRC, Section E3705.4.4, the following sentences are deleted:
338 
"Where more than two NM cables containing two or more current-carrying
339 
conductors are installed, without maintaining space between the cables, through the
340 
same opening in wood framing should be sealed with thermal insulation, caulk or
341 
sealing foam. The allowable ampacity of each conductor shall be adjusted in accordance
342 
with Table E3705.3 and the provisions of Section E3701.3. Exception. may not apply."
343 	(5) IRC, Section E3901.4.2, is deleted and replaced with the following:
344 
      "E3901.4.2 Island and Peninsular Countertops and Work Spaces. Receptacle outlets, if
345 
installed to serve an island or peninsular countertop or work surface, shall be installed in
346 
accordance with E3901.4.3. If a receptacle outlet is not provided to serve an island or
347 
peninsular countertop or work surface, provisions shall be provided at the island or peninsula
348 
for future addition of a receptacle outlet to serve the island or peninsular countertop or work
349 
surface."
350 	[(5)] (6) IRC, Section E3901.4.3, is deleted and replaced with the following:
351 
      "E3901.4.3 Receptacle Outlet Location. [Receptacle] When installed, receptacle outlets
352 
shall be located in one or more of the following:
353 
      1. On or above, but not more than 20 inches (508 mm) above a countertop or work
354 
surface.
355 
      2. In a countertop using receptacle outlet assemblies listed for use in countertops.
- 11 - 2nd Sub. (Gray) H.B. 313	02-26 21:36
356 
      3. In a work surface using receptacle outlet assemblies listed for use in work surface or
357 
listed for use in countertops.
358 
      Receptacle outlets rendered not readily accessible by appliances fastened in place,
359 
appliance garages, sinks, or range tops as covered in the exception to Section E3901.4.1 or
360 
appliances occupying assigned spaces shall not be considered as these required outlets.
361 
      4. Under the countertop not more than 14 inches from the bottom leading edge of the
362 
countertop."
363 
[(6)] (7) In IRC, Section 3902.1, after the word "125-volt" add "single phase 15 and 20
364 
ampere" and strike the words "through 250 volt."
365 
[(7)] (8) In IRC, Section 3902.2, after the word "125-volt" add "single phase 15 and 20
366 
ampere" and strike the words "through 250 volt."
367 
[(8)] (9) In IRC, Section 3902.3, after the word "125-volt" add "single phase 15 and 20
368 
ampere" and strike the words "through 250 volt."
369 
[(9)] (10) In IRC, Section 3902.4, after the word "125-volt" add "single phase 15 and 20
370 
ampere" and strike the words "through 250 volt."
371 
[(10)] (11) In IRC, Section 3902.5, after the word "125-volt" add the words "single phase 15
372 
and 20 ampere in unfinished portions of the basement shall have ground-fault
373 
circuit-interrupter protection for personnel" and delete the rest of the section.
374 
[(11)] (12) In IRC, Section 3902.6, after the word "125-volt" add "single phase 15 and 20
375 
ampere" and strike the words "through 250 volt."
376 
[(12)] (13) In IRC, Section 3902.7, after the word "125-volt" add "single phase 15 and 20
377 
ampere" and strike the words "through 250 volt."
378 
[(13)] (14) In IRC, Section 3902.8, after the word "125-volt" add "single phase 15 and 20
379 
ampere" and strike the words "through 250 volt."
380 
[(14)] (15) In IRC, Section 3902.9, after the word "125-volt" add "single phase 15 and 20
381 
ampere" and strike the words "through 250 volt."
382 
[(15)] (16) IRC, Section 3902.10, is deleted.
383 
[(16)] (17) In IRC, Section 3902.12, after the word "125-volt" add "single phase 15 and 20
384 
ampere" and strike the words "through 250 volt."
385 
[(17)] (18) In IRC, Section 3902.13, after the word "125-volt" add "single phase 15 and 20
386 
ampere" and strike the words "through 250 volt."
387 
[(18)] (19) IRC, Section 3902.15, Crawl space lighting outlets, is deleted.
388 
[(19)] (20) IRC, Section 3902.16, Equipment requiring servicing, is deleted.
389 
[(20)] (21) IRC Section 3902.17, Outdoor outlets, is deleted.
- 12 - 02-26 21:36	2nd Sub. (Gray) H.B. 313
390 
[(21)] (22) IRC, Section 3902.19, Location of arc-fault circuit interrupters, is deleted.
391 
[(22)] (23) IRC, Section E3902.20, Arc-fault circuit interrupter protection, is deleted.
392 
[(23)] (24) IRC, Section E3902.21, Arc-fault circuit interrupter protection for branch circuit
393 
extensions or modification, is deleted.
394 
[(24)] (25) IRC, Section 4002.11, is deleted and replaced with the following: "4002.11
395 
Bathtub and Shower Space. Receptacles shall not be installed within or directly over a
396 
bathtub or shower stall."
397 
[(25)] (26) IRC, Chapter 44, is amended by deleting the standard for "ANCE."
398 
[(26)] (27) In IRC, Chapter 44, the standard for ASHRAE is amended by changing
399 
"34-2013" to "34-2019."
400 
[(27)] (28) In IRC, Chapter 44, the standard for CSA, is amended by changing the:
401 
(a) standard reference number "UL/CSA/ANCE 60335-2-40-2012" to "UL/CSA
402 
60335-2-40-2019"; and
403 
(b) title "Standard for Household and Similar Electrical Appliances, Part 2: Particular
404 
Requirements for Motor-Compressors" to "Standard for Household and Similar
405 
Electrical Appliances, Part 2-40, Requirements for Electric Heat Pumps, Air
406 
Conditioners and Dehumidifiers-3rd Edition."
407 
[(28)] (29) In IRC, Chapter 44, the standard for UL, is amended by changing the:
408 
(a) standard reference number "1995-2011" to "1995-2015";
409 
(b) standard reference number "UL/CSA/ANCE 60335-2-40-2012" to "UL/CSA
410 
60335-2-40-2019"; and
411 
(c) title "Standard for Household and Similar Electrical Appliances, Part 2: Particular
412 
Requirements for Motor-Compressors" to "Standard for Household and Similar
413 
Electrical Appliances, Part 2-40, Requirements for Electric Heat Pumps, Air
414 
Conditioners and Dehumidifiers-3rd Edition."
415 	[(29)] (30) In IRC, Chapter 44, the standard for ANSI/RESNET/ICC 201-2019 Section 4.4.4 is
416 
added as follows: "4.4.4. Air Source Heat Pumps and Air Conditioners. For Heat Pumps and
417 
Air Conditioners with the more recent Manufacturers Equipment Performance Ratings (HSPF2
418 
or SEER2) available, and HSPF and SEER are not available, these ratings shall be converted
419 
to HSPF and SEER values by dividing HSPF2 or SEER2 by the conversion factors in Table
420 
4.4.4.1(1).  If the type of equipment is not determined, the conversion shall default to the
421 
Ducted Split System factors.  All calculations, including Equation 4.1-1a shall use HSPF or
422 
SEER values as made available by the Manufacturer or converted as specified in this section.
423 
Table 4.4.4.1(1) SEER2 and HSPF2 Conversion Factors3.
- 13 - 2nd Sub. (Gray) H.B. 313	02-26 21:36
424 	Equipment Type	SEER2/SEEREER/EER4 HSPF/HSPF425 
Ductless Systems	1.00 1.00 0.90
426 
Ducted Split System	0.95 0.95 0.85
427 
Ducted Package System	0.95 0.95 0.84
428 
Small Duct High Velocity System	1.00 not applicable0.85
429 
Ducted Space-Constrained Air Conditioner 0.97 not applicablenot applicable
430 
Ducted Space-Constrained Heat Pump	not applicable0.85"
431 	[(30)] (31) IRC, Chapter 44, is amended by adding the following reference standard:
432 
433 	"Standard reference numberTitle	Referenced in code
section number
434 
USC-FCCCHR 10th
Edition Manual of Cross
Connection Control
Foundation for Cross-Connection Control and
Hydraulic Research University of Southern
California Kaprielian Hall 300 Los Angeles
CA 90089-2531
Table P2902.3"
435 
[(31)] (32) IRC, Chapter 44, is amended by adding the following reference standard: "UL
436 
9540-20: Energy Storage Systems and Equipment; R328.1, R328.2, and R328.6."
437 
[(32)] (33)(a) When passive radon controls or portions thereof are voluntarily installed,
438 
the voluntary installation shall comply with Appendix F of the IRC.
439 
(b) An additional inspection of a voluntary installation described in Subsection [(27)(a) ] 
440 
(28)(a) is not required.
441 
Section 5.  Section 15A-3-601 is amended to read:
442 
15A-3-601 . General provisions.
443 
      The following are adopted as amendments to the NEC to be applicable statewide:
444 
(1) The IRC provisions are adopted as the residential electrical standards applicable to
445 
residential installations under the IRC.  All other installations shall comply with the
446 
adopted NEC.
447 
(2) In NEC, Section 210.8(A), the words "through 250-volt" are deleted.
448 
(3) In NEC, Section 210.8(A) number (5), the word "Basements" is deleted and replaced
449 
with the following:
450 
"Unfinished portions or areas of the basement not intended as habitable rooms."
451 
(4) In NEC, Section 210.8(A), number (6), the following is added after the word "Kitchens":
452 
"where the receptacles are installed to serve the countertop surfaces."
- 14 - 02-26 21:36	2nd Sub. (Gray) H.B. 313
453 
(5) In NEC, Section 210.8(A), number (7) is deleted.
454 
(6) In NEC, Section 210.8(D), numbers (8) through (12) are deleted.
455 
(7) NEC, Section 210.8(F), is deleted.
456 	[(5)] (8) NEC, Sections 210.52(C) number (2) and number (3) are deleted and replaced with the
457 
following:
458 
      "210.52(C)(2) Island and peninsular countertops and Work Surfaces. Receptacle outlets,
459 
if installed to serve an island or peninsular countertop or work surface, shall be installed in
460 
accordance with 210.52(C)(3). If a receptacle outlet is not provided to serve an island or
461 
peninsular countertop or work surface, provisions shall be provided at the island or peninsula
462 
for future addition of a receptacle outlet to serve the island or peninsular countertop or work
463 
surface.
464 
      210.2(C)(3) Receptacle outlet location. Receptacle outlets shall be located in one or
465 
more of the following:
466 
(a) On or above, but not more than 500 mm (20 inches) above a countertop or work
467 
surface.
468 
(b) In a countertop using receptacle assemblies listed for use in countertops.
469 	(c) In a work surface using receptacle outlet assemblies listed for use in work surfaces or listed
470 
for use in countertops.
471 
      Receptacle outlets rendered not readily accessible by appliances fastened in place,
472 
appliance garages, sinks, or range tops as covered in the exception to 210.52(C)(1), occupying
473 
assigned spaces shall not be considered as these required outlets.
474 
      Exception: In dwelling units designed to be accessible to persons with disabilities,
475 
receptacles shall be permitted to be installed not more than 300 mm (12 inches) below the
476 
countertop or work surface. Receptacles installed below a countertop or work surface shall not
477 
be located where the countertop or work surface extends more than 150 mm (6 inches) beyond
478 
its support or base."
479 
[(6)] (9) NEC, Section 210.12, is deleted.
480 
[(7)] (10) NEC, Section 210.65, is deleted.
481 
(11) NEC, Section 215.18, is deleted.
482 
(12) NEC, Section 225.42 is deleted.
483 
[(8)] (13) NEC, Section 230.67, is deleted.
484 	[(9)] (14) NEC, Section 230.71, is deleted and replaced with the following:
485 
"230.71 Maximum Number of Disconnects.
486 
(A) General. The service disconnecting means for each service permitted by 230.2, or for
- 15 - 2nd Sub. (Gray) H.B. 313	02-26 21:36
487 
each set of service-entrance conductors permitted by 230.40, Exception No. 1, 3, 4, or 5 shall
488 
consist of not more than six switches or sets of circuit breakers, or a combination of not more
489 
than six switches and sets of circuit breakers, mounted in a single enclosure, in a group of
490 
separate enclosures, or in or on a switchboard or in switchgear. There shall be not more than
491 
six sets of disconnects per service grouped in any one location. For the purpose of this section,
492 
disconnecting means installed as part of listed equipment and used solely for the following
493 
shall not be considered a service disconnecting means:
494 
(1) Power monitoring equipment;
495 
(2) Surge-protective device(s);
496 
(3) Control circuit of the ground-fault protection system; or
497 
(4) Power-operable service disconnecting.
498 
(B) Single-Pole Units. Two or three single-pole switches or breakers, capable of individual
499 
operation, shall be permitted on multiwire circuits, one pole for each ungrounded conductor, as
500 
one multipole disconnect, provided they are equipped with identified handle ties or a master
501 
handle to disconnect all conductors of the service with no more than six operations of the hand.
502 
(C) Beginning on July 1, 2027, Section 230.71(B) is no longer in effect."
503 
[(10)] (15) NEC, Section 314.27(C), is deleted and replaced with the following: "314.27(C)
504 
Boxes at Ceiling-Suspended (Paddle) Fan Outlets. Outlet boxes or outlet box systems
505 
used as the sole support of a ceiling-suspended (paddle) fan shall be listed, shall be
506 
marked by their manufacturer as suitable for this purpose, and shall not support
507 
ceiling-suspended (paddle) fans that weigh more than 32 kg (70 lb). For outlet boxes or
508 
outlet box systems designed to support ceiling-suspended (paddle) fans that weigh more
509 
than 16 kg (35 lb), the required marking shall include the maximum weight to be
510 
supported."
511 
(16) In NEC, Section 334.24, the last sentence is deleted and replaced with the following:
512 
"For flat cables, the minor diameter dimension of the cable shall be used to determine
513 
the bending radius when bending on the flat side of the cable. For all other bends, the
514 
major diameter dimension shall be used."
515 
[(11) NEC, Section 406.9(C), is deleted and replaced with the following: "406.9(C) Bathtub
516 
and Shower Space. Receptacles shall not be installed within or directly over a bathtub or
517 
shower stall."]
518 
(17) In NEC, Section 334.80, the second paragraph is deleted.
519 
(18) In NEC, Section 338.24, the last sentence is deleted and replaced with the following:
520 
"For flat cables, the minor diameter dimension of the cable shall be used to determine
- 16 - 02-26 21:36	2nd Sub. (Gray) H.B. 313
521 
the bending radius when bending on the flat side of the cable. For all other bends, the
522 
major diameter dimension shall be used."
523 
(19) In NEC, Section 406.9(B) number (2),  the following words are deleted:
524 
"be listed weather-resistant type, and installation shall".
525 
(20) NEC, Section 700.3(A) is deleted and replaced with the following:
526 
"700.3(A) Conductor Witness Test.
527 
The authority having jurisdiction shall conduct or witness a test of the complete
528 
system upon installation and periodically afterward."
529 
Section 6.  Effective Date.
530 
This bill takes effect on May 7, 2025.
531 
Section 7.  Coordinating H.B. 313 with H.B. 175.
532 
If H.B. 313, State Construction and Electrical Standards Amendments, and H.B. 175,
533 
Housing Construction Amendments, both pass and become law, the Legislature intends that,
534 
on May 7, 2025, the amendments to Section 15A-3-202 in H.B. 313 supersede the
535 
amendments to Section 15A-3-202 in H.B. 175.
- 17 -