2 | 3 | | 1 |
---|
3 | 4 | | Construction Industry Amendments |
---|
4 | 5 | | 2025 GENERAL SESSION |
---|
5 | 6 | | STATE OF UTAH |
---|
6 | 7 | | Chief Sponsor: Thomas W. Peterson |
---|
7 | 8 | | Senate Sponsor: Calvin R. Musselman |
---|
8 | 9 | | 2 |
---|
9 | 10 | | |
---|
10 | 11 | | 3 |
---|
11 | 12 | | LONG TITLE |
---|
12 | 13 | | 4 |
---|
13 | 14 | | General Description: |
---|
14 | 15 | | 5 |
---|
15 | 16 | | This bill modifies the State Construction Code. |
---|
16 | 17 | | 6 |
---|
17 | 18 | | Highlighted Provisions: |
---|
18 | 19 | | 7 |
---|
19 | 20 | | This bill: |
---|
20 | 21 | | 8 |
---|
21 | 22 | | ▸ amends the State Construction Code to: |
---|
22 | 23 | | 9 |
---|
23 | 24 | | ● align with updated standards in the International Residential Code (IRC); and |
---|
24 | 25 | | 10 |
---|
25 | 26 | | ● align with the updated standards in the National Electric Code (NEC); |
---|
26 | 27 | | 11 |
---|
27 | 28 | | ▸ includes a coordination clause to make the amendments to Section 15A-3-202 in this bill |
---|
28 | 29 | | 12 |
---|
29 | 30 | | supersede the amendments to Section 15A-3-202 in H.B. 175, Housing Construction |
---|
30 | 31 | | 13 |
---|
31 | 32 | | Amendments; |
---|
32 | 33 | | 14 |
---|
33 | 34 | | ▸ removes regulations for water heaters in certain areas; and |
---|
34 | 35 | | 15 |
---|
35 | 36 | | ▸ makes technical changes. |
---|
36 | 37 | | 16 |
---|
37 | 38 | | Money Appropriated in this Bill: |
---|
38 | 39 | | 17 |
---|
39 | 40 | | None |
---|
40 | 41 | | 18 |
---|
41 | 42 | | Other Special Clauses: |
---|
42 | 43 | | 19 |
---|
43 | 44 | | This bill provides a special effective date. |
---|
44 | 45 | | 20 |
---|
45 | 46 | | This bill provides a coordination clause. |
---|
46 | 47 | | 21 |
---|
47 | 48 | | Utah Code Sections Affected: |
---|
48 | 49 | | 22 |
---|
49 | 50 | | AMENDS: |
---|
50 | 51 | | 23 |
---|
51 | 52 | | 15A-2-103, as last amended by Laws of Utah 2024, Chapter 505 |
---|
52 | 53 | | 24 |
---|
53 | 54 | | 15A-3-105, as last amended by Laws of Utah 2024, Chapter 505 |
---|
54 | 55 | | 25 |
---|
55 | 56 | | 15A-3-202, as last amended by Laws of Utah 2024, Chapter 505 |
---|
56 | 57 | | 26 |
---|
57 | 58 | | 15A-3-206, as last amended by Laws of Utah 2024, Chapter 505 |
---|
58 | 59 | | 27 |
---|
62 | 64 | | 29 |
---|
63 | 65 | | Utah Code Sections affected by Coordination Clause: |
---|
64 | 66 | | 30 |
---|
65 | 67 | | 15A-3-202, as last amended by Laws of Utah 2024, Chapter 505 |
---|
66 | 68 | | 31 |
---|
67 | 69 | | |
---|
68 | 70 | | 32 |
---|
69 | 71 | | Be it enacted by the Legislature of the state of Utah: |
---|
70 | 72 | | 33 |
---|
71 | 73 | | Section 1. Section 15A-2-103 is amended to read: |
---|
72 | 74 | | 34 |
---|
73 | 75 | | 15A-2-103 . Specific editions adopted of construction code of a nationally |
---|
74 | 76 | | 35 |
---|
75 | 77 | | recognized code authority. |
---|
76 | 78 | | 36 |
---|
77 | 79 | | (1) Subject to the other provisions of this part, the following construction codes are |
---|
78 | 80 | | 37 |
---|
79 | 81 | | incorporated by reference, and together with the amendments specified in Chapter 3, |
---|
80 | 82 | | 38 |
---|
81 | 83 | | Statewide Amendments Incorporated as Part of State Construction Code, and Chapter 4, |
---|
82 | 84 | | 39 |
---|
83 | 85 | | Local Amendments Incorporated as Part of State Construction Code, are the |
---|
84 | 86 | | 40 |
---|
85 | 87 | | construction standards to be applied to building construction, alteration, remodeling, and |
---|
86 | 88 | | 41 |
---|
87 | 89 | | repair, and in the regulation of building construction, alteration, remodeling, and repair |
---|
88 | 90 | | 42 |
---|
89 | 91 | | in the state: |
---|
90 | 92 | | 43 |
---|
91 | 93 | | (a) the 2021 edition of the International Building Code, including Appendices C and J, |
---|
92 | 94 | | 44 |
---|
93 | 95 | | issued by the International Code Council; |
---|
94 | 96 | | 45 |
---|
95 | 97 | | (b) the 2021 edition of the International Residential Code, issued by the International |
---|
96 | 98 | | 46 |
---|
97 | 99 | | Code Council; |
---|
98 | 100 | | 47 |
---|
99 | 101 | | (c) Appendix AQ of the 2021 edition of the International Residential Code, issued by the |
---|
100 | 102 | | 48 |
---|
101 | 103 | | International Code Council; |
---|
102 | 104 | | 49 |
---|
103 | 105 | | (d) the 2021 edition of the International Plumbing Code, issued by the International |
---|
104 | 106 | | 50 |
---|
105 | 107 | | Code Council; |
---|
106 | 108 | | 51 |
---|
107 | 109 | | (e) the 2021 edition of the International Mechanical Code, issued by the International |
---|
108 | 110 | | 52 |
---|
109 | 111 | | Code Council; |
---|
110 | 112 | | 53 |
---|
111 | 113 | | (f) the 2021 edition of the International Fuel Gas Code, issued by the International Code |
---|
112 | 114 | | 54 |
---|
113 | 115 | | Council; |
---|
114 | 116 | | 55 |
---|
115 | 117 | | (g) the [2020] 2023 edition of the National Electrical Code, issued by the National Fire |
---|
116 | 118 | | 56 |
---|
117 | 119 | | Protection Association; |
---|
118 | 120 | | 57 |
---|
119 | 121 | | (h) the 2021 edition of the International Energy Conservation Code, issued by the |
---|
120 | 122 | | 58 |
---|
121 | 123 | | International Code Council; |
---|
122 | 124 | | 59 |
---|
123 | 125 | | (i) the 2021 edition of the International Existing Building Code, issued by the |
---|
124 | 126 | | 60 |
---|
125 | 127 | | International Code Council; |
---|
126 | 128 | | 61 |
---|
127 | 129 | | (j) subject to Subsection 15A-2-104(2), the HUD Code; |
---|
131 | 133 | | 63 |
---|
132 | 134 | | International Residential Code, issued by the International Code Council; |
---|
133 | 135 | | 64 |
---|
134 | 136 | | (l) subject to Subsection 15A-2-104(1), the 2005 edition of the NFPA 225 Model |
---|
135 | 137 | | 65 |
---|
136 | 138 | | Manufactured Home Installation Standard, issued by the National Fire Protection |
---|
137 | 139 | | 66 |
---|
138 | 140 | | Association; |
---|
139 | 141 | | 67 |
---|
140 | 142 | | (m) subject to Subsection (3), for standards and guidelines pertaining to plaster on a |
---|
141 | 143 | | 68 |
---|
142 | 144 | | historic property, as defined in Section 9-8a-302, the U.S. Department of the Interior |
---|
143 | 145 | | 69 |
---|
144 | 146 | | Secretary's Standards for Rehabilitation and Guidelines for Rehabilitating Historic |
---|
145 | 147 | | 70 |
---|
146 | 148 | | Buildings;[ and] |
---|
147 | 149 | | 71 |
---|
148 | 150 | | (n) the residential provisions of the 2021 edition of the International Swimming Pool |
---|
149 | 151 | | 72 |
---|
150 | 152 | | and Spa Code, issued by the International Code Council; and |
---|
151 | 153 | | 73 |
---|
152 | 154 | | (o) Modular Building Institute Standards 1200 and 1205, issued by the International |
---|
153 | 155 | | 74 |
---|
154 | 156 | | Code Council, except as modified by provisions of this title governing modular units. |
---|
155 | 157 | | 75 |
---|
156 | 158 | | (2) Consistent with Title 65A, Chapter 8, Management of Forest Lands and Fire Control, |
---|
157 | 159 | | 76 |
---|
158 | 160 | | the Legislature adopts the 2006 edition of the Utah Wildland Urban Interface Code, |
---|
159 | 161 | | 77 |
---|
160 | 162 | | issued by the International Code Council, with the alternatives or amendments approved |
---|
161 | 163 | | 78 |
---|
162 | 164 | | by the Utah Division of Forestry, Fire, and State Lands, as a construction code that may |
---|
163 | 165 | | 79 |
---|
164 | 166 | | be adopted by a local compliance agency by local ordinance or other similar action as a |
---|
165 | 167 | | 80 |
---|
166 | 168 | | local amendment to the codes listed in this section. |
---|
167 | 169 | | 81 |
---|
168 | 170 | | (3) The standards and guidelines described in Subsection (1)[(n) ] (m) apply only if: |
---|
169 | 171 | | 82 |
---|
170 | 172 | | (a) the owner of the historic property receives a government tax subsidy based on the |
---|
171 | 173 | | 83 |
---|
172 | 174 | | property's status as a historic property; |
---|
173 | 175 | | 84 |
---|
174 | 176 | | (b) the historic property is wholly or partially funded by public money; or |
---|
175 | 177 | | 85 |
---|
176 | 178 | | (c) the historic property is owned by a government entity. |
---|
177 | 179 | | 86 |
---|
178 | 180 | | Section 2. Section 15A-3-105 is amended to read: |
---|
179 | 181 | | 87 |
---|
180 | 182 | | 15A-3-105 . Amendments to Chapters 10 through 12 of IBC. |
---|
181 | 183 | | 88 |
---|
182 | 184 | | (1) In IBC, Section 1010.2.4, number (2), the following is added at the end of the sentence: |
---|
183 | 185 | | 89 |
---|
184 | 186 | | "Blended assisted living facilities shall comply with Section 1010.2.14.1." |
---|
185 | 187 | | 90 |
---|
186 | 188 | | (2) A new IBC Section 1010.2.14.1 is added as follows: "1010.2.14.1 Blended assisted |
---|
187 | 189 | | 91 |
---|
188 | 190 | | living facilities. In occupancy Group I-1, Condition 2 or Group I-2, a Type-II assisted |
---|
189 | 191 | | 92 |
---|
190 | 192 | | living facility licensed by the Department of Health and Human Services for residents |
---|
191 | 193 | | 93 |
---|
192 | 194 | | with Alzheimer's or dementia, and having a controlled egress locking system to prevent |
---|
193 | 195 | | 94 |
---|
194 | 196 | | operation from the egress side shall be permitted to also house residents without a |
---|
195 | 197 | | 95 |
---|
196 | 198 | | clinical need for their containment where all of the following provisions are met: |
---|
200 | 202 | | 97 |
---|
201 | 203 | | doors; |
---|
202 | 204 | | 98 |
---|
203 | 205 | | (b) all residents without a clinical need for their containment shall have the keys, codes, |
---|
204 | 206 | | 99 |
---|
205 | 207 | | or other means necessary to exit the facility, in a manner that is determined by the |
---|
206 | 208 | | 100 |
---|
207 | 209 | | facility operator and communicated to the resident or their legal representative; |
---|
208 | 210 | | 101 |
---|
209 | 211 | | (c) residents or their legal representative acknowledge in writing that they understand |
---|
210 | 212 | | 102 |
---|
211 | 213 | | and agree to living in a facility where egress is controlled; and |
---|
212 | 214 | | 103 |
---|
213 | 215 | | (d) the number of residents housed in a smoke compartment with controlled egress shall |
---|
214 | 216 | | 104 |
---|
215 | 217 | | not be greater than 30." |
---|
216 | 218 | | 105 |
---|
217 | 219 | | (3) In IBC, Section 1011.5.2, exception 3 is deleted and replaced with the following: " 3. In |
---|
218 | 220 | | 106 |
---|
219 | 221 | | Group R-3 occupancies, within dwelling units in Group R-2 occupancies, and in Group |
---|
220 | 222 | | 107 |
---|
221 | 223 | | U occupancies that are accessory to a Group R-3 occupancy, or accessory to individual |
---|
222 | 224 | | 108 |
---|
223 | 225 | | dwelling units in Group R-2 occupancies, the maximum riser height shall be 8 inches |
---|
224 | 226 | | 109 |
---|
225 | 227 | | (203 mm) and the minimum tread depth shall be 9 inches (229 mm). The minimum |
---|
226 | 228 | | 110 |
---|
227 | 229 | | winder tread depth at the walk line shall be 10 inches (254 mm), and the minimum |
---|
228 | 230 | | 111 |
---|
229 | 231 | | winder tread depth shall be 6 inches (152 mm). A nosing not less than 0.75 inch (19.1 |
---|
230 | 232 | | 112 |
---|
231 | 233 | | mm) but not more than 1.25 inches (32 mm) shall be provided on stairways with solid |
---|
232 | 234 | | 113 |
---|
233 | 235 | | risers where the tread depth is less than 10 inches (254 mm)." |
---|
234 | 236 | | 114 |
---|
235 | 237 | | (4) In IBC, Section 1011.11, a new exception 6 is added as follows: " 6. In occupancies in |
---|
236 | 238 | | 115 |
---|
237 | 239 | | Group R-3, as applicable in Section 101.2 and in occupancies in Group U, which are |
---|
238 | 240 | | 116 |
---|
239 | 241 | | accessory to an occupancy in Group R-3, as applicable in Section 101.2, handrails shall |
---|
240 | 242 | | 117 |
---|
241 | 243 | | be provided on at least one side of stairways consisting of four or more risers." |
---|
242 | 244 | | 118 |
---|
243 | 245 | | (5) In IBC, Section 1025, is deleted. |
---|
244 | 246 | | 119 |
---|
245 | 247 | | (6) In IBC, Section 1104.4, exception 1.5 is deleted. |
---|
246 | 248 | | 120 |
---|
247 | 249 | | The following section is affected by a coordination clause at the end of this bill. |
---|
248 | 250 | | 121 |
---|
249 | 251 | | Section 3. Section 15A-3-202 is amended to read: |
---|
250 | 252 | | 122 |
---|
251 | 253 | | 15A-3-202 . Amendments to Chapters 1 through 5 of IRC. |
---|
252 | 254 | | 123 |
---|
253 | 255 | | (1) In IRC, Section R101.2, Exception, the words "where provided with an automatic |
---|
254 | 256 | | 124 |
---|
255 | 257 | | sprinkler system complying with Section P2904" are deleted. |
---|
256 | 258 | | 125 |
---|
257 | 259 | | (2) In IRC, Section R101.2, Exception, the words "6. A triplex or fourplex of no more than |
---|
258 | 260 | | 126 |
---|
259 | 261 | | two levels with 2-hour fire-resistance-rated vertical shared wall assemblies tested in |
---|
260 | 262 | | 127 |
---|
261 | 263 | | accordance with ASTM E119 or UL263, 1-hour fire-resistance-rated horizontal floor |
---|
262 | 264 | | 128 |
---|
263 | 265 | | assemblies tested in accordance with ASTM E119 or UL263, and independent egress for |
---|
264 | 266 | | 129 |
---|
265 | 267 | | each unit." are added. |
---|
269 | 271 | | 131 |
---|
270 | 272 | | Physical change for bedroom window egress. A structure whose egress window in an |
---|
271 | 273 | | 132 |
---|
272 | 274 | | existing bedroom is smaller than required by this code, and that complied with the |
---|
273 | 275 | | 133 |
---|
274 | 276 | | construction code in effect at the time that the bedroom was finished, is not required to |
---|
275 | 277 | | 134 |
---|
276 | 278 | | undergo a physical change to conform to this code if the change would compromise the |
---|
277 | 279 | | 135 |
---|
278 | 280 | | structural integrity of the structure or could not be completed in accordance with other |
---|
279 | 281 | | 136 |
---|
280 | 282 | | applicable requirements of this code, including setback and window well requirements." |
---|
281 | 283 | | 137 |
---|
282 | 284 | | [(3)] (4) In IRC Section R105.2, under Building, the following changes are made: |
---|
283 | 285 | | 138 |
---|
284 | 286 | | (a) Number 3 is deleted and replaced with the following: "3. Retaining walls retaining |
---|
285 | 287 | | 139 |
---|
286 | 288 | | less than 4 feet (1219mm) of unbalanced fill, unless supporting a surcharge or |
---|
287 | 289 | | 140 |
---|
288 | 290 | | requiring design per Section R404.4." |
---|
289 | 291 | | 141 |
---|
290 | 292 | | (b) Number 10 is deleted and replaced with the following: "10. Decks that are not more |
---|
291 | 293 | | 142 |
---|
292 | 294 | | than 30 inches (762mm) above grade at any point and not requiring guardrails, that |
---|
293 | 295 | | 143 |
---|
294 | 296 | | do not serve exit door required by Section R311.4." |
---|
295 | 297 | | 144 |
---|
296 | 298 | | [(4)] (5) In IRC, Section R105.2, a new exception is added: "11. Grade level, non-connected |
---|
297 | 299 | | 145 |
---|
298 | 300 | | conex boxes, less than 350 square feet, used for storage only." |
---|
299 | 301 | | 146 |
---|
300 | 302 | | [(5)] (6) In IRC, Section R108.3, the following sentence is added at the end of the section: |
---|
301 | 303 | | 147 |
---|
302 | 304 | | "The building official shall not request proprietary information." |
---|
303 | 305 | | 148 |
---|
304 | 306 | | [(6)] (7) In IRC, Section 109.1.5, is deleted and replaced with the following: "R109.1.5 |
---|
305 | 307 | | 149 |
---|
306 | 308 | | Other inspections. In addition to the inspections listed in R109.1.1 through R109.1.4, the |
---|
307 | 309 | | 150 |
---|
308 | 310 | | building official shall have the authority to inspect the proper installation of insulation. |
---|
309 | 311 | | 151 |
---|
310 | 312 | | R109.1.5.1 Weather-resistant exterior wall envelope inspections. An inspection shall be |
---|
311 | 313 | | 152 |
---|
312 | 314 | | made of the weather-resistant exterior wall envelope as required by Section R703.1 and |
---|
313 | 315 | | 153 |
---|
314 | 316 | | flashings as required by Section R703.4 to prevent water from entering the |
---|
315 | 317 | | 154 |
---|
316 | 318 | | weather-resistive barrier.R109.1.5.2 Fire-resistance-rated construction inspection. Where |
---|
317 | 319 | | 155 |
---|
318 | 320 | | fire-resistance-rated construction is required between dwelling units or due to location |
---|
319 | 321 | | 156 |
---|
320 | 322 | | on property, the building official shall require an inspection of such construction after |
---|
321 | 323 | | 157 |
---|
322 | 324 | | lathing or gypsum board or gypsum panel products are in place, but before any plaster is |
---|
323 | 325 | | 158 |
---|
324 | 326 | | applied, or before board or panel joints and fasteners are taped and finished." |
---|
325 | 327 | | 159 |
---|
326 | 328 | | [(7)] (8) In IRC, Section R202, the following definition is added: "ACCESSORY |
---|
327 | 329 | | 160 |
---|
328 | 330 | | DWELLING UNIT: A habitable living unit created within the existing footprint of a |
---|
329 | 331 | | 161 |
---|
330 | 332 | | primary owner-occupied single-family dwelling." |
---|
331 | 333 | | 162 |
---|
332 | 334 | | [(8)] (9) In IRC, Section R202, the definition for "Approved" is modified by adding the |
---|
333 | 335 | | 163 |
---|
334 | 336 | | words "or independent third-party licensed engineer or architect and submitted to the |
---|
338 | 340 | | 165 |
---|
339 | 341 | | [(9)] (10) In IRC, Section R202, the definition for "Approved Agency" is modified by |
---|
340 | 342 | | 166 |
---|
341 | 343 | | replacing the word "and" with "or." |
---|
342 | 344 | | 167 |
---|
343 | 345 | | [(10)] (11) In IRC, Section 202, the definition for "Approved Source" is modified by adding |
---|
344 | 346 | | 168 |
---|
345 | 347 | | the words "or licensed engineer or architect" after the word "official." |
---|
346 | 348 | | 169 |
---|
347 | 349 | | [(11)] (12) In IRC, Section R202, the following definition is added: "CERTIFIED |
---|
348 | 350 | | 170 |
---|
349 | 351 | | BACKFLOW PREVENTER ASSEMBLY TESTER: A person who has shown |
---|
350 | 352 | | 171 |
---|
351 | 353 | | competence to test Backflow prevention assemblies to the satisfaction of the authority |
---|
352 | 354 | | 172 |
---|
353 | 355 | | having jurisdiction under Utah Code, Subsection 19-4-104(4)." |
---|
354 | 356 | | 173 |
---|
355 | 357 | | [(12)] (13) In IRC, Section R202, the definition of "Cross Connection" is deleted and |
---|
356 | 358 | | 174 |
---|
357 | 359 | | replaced with the following: "CROSS CONNECTION. Any physical connection or |
---|
358 | 360 | | 175 |
---|
359 | 361 | | potential connection or arrangement between two otherwise separate piping systems, |
---|
360 | 362 | | 176 |
---|
361 | 363 | | one of which contains potable water and the other either water of unknown or |
---|
362 | 364 | | 177 |
---|
363 | 365 | | questionable safety or steam, gas, or chemical, whereby there exists the possibility for |
---|
364 | 366 | | 178 |
---|
365 | 367 | | flow from one system to the other, with the direction of flow depending on the pressure |
---|
366 | 368 | | 179 |
---|
367 | 369 | | differential between the two systems (see "Backflow, Water Distribution")." |
---|
368 | 370 | | 180 |
---|
369 | 371 | | [(13)] (14) In IRC, Section 202, the following definition is added: "DUAL SOURCE |
---|
370 | 372 | | 181 |
---|
371 | 373 | | CONNECTION. A pipe that is installed so that either the nonpotable (i.e. secondary) |
---|
372 | 374 | | 182 |
---|
373 | 375 | | irrigation water or the potable water is connected to a pressurized irrigation system at |
---|
374 | 376 | | 183 |
---|
375 | 377 | | one time, but not both at the same time; or a pipe that is installed so that either the |
---|
376 | 378 | | 184 |
---|
377 | 379 | | potable water or private well water is connected to a residence at one time, but not both |
---|
378 | 380 | | 185 |
---|
379 | 381 | | at the same time. The potable water supply line shall be protected by a reduced pressure |
---|
380 | 382 | | 186 |
---|
381 | 383 | | backflow preventer." |
---|
382 | 384 | | 187 |
---|
383 | 385 | | [(14)] (15) In IRC, Section 202, the following definition is added: "ENERGY STORAGE |
---|
384 | 386 | | 188 |
---|
385 | 387 | | SYSTEM (ESS). One or more devices, assembled together, that are capable of storing |
---|
386 | 388 | | 189 |
---|
387 | 389 | | energy for supplying electrical energy at a future time." |
---|
388 | 390 | | 190 |
---|
389 | 391 | | [(15)] (16) In IRC, Section 202, in the definition for gray water a comma is inserted after the |
---|
390 | 392 | | 191 |
---|
391 | 393 | | word "washers"; the word "and" is deleted; and the following is added to the end: "and |
---|
392 | 394 | | 192 |
---|
393 | 395 | | clear water wastes which have a pH of 6.0 to 9.0; are non-flammable; non-combustible; |
---|
394 | 396 | | 193 |
---|
395 | 397 | | without objectionable odors; non-highly pigmented; and will not interfere with the |
---|
396 | 398 | | 194 |
---|
397 | 399 | | operation of the sewer treatment facility." |
---|
398 | 400 | | 195 |
---|
399 | 401 | | [(16)] (17) In IRC, Section R202, the definition of "Potable Water" is deleted and replaced |
---|
400 | 402 | | 196 |
---|
401 | 403 | | with the following: "POTABLE WATER. Water free from impurities present in |
---|
402 | 404 | | 197 |
---|
403 | 405 | | amounts sufficient to cause disease or harmful physiological effects and conforming to |
---|
407 | 409 | | 199 |
---|
408 | 410 | | Water Quality Act, and the regulations of the public health authority having jurisdiction." |
---|
409 | 411 | | 200 |
---|
410 | 412 | | [(17)] (18) In IRC, Figure R301.2 (3), is deleted and replaced with R301.2 (3) as follows: |
---|
411 | 413 | | 201 "TABLE R301.2 (3)202 |
---|
412 | 414 | | GROUND SNOW LOADS FOR SELECTED LOCATIONS IN UTAH |
---|
413 | 415 | | 203 |
---|
414 | 416 | | City/Town County Ground Snow Load (lb/ft2)Elevation (ft) |
---|
415 | 417 | | 204 |
---|
416 | 418 | | Beaver Beaver 35 5886 |
---|
417 | 419 | | 205 |
---|
418 | 420 | | Brigham City Box Elder 42 4423 |
---|
419 | 421 | | 206 |
---|
420 | 422 | | Castle Dale Emery 32 5669 |
---|
421 | 423 | | 207 |
---|
422 | 424 | | Coalville Summit 57 5581 |
---|
423 | 425 | | 208 |
---|
424 | 426 | | Duchesne Duchesne 39 5508 |
---|
425 | 427 | | 209 |
---|
426 | 428 | | Farmington Davis 35 4318 |
---|
427 | 429 | | 210 |
---|
428 | 430 | | Fillmore Millard 30 5138 |
---|
429 | 431 | | 211 |
---|
430 | 432 | | Heber City Wasatch 60 5604 |
---|
431 | 433 | | 212 |
---|
432 | 434 | | Junction Piute 27 6030 |
---|
433 | 435 | | 213 |
---|
434 | 436 | | Kanab Kane 25 4964 |
---|
435 | 437 | | 214 |
---|
436 | 438 | | Loa Wayne 37 7060 |
---|
437 | 439 | | 215 |
---|
438 | 440 | | Logan Cache 43 4531 |
---|
439 | 441 | | 216 |
---|
440 | 442 | | Manila Daggett 26 6368 |
---|
441 | 443 | | 217 |
---|
442 | 444 | | Manti Sanpete 37 5620 |
---|
443 | 445 | | 218 |
---|
444 | 446 | | Moab Grand 21 4029 |
---|
445 | 447 | | 219 |
---|
446 | 448 | | Monticello San Juan 67 7064 |
---|
447 | 449 | | 220 |
---|
448 | 450 | | Morgan Morgan 52 5062 |
---|
449 | 451 | | 221 |
---|
450 | 452 | | Nephi Juab 39 5131 |
---|
451 | 453 | | 222 |
---|
452 | 454 | | Ogden Weber 37 4334 |
---|
453 | 455 | | 223 |
---|
454 | 456 | | Panguitch Garfield 41 6630 |
---|
455 | 457 | | 224 |
---|
456 | 458 | | Parowan Iron 32 6007 |
---|
457 | 459 | | 225 |
---|
458 | 460 | | Price Carbon 31 5558 |
---|
463 | 465 | | Richfield Sevier 27 5338 |
---|
464 | 466 | | 229 |
---|
465 | 467 | | St. George Washington 21 2585 |
---|
466 | 468 | | 230 |
---|
467 | 469 | | Salt Lake City Salt Lake 28 4239 |
---|
468 | 470 | | 231 |
---|
469 | 471 | | Tooele Tooele 35 5029 |
---|
470 | 472 | | 232 |
---|
471 | 473 | | Vernal Uintah 39 5384 |
---|
472 | 474 | | 233 |
---|
473 | 475 | | Note: To convert lb/ft2 to kN/m2, multiply by 0.0479. To convert feet to meters, multiply by 0.3048.1. |
---|
474 | 476 | | Statutory requirements of the Authority Having Jurisdiction are not included in this state ground snow |
---|
475 | 477 | | load table. |
---|
476 | 478 | | 2. For locations where there is substantial change in altitude over the city/town, the load applies at and |
---|
477 | 479 | | below the cited elevation, with a tolerance of 100 ft (30 m). |
---|
478 | 480 | | 3. For other locations in Utah, see Bean, B., Maguire, M., Sun, Y. (2018), "The Utah Snow Load |
---|
479 | 481 | | Study," Utah State University Civil and Environmental Engineering Faculty Publications, Paper 3589, |
---|
480 | 482 | | http://utahsnowload.usu.edu/, for ground snow load values." |
---|
481 | 483 | | 234 |
---|
482 | 484 | | [(18)] (19) In IRC, Section R301.6, is deleted and replaced with the following: "R301.6 |
---|
483 | 485 | | 235 |
---|
484 | 486 | | Utah Snow Loads. The snow loads specified in Table R301.2(5b) shall be used for the |
---|
485 | 487 | | 236 |
---|
486 | 488 | | jurisdictions identified in that table. Otherwise, for other locations in Utah, see Bean, |
---|
487 | 489 | | 237 |
---|
488 | 490 | | B., Maguire, M., Sun, Y. (2018), "The Utah Snow Load Study," Utah State University |
---|
489 | 491 | | 238 |
---|
490 | 492 | | Civil and Environmental Engineering Faculty Publications, Paper 3589, |
---|
491 | 493 | | 239 |
---|
492 | 494 | | http://utahsnowload.usu.edu/, for ground snow load values." |
---|
493 | 495 | | 240 |
---|
494 | 496 | | [(19)] (20) In IRC, Section R302.2, the following sentence is added at the end of the |
---|
495 | 497 | | 241 |
---|
496 | 498 | | paragraph: "When an access/maintenance agreement or easement is in place, plumbing, |
---|
497 | 499 | | 242 |
---|
498 | 500 | | mechanical ducting, schedule 40 steel gas pipe, and electric service conductors including |
---|
499 | 501 | | 243 |
---|
500 | 502 | | feeders, are permitted to penetrate the common wall at grade, above grade, or below |
---|
501 | 503 | | 244 |
---|
502 | 504 | | grade." |
---|
503 | 505 | | 245 |
---|
504 | 506 | | [(20)] (21) In IRC, Section R302.3, a new exception 3 is added as follows: "3. Accessory |
---|
505 | 507 | | 246 |
---|
506 | 508 | | dwelling units separated by walls or floor assemblies protected by not less than 1/2-inch |
---|
507 | 509 | | 247 |
---|
508 | 510 | | (12.7 mm) gypsum board or equivalent on each side of the wall or bottom of the floor |
---|
509 | 511 | | 248 |
---|
510 | 512 | | assembly are exempt from the requirements of this section." |
---|
511 | 513 | | 249 |
---|
512 | 514 | | [(21)] (22) In IRC, Section R302.5.1, the last sentence is deleted. |
---|
513 | 515 | | 250 |
---|
514 | 516 | | [(22)] (23) In IRC, Section R302.13, is deleted. |
---|
518 | 520 | | 252 |
---|
519 | 521 | | units tested in accordance with Section N1102.4.1.2 (R402.4.1.2) which has an air |
---|
520 | 522 | | 253 |
---|
521 | 523 | | tightness of 3.0 ACH (50) or greater do not require mechanical ventilation." |
---|
522 | 524 | | 254 |
---|
523 | 525 | | [(24)] (25) In IRC, Section R310.1, all words in the last sentence after "or to a yard or |
---|
524 | 526 | | 255 |
---|
525 | 527 | | court", are deleted, and Exception 3 of this section is deleted. |
---|
526 | 528 | | 256 |
---|
527 | 529 | | [(25)] (26) In IRC, Section R310.7, in the exception, the words "or accessory dwelling |
---|
528 | 530 | | 257 |
---|
529 | 531 | | units" are added after the words "sleeping rooms". |
---|
530 | 532 | | 258 [(26)] (27) IRC, Sections R311.7.45 through R311.7.5.3, are deleted and replaced with the |
---|
531 | 533 | | 259 |
---|
532 | 534 | | following: "R311.7.45.1 Stair treads and risers. R311.7.5.1 Riser height. The maximum riser |
---|
533 | 535 | | 260 |
---|
534 | 536 | | height shall be 8 inches (203 mm). The riser shall be measured vertically between leading |
---|
535 | 537 | | 261 |
---|
536 | 538 | | edges of the adjacent treads. The greatest riser height within any flight of stairs shall not |
---|
537 | 539 | | 262 |
---|
538 | 540 | | exceed the smallest by more than 3/8 inch (9.5 mm). |
---|
539 | 541 | | 263 |
---|
540 | 542 | | R311.7.5.2 Tread depth. The minimum tread depth shall be 9 inches (228 mm). The |
---|
541 | 543 | | 264 |
---|
542 | 544 | | tread depth shall be measured horizontally between the vertical planes of the foremost |
---|
543 | 545 | | 265 |
---|
544 | 546 | | projection of adjacent treads and at a right angle to the tread's leading edge. The greatest tread |
---|
545 | 547 | | 266 |
---|
546 | 548 | | depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). |
---|
547 | 549 | | 267 |
---|
548 | 550 | | Winder treads shall have a minimum tread depth of 10 inches (254 mm) measured as above at |
---|
549 | 551 | | 268 |
---|
550 | 552 | | a point 12 inches (305 mm) from the side where the treads are narrower. Winder treads shall |
---|
551 | 553 | | 269 |
---|
552 | 554 | | have a minimum tread depth of 6 inches (152 mm) at any point. Within any flight of stairs, the |
---|
553 | 555 | | 270 |
---|
554 | 556 | | greatest winder tread depth at the 12-inch (305 mm) walk line shall not exceed the smallest by |
---|
555 | 557 | | 271 |
---|
556 | 558 | | more than 3/8 inch (9.5 mm). |
---|
557 | 559 | | 272 |
---|
558 | 560 | | R311.7.5.3 Nosing. The radius of curvature at the leading edge of the tread shall be no |
---|
559 | 561 | | 273 |
---|
560 | 562 | | greater than 9/16 inch (14.3 mm). A nosing not less than 3/4 inch (19 mm) but not more than |
---|
561 | 563 | | 274 |
---|
562 | 564 | | 1 1/4 inches (32 mm) shall be provided on stairways with solid risers. The greatest nosing |
---|
563 | 565 | | 275 |
---|
564 | 566 | | projection shall not exceed the smallest nosing projection by more than 3/8 inch (9.5 mm) |
---|
565 | 567 | | 276 |
---|
566 | 568 | | between two stories, including the nosing at the level of floors and landings. Beveling of |
---|
567 | 569 | | 277 |
---|
568 | 570 | | nosing shall not exceed 1/2 inch (12.7 mm). Risers shall be vertical or sloped from the |
---|
569 | 571 | | 278 |
---|
570 | 572 | | underside of the leading edge of the tread above at an angle not more than 30 degrees (0.51 |
---|
571 | 573 | | 279 |
---|
572 | 574 | | rad) from the vertical. Open risers are permitted, provided that the opening between treads |
---|
573 | 575 | | 280 |
---|
574 | 576 | | does not permit the passage of a 4-inch diameter (102 mm) sphere. |
---|
575 | 577 | | 281 |
---|
576 | 578 | | Exceptions. |
---|
577 | 579 | | 282 |
---|
578 | 580 | | 1. A nosing is not required where the tread depth is a minimum of 10 inches (254 mm). |
---|
579 | 581 | | 283 |
---|
580 | 582 | | 2. The opening between adjacent treads is not limited on stairs with a total rise of 30 |
---|
581 | 583 | | 284 |
---|
582 | 584 | | inches (762 mm) or less." |
---|
586 | 588 | | 286 |
---|
587 | 589 | | [(28)] (29) In IRC, Sections R313.1 through R313.2.1, are deleted and replaced with the |
---|
588 | 590 | | 287 |
---|
589 | 591 | | following: "R313.1 Design and installation. When installed, automatic residential fire |
---|
590 | 592 | | 288 |
---|
591 | 593 | | sprinkler systems for townhouses or one- and two-family dwellings shall be designed |
---|
592 | 594 | | 289 |
---|
593 | 595 | | and installed in accordance with Section P2904 or NFPA 13D." |
---|
594 | 596 | | 290 |
---|
595 | 597 | | [(29)] (30) In IRC, Section R314.2.2, the words "accessory dwelling units," are added after |
---|
596 | 598 | | 291 |
---|
597 | 599 | | the words "Where alterations, repairs." |
---|
598 | 600 | | 292 |
---|
599 | 601 | | [(30)] (31) In IRC, Section R315.2.2, the words "accessory dwelling units," are added after |
---|
600 | 602 | | 293 |
---|
601 | 603 | | the words "Where alterations, repairs." |
---|
602 | 604 | | 294 |
---|
603 | 605 | | [(31)] (32) In IRC, Section 315.3, the following words are added to the first sentence after |
---|
604 | 606 | | 295 |
---|
605 | 607 | | the word "installed": "on each level of the dwelling unit and." |
---|
606 | 608 | | 296 [(32)] (33) A new IRC, Section R328.12, is added as follows: |
---|
607 | 609 | | 297 |
---|
608 | 610 | | "R328.12 Signage. A sign located on the exterior of the dwelling shall be installed at a |
---|
609 | 611 | | 298 |
---|
610 | 612 | | location approved by the authority having jurisdiction which identifies the battery chemistry |
---|
611 | 613 | | 299 |
---|
612 | 614 | | included in the ESS. This sign shall be of sufficient durability to withstand the environment |
---|
613 | 615 | | 300 |
---|
614 | 616 | | involved and shall not be handwritten." |
---|
615 | 617 | | 301 |
---|
616 | 618 | | [(33)] (34) In IRC, Section 403.1.3.5.3, an exception is added as follows: "Exception: |
---|
617 | 619 | | 302 |
---|
618 | 620 | | Vertical steel in footings shall be permitted to be located while concrete is still plastic |
---|
619 | 621 | | 303 |
---|
620 | 622 | | and before it has set. Where vertical steel resists placement or the consolidation of |
---|
621 | 623 | | 304 |
---|
622 | 624 | | concrete around steel is impeded, the concrete shall be vibrated to ensure full contact |
---|
623 | 625 | | 305 |
---|
624 | 626 | | between the vertical steel and concrete." |
---|
625 | 627 | | 306 |
---|
626 | 628 | | [(34)] (35) In IRC, Section R403.1.6, a new Exception 3 is added as follows: "3. When |
---|
627 | 629 | | 307 |
---|
628 | 630 | | anchor bolt spacing does not exceed 32 inches (813 mm) apart, anchor bolts may be |
---|
629 | 631 | | 308 |
---|
630 | 632 | | placed with a minimum of two bolts per plate section located not less than 4 inches (102 |
---|
631 | 633 | | 309 |
---|
632 | 634 | | mm) from each end of each plate section at interior bearing walls, interior braced wall |
---|
633 | 635 | | 310 |
---|
634 | 636 | | lines, and at all exterior walls." |
---|
635 | 637 | | 311 |
---|
636 | 638 | | [(35)] (36) In IRC, Section R403.1.6.1, a new exception is added at the end of Item 2 and |
---|
637 | 639 | | 312 |
---|
638 | 640 | | Item 3 as follows: "Exception: When anchor bolt spacing does not exceed 32 inches |
---|
639 | 641 | | 313 |
---|
640 | 642 | | (816 mm) apart, anchor bolts may be placed with a minimum of two bolts per plate |
---|
641 | 643 | | 314 |
---|
642 | 644 | | section located not less than 4 inches (102 mm) from each end of each plate section at |
---|
643 | 645 | | 315 |
---|
644 | 646 | | interior bearing walls, interior braced wall lines, and at all exterior walls." |
---|
645 | 647 | | 316 |
---|
646 | 648 | | [(36)] (37) In IRC, Section R404.1, a new exception is added as follows: "Exception: As an |
---|
647 | 649 | | 317 |
---|
648 | 650 | | alternative to complying with Sections R404.1 through R404.1.5.3, concrete and |
---|
649 | 651 | | 318 |
---|
650 | 652 | | masonry foundation walls may be designed in accordance with IBC Sections 1807.1.5 |
---|
654 | 656 | | 320 |
---|
655 | 657 | | [(37)] (38) In IRC, Section R405.1, a second exception is added as follows: "Exception: |
---|
656 | 658 | | 321 |
---|
657 | 659 | | When a geotechnical report has been provided for the property, a drainage system is not |
---|
658 | 660 | | 322 |
---|
659 | 661 | | required unless the drainage system is required as a condition of the geotechnical report. |
---|
660 | 662 | | 323 |
---|
661 | 663 | | The geotechnical report shall make a recommendation regarding a drainage system." |
---|
662 | 664 | | 324 |
---|
663 | 665 | | [(38)] (39) In IRC, Section R506.2.3, the words "10-mil (0.010 inch; 0.25 mm)" are deleted |
---|
664 | 666 | | 325 |
---|
665 | 667 | | and replaced with "6-mil (0.006 inch; 0.152 mm)" and the words "conforming to ASTM |
---|
666 | 668 | | 326 |
---|
667 | 669 | | E1745 Class A requirements" are deleted. |
---|
668 | 670 | | 327 |
---|
669 | 671 | | (40) In IRC, Section 507.2.1, Wood materials. The following sentence is added after the |
---|
670 | 672 | | 328 |
---|
671 | 673 | | words, "in accordance with section R317," "field applied weather resistant barrier |
---|
672 | 674 | | 329 |
---|
673 | 675 | | applied to the top of untreated material,". |
---|
674 | 676 | | 330 |
---|
675 | 677 | | Section 4. Section 15A-3-206 is amended to read: |
---|
676 | 678 | | 331 |
---|
677 | 679 | | 15A-3-206 . Amendments to Chapters 36, 37, 39, and 44 and Appendix F of IRC. |
---|
678 | 680 | | 332 |
---|
679 | 681 | | (1) In IRC, Section E3601.6.2, a new exception is added as follows: "Exception: An |
---|
680 | 682 | | 333 |
---|
681 | 683 | | occupant of an accessory dwelling unit is not required to have access to the disconnect |
---|
682 | 684 | | 334 |
---|
683 | 685 | | serving the dwelling unit in which they reside." |
---|
684 | 686 | | 335 |
---|
685 | 687 | | (2) IRC, Section E3606.5, is deleted. |
---|
686 | 688 | | 336 (3) IRC, Section E3601.7, is deleted and replaced with the following: |
---|
687 | 689 | | 337 |
---|
688 | 690 | | "3601.7 Maximum number of disconnects. The service disconnecting means shall consist of |
---|
689 | 691 | | 338 |
---|
690 | 692 | | not more than six switches or six sets of circuit breakers mounted in a single enclosure or in a |
---|
691 | 693 | | 339 |
---|
692 | 694 | | group of separate enclosures." |
---|
693 | 695 | | 340 |
---|
694 | 696 | | (4) In IRC, Section E3705.4.4, the following sentences are deleted: |
---|
695 | 697 | | 341 |
---|
696 | 698 | | "Where more than two NM cables containing two or more current-carrying |
---|
697 | 699 | | 342 |
---|
698 | 700 | | conductors are installed, without maintaining space between the cables, through the |
---|
699 | 701 | | 343 |
---|
700 | 702 | | same opening in wood framing should be sealed with thermal insulation, caulk or |
---|
701 | 703 | | 344 |
---|
702 | 704 | | sealing foam. The allowable ampacity of each conductor shall be adjusted in accordance |
---|
703 | 705 | | 345 |
---|
704 | 706 | | with Table E3705.3 and the provisions of Section E3701.3. Exception. may not apply." |
---|
705 | 707 | | 346 (5) IRC, Section E3901.4.2, is deleted and replaced with the following: |
---|
706 | 708 | | 347 |
---|
707 | 709 | | "E3901.4.2 Island and Peninsular Countertops and Work Spaces. Receptacle outlets, if |
---|
708 | 710 | | 348 |
---|
709 | 711 | | installed to serve an island or peninsular countertop or work surface, shall be installed in |
---|
710 | 712 | | 349 |
---|
711 | 713 | | accordance with E3901.4.3. If a receptacle outlet is not provided to serve an island or |
---|
712 | 714 | | 350 |
---|
713 | 715 | | peninsular countertop or work surface, provisions shall be provided at the island or peninsula |
---|
714 | 716 | | 351 |
---|
715 | 717 | | for future addition of a receptacle outlet to serve the island or peninsular countertop or work |
---|
716 | 718 | | 352 |
---|
717 | 719 | | surface." |
---|
721 | 722 | | 354 |
---|
722 | 723 | | "E3901.4.3 Receptacle Outlet Location. [Receptacle] When installed, receptacle outlets |
---|
723 | 724 | | 355 |
---|
724 | 725 | | shall be located in one or more of the following: |
---|
725 | 726 | | 356 |
---|
726 | 727 | | 1. On or above, but not more than 20 inches (508 mm) above a countertop or work |
---|
727 | 728 | | 357 |
---|
728 | 729 | | surface. |
---|
729 | 730 | | 358 |
---|
730 | 731 | | 2. In a countertop using receptacle outlet assemblies listed for use in countertops. |
---|
731 | 732 | | 359 |
---|
732 | 733 | | 3. In a work surface using receptacle outlet assemblies listed for use in work surface or |
---|
733 | 734 | | 360 |
---|
734 | 735 | | listed for use in countertops. |
---|
735 | 736 | | 361 |
---|
736 | 737 | | Receptacle outlets rendered not readily accessible by appliances fastened in place, |
---|
737 | 738 | | 362 |
---|
738 | 739 | | appliance garages, sinks, or range tops as covered in the exception to Section E3901.4.1 or |
---|
739 | 740 | | 363 |
---|
740 | 741 | | appliances occupying assigned spaces shall not be considered as these required outlets. |
---|
741 | 742 | | 364 |
---|
742 | 743 | | 4. Under the countertop not more than 14 inches from the bottom leading edge of the |
---|
743 | 744 | | 365 |
---|
744 | 745 | | countertop." |
---|
745 | 746 | | 366 |
---|
746 | 747 | | [(6)] (7) In IRC, Section 3902.1, after the word "125-volt" add "single phase 15 and 20 |
---|
747 | 748 | | 367 |
---|
748 | 749 | | ampere" and strike the words "through 250 volt." |
---|
749 | 750 | | 368 |
---|
750 | 751 | | [(7)] (8) In IRC, Section 3902.2, after the word "125-volt" add "single phase 15 and 20 |
---|
751 | 752 | | 369 |
---|
752 | 753 | | ampere" and strike the words "through 250 volt." |
---|
753 | 754 | | 370 |
---|
754 | 755 | | [(8)] (9) In IRC, Section 3902.3, after the word "125-volt" add "single phase 15 and 20 |
---|
755 | 756 | | 371 |
---|
756 | 757 | | ampere" and strike the words "through 250 volt." |
---|
757 | 758 | | 372 |
---|
758 | 759 | | [(9)] (10) In IRC, Section 3902.4, after the word "125-volt" add "single phase 15 and 20 |
---|
759 | 760 | | 373 |
---|
760 | 761 | | ampere" and strike the words "through 250 volt." |
---|
761 | 762 | | 374 |
---|
762 | 763 | | [(10)] (11) In IRC, Section 3902.5, after the word "125-volt" add the words "single phase 15 |
---|
763 | 764 | | 375 |
---|
764 | 765 | | and 20 ampere in unfinished portions of the basement shall have ground-fault |
---|
765 | 766 | | 376 |
---|
766 | 767 | | circuit-interrupter protection for personnel" and delete the rest of the section. |
---|
767 | 768 | | 377 |
---|
768 | 769 | | [(11)] (12) In IRC, Section 3902.6, after the word "125-volt" add "single phase 15 and 20 |
---|
769 | 770 | | 378 |
---|
770 | 771 | | ampere" and strike the words "through 250 volt." |
---|
771 | 772 | | 379 |
---|
772 | 773 | | [(12)] (13) In IRC, Section 3902.7, after the word "125-volt" add "single phase 15 and 20 |
---|
773 | 774 | | 380 |
---|
774 | 775 | | ampere" and strike the words "through 250 volt." |
---|
775 | 776 | | 381 |
---|
776 | 777 | | [(13)] (14) In IRC, Section 3902.8, after the word "125-volt" add "single phase 15 and 20 |
---|
777 | 778 | | 382 |
---|
778 | 779 | | ampere" and strike the words "through 250 volt." |
---|
779 | 780 | | 383 |
---|
780 | 781 | | [(14)] (15) In IRC, Section 3902.9, after the word "125-volt" add "single phase 15 and 20 |
---|
781 | 782 | | 384 |
---|
782 | 783 | | ampere" and strike the words "through 250 volt." |
---|
783 | 784 | | 385 |
---|
784 | 785 | | [(15)] (16) IRC, Section 3902.10, is deleted. |
---|
785 | 786 | | 386 |
---|
786 | 787 | | [(16)] (17) In IRC, Section 3902.12, after the word "125-volt" add "single phase 15 and 20 |
---|
790 | 791 | | 388 |
---|
791 | 792 | | [(17)] (18) In IRC, Section 3902.13, after the word "125-volt" add "single phase 15 and 20 |
---|
792 | 793 | | 389 |
---|
793 | 794 | | ampere" and strike the words "through 250 volt." |
---|
794 | 795 | | 390 |
---|
795 | 796 | | [(18)] (19) IRC, Section 3902.15, Crawl space lighting outlets, is deleted. |
---|
796 | 797 | | 391 |
---|
797 | 798 | | [(19)] (20) IRC, Section 3902.16, Equipment requiring servicing, is deleted. |
---|
798 | 799 | | 392 |
---|
799 | 800 | | [(20)] (21) IRC Section 3902.17, Outdoor outlets, is deleted. |
---|
800 | 801 | | 393 |
---|
801 | 802 | | [(21)] (22) IRC, Section 3902.19, Location of arc-fault circuit interrupters, is deleted. |
---|
802 | 803 | | 394 |
---|
803 | 804 | | [(22)] (23) IRC, Section E3902.20, Arc-fault circuit interrupter protection, is deleted. |
---|
804 | 805 | | 395 |
---|
805 | 806 | | [(23)] (24) IRC, Section E3902.21, Arc-fault circuit interrupter protection for branch circuit |
---|
806 | 807 | | 396 |
---|
807 | 808 | | extensions or modification, is deleted. |
---|
808 | 809 | | 397 |
---|
809 | 810 | | [(24)] (25) IRC, Section 4002.11, is deleted and replaced with the following: "4002.11 |
---|
810 | 811 | | 398 |
---|
811 | 812 | | Bathtub and Shower Space. Receptacles shall not be installed within or directly over a |
---|
812 | 813 | | 399 |
---|
813 | 814 | | bathtub or shower stall." |
---|
814 | 815 | | 400 |
---|
815 | 816 | | [(25)] (26) IRC, Chapter 44, is amended by deleting the standard for "ANCE." |
---|
816 | 817 | | 401 |
---|
817 | 818 | | [(26)] (27) In IRC, Chapter 44, the standard for ASHRAE is amended by changing |
---|
818 | 819 | | 402 |
---|
819 | 820 | | "34-2013" to "34-2019." |
---|
820 | 821 | | 403 |
---|
821 | 822 | | [(27)] (28) In IRC, Chapter 44, the standard for CSA, is amended by changing the: |
---|
822 | 823 | | 404 |
---|
823 | 824 | | (a) standard reference number "UL/CSA/ANCE 60335-2-40-2012" to "UL/CSA |
---|
824 | 825 | | 405 |
---|
825 | 826 | | 60335-2-40-2019"; and |
---|
826 | 827 | | 406 |
---|
827 | 828 | | (b) title "Standard for Household and Similar Electrical Appliances, Part 2: Particular |
---|
828 | 829 | | 407 |
---|
829 | 830 | | Requirements for Motor-Compressors" to "Standard for Household and Similar |
---|
830 | 831 | | 408 |
---|
831 | 832 | | Electrical Appliances, Part 2-40, Requirements for Electric Heat Pumps, Air |
---|
832 | 833 | | 409 |
---|
833 | 834 | | Conditioners and Dehumidifiers-3rd Edition." |
---|
834 | 835 | | 410 |
---|
835 | 836 | | [(28)] (29) In IRC, Chapter 44, the standard for UL, is amended by changing the: |
---|
836 | 837 | | 411 |
---|
837 | 838 | | (a) standard reference number "1995-2011" to "1995-2015"; |
---|
838 | 839 | | 412 |
---|
839 | 840 | | (b) standard reference number "UL/CSA/ANCE 60335-2-40-2012" to "UL/CSA |
---|
840 | 841 | | 413 |
---|
841 | 842 | | 60335-2-40-2019"; and |
---|
842 | 843 | | 414 |
---|
843 | 844 | | (c) title "Standard for Household and Similar Electrical Appliances, Part 2: Particular |
---|
844 | 845 | | 415 |
---|
845 | 846 | | Requirements for Motor-Compressors" to "Standard for Household and Similar |
---|
846 | 847 | | 416 |
---|
847 | 848 | | Electrical Appliances, Part 2-40, Requirements for Electric Heat Pumps, Air |
---|
848 | 849 | | 417 |
---|
849 | 850 | | Conditioners and Dehumidifiers-3rd Edition." |
---|
850 | 851 | | 418 [(29)] (30) In IRC, Chapter 44, the standard for ANSI/RESNET/ICC 201-2019 Section 4.4.4 is |
---|
851 | 852 | | 419 |
---|
852 | 853 | | added as follows: "4.4.4. Air Source Heat Pumps and Air Conditioners. For Heat Pumps and |
---|
853 | 854 | | 420 |
---|
854 | 855 | | Air Conditioners with the more recent Manufacturers Equipment Performance Ratings (HSPF2 |
---|
858 | 859 | | 422 |
---|
859 | 860 | | to HSPF and SEER values by dividing HSPF2 or SEER2 by the conversion factors in Table |
---|
860 | 861 | | 423 |
---|
861 | 862 | | 4.4.4.1(1). If the type of equipment is not determined, the conversion shall default to the |
---|
862 | 863 | | 424 |
---|
863 | 864 | | Ducted Split System factors. All calculations, including Equation 4.1-1a shall use HSPF or |
---|
864 | 865 | | 425 |
---|
865 | 866 | | SEER values as made available by the Manufacturer or converted as specified in this section. |
---|
866 | 867 | | 426 |
---|
867 | 868 | | Table 4.4.4.1(1) SEER2 and HSPF2 Conversion Factors3. |
---|
868 | 869 | | 427 Equipment Type SEER2/SEEREER/EER4 HSPF/HSPF428 |
---|
869 | 870 | | Ductless Systems 1.00 1.00 0.90 |
---|
870 | 871 | | 429 |
---|
871 | 872 | | Ducted Split System 0.95 0.95 0.85 |
---|
872 | 873 | | 430 |
---|
873 | 874 | | Ducted Package System 0.95 0.95 0.84 |
---|
874 | 875 | | 431 |
---|
875 | 876 | | Small Duct High Velocity System 1.00 not applicable0.85 |
---|
876 | 877 | | 432 |
---|
877 | 878 | | Ducted Space-Constrained Air Conditioner 0.97 not applicablenot applicable |
---|
878 | 879 | | 433 |
---|
879 | 880 | | Ducted Space-Constrained Heat Pump not applicable0.85" |
---|
880 | 881 | | 434 [(30)] (31) IRC, Chapter 44, is amended by adding the following reference standard: |
---|
881 | 882 | | 435 |
---|
882 | 883 | | 436 "Standard reference numberTitle Referenced in code |
---|
883 | 884 | | section number |
---|
884 | 885 | | 437 |
---|
885 | 886 | | USC-FCCCHR 10th |
---|
886 | 887 | | Edition Manual of Cross |
---|
887 | 888 | | Connection Control |
---|
888 | 889 | | Foundation for Cross-Connection Control and |
---|
889 | 890 | | Hydraulic Research University of Southern |
---|
890 | 891 | | California Kaprielian Hall 300 Los Angeles |
---|
891 | 892 | | CA 90089-2531 |
---|
892 | 893 | | Table P2902.3" |
---|
893 | 894 | | 438 |
---|
894 | 895 | | [(31)] (32) IRC, Chapter 44, is amended by adding the following reference standard: "UL |
---|
895 | 896 | | 439 |
---|
896 | 897 | | 9540-20: Energy Storage Systems and Equipment; R328.1, R328.2, and R328.6." |
---|
897 | 898 | | 440 |
---|
898 | 899 | | [(32)] (33)(a) When passive radon controls or portions thereof are voluntarily installed, |
---|
899 | 900 | | 441 |
---|
900 | 901 | | the voluntary installation shall comply with Appendix F of the IRC. |
---|
901 | 902 | | 442 |
---|
902 | 903 | | (b) An additional inspection of a voluntary installation described in Subsection [(27)(a) ] |
---|
903 | 904 | | 443 |
---|
904 | 905 | | (28)(a) is not required. |
---|
905 | 906 | | 444 |
---|
906 | 907 | | Section 5. Section 15A-3-601 is amended to read: |
---|
907 | 908 | | 445 |
---|
908 | 909 | | 15A-3-601 . General provisions. |
---|
909 | 910 | | 446 |
---|
910 | 911 | | The following are adopted as amendments to the NEC to be applicable statewide: |
---|
911 | 912 | | 447 |
---|
912 | 913 | | (1) The IRC provisions are adopted as the residential electrical standards applicable to |
---|
913 | 914 | | 448 |
---|
914 | 915 | | residential installations under the IRC. All other installations shall comply with the |
---|
915 | 916 | | 449 |
---|
916 | 917 | | adopted NEC. |
---|
920 | 921 | | 451 |
---|
921 | 922 | | (3) In NEC, Section 210.8(A) number (5), the word "Basements" is deleted and replaced |
---|
922 | 923 | | 452 |
---|
923 | 924 | | with the following: |
---|
924 | 925 | | 453 |
---|
925 | 926 | | "Unfinished portions or areas of the basement not intended as habitable rooms." |
---|
926 | 927 | | 454 |
---|
927 | 928 | | (4) In NEC, Section 210.8(A), number (6), the following is added after the word "Kitchens": |
---|
928 | 929 | | 455 |
---|
929 | 930 | | "where the receptacles are installed to serve the countertop surfaces." |
---|
930 | 931 | | 456 |
---|
931 | 932 | | (5) In NEC, Section 210.8(A), number (7) is deleted. |
---|
932 | 933 | | 457 |
---|
933 | 934 | | (6) In NEC, Section 210.8(D), numbers (8) through (12) are deleted. |
---|
934 | 935 | | 458 |
---|
935 | 936 | | (7) NEC, Section 210.8(F), is deleted. |
---|
936 | 937 | | 459 [(5)] (8) NEC, Sections 210.52(C) number (2) and number (3) are deleted and replaced with the |
---|
937 | 938 | | 460 |
---|
938 | 939 | | following: |
---|
939 | 940 | | 461 |
---|
940 | 941 | | "210.52(C)(2) Island and peninsular countertops and Work Surfaces. Receptacle outlets, |
---|
941 | 942 | | 462 |
---|
942 | 943 | | if installed to serve an island or peninsular countertop or work surface, shall be installed in |
---|
943 | 944 | | 463 |
---|
944 | 945 | | accordance with 210.52(C)(3). If a receptacle outlet is not provided to serve an island or |
---|
945 | 946 | | 464 |
---|
946 | 947 | | peninsular countertop or work surface, provisions shall be provided at the island or peninsula |
---|
947 | 948 | | 465 |
---|
948 | 949 | | for future addition of a receptacle outlet to serve the island or peninsular countertop or work |
---|
949 | 950 | | 466 |
---|
950 | 951 | | surface. |
---|
951 | 952 | | 467 |
---|
952 | 953 | | 210.2(C)(3) Receptacle outlet location. Receptacle outlets shall be located in one or |
---|
953 | 954 | | 468 |
---|
954 | 955 | | more of the following: |
---|
955 | 956 | | 469 |
---|
956 | 957 | | (a) On or above, but not more than 500 mm (20 inches) above a countertop or work |
---|
957 | 958 | | 470 |
---|
958 | 959 | | surface. |
---|
959 | 960 | | 471 |
---|
960 | 961 | | (b) In a countertop using receptacle assemblies listed for use in countertops. |
---|
961 | 962 | | 472 (c) In a work surface using receptacle outlet assemblies listed for use in work surfaces or listed |
---|
962 | 963 | | 473 |
---|
963 | 964 | | for use in countertops. |
---|
964 | 965 | | 474 |
---|
965 | 966 | | Receptacle outlets rendered not readily accessible by appliances fastened in place, |
---|
966 | 967 | | 475 |
---|
967 | 968 | | appliance garages, sinks, or range tops as covered in the exception to 210.52(C)(1), occupying |
---|
968 | 969 | | 476 |
---|
969 | 970 | | assigned spaces shall not be considered as these required outlets. |
---|
970 | 971 | | 477 |
---|
971 | 972 | | Exception: In dwelling units designed to be accessible to persons with disabilities, |
---|
972 | 973 | | 478 |
---|
973 | 974 | | receptacles shall be permitted to be installed not more than 300 mm (12 inches) below the |
---|
974 | 975 | | 479 |
---|
975 | 976 | | countertop or work surface. Receptacles installed below a countertop or work surface shall not |
---|
976 | 977 | | 480 |
---|
977 | 978 | | be located where the countertop or work surface extends more than 150 mm (6 inches) beyond |
---|
978 | 979 | | 481 |
---|
979 | 980 | | its support or base." |
---|
980 | 981 | | 482 |
---|
981 | 982 | | [(6)] (9) NEC, Section 210.12, is deleted. |
---|
982 | 983 | | 483 |
---|
983 | 984 | | [(7)] (10) NEC, Section 210.65, is deleted. |
---|
987 | 988 | | 485 |
---|
988 | 989 | | (12) NEC, Section 225.42 is deleted. |
---|
989 | 990 | | 486 |
---|
990 | 991 | | [(8)] (13) NEC, Section 230.67, is deleted. |
---|
991 | 992 | | 487 [(9)] (14) NEC, Section 230.71, is deleted and replaced with the following: |
---|
992 | 993 | | 488 |
---|
993 | 994 | | "230.71 Maximum Number of Disconnects. |
---|
994 | 995 | | 489 |
---|
995 | 996 | | (A) General. The service disconnecting means for each service permitted by 230.2, or for |
---|
996 | 997 | | 490 |
---|
997 | 998 | | each set of service-entrance conductors permitted by 230.40, Exception No. 1, 3, 4, or 5 shall |
---|
998 | 999 | | 491 |
---|
999 | 1000 | | consist of not more than six switches or sets of circuit breakers, or a combination of not more |
---|
1000 | 1001 | | 492 |
---|
1001 | 1002 | | than six switches and sets of circuit breakers, mounted in a single enclosure, in a group of |
---|
1002 | 1003 | | 493 |
---|
1003 | 1004 | | separate enclosures, or in or on a switchboard or in switchgear. There shall be not more than |
---|
1004 | 1005 | | 494 |
---|
1005 | 1006 | | six sets of disconnects per service grouped in any one location. For the purpose of this section, |
---|
1006 | 1007 | | 495 |
---|
1007 | 1008 | | disconnecting means installed as part of listed equipment and used solely for the following |
---|
1008 | 1009 | | 496 |
---|
1009 | 1010 | | shall not be considered a service disconnecting means: |
---|
1010 | 1011 | | 497 |
---|
1011 | 1012 | | (1) Power monitoring equipment; |
---|
1012 | 1013 | | 498 |
---|
1013 | 1014 | | (2) Surge-protective device(s); |
---|
1014 | 1015 | | 499 |
---|
1015 | 1016 | | (3) Control circuit of the ground-fault protection system; or |
---|
1016 | 1017 | | 500 |
---|
1017 | 1018 | | (4) Power-operable service disconnecting. |
---|
1018 | 1019 | | 501 |
---|
1019 | 1020 | | (B) Single-Pole Units. Two or three single-pole switches or breakers, capable of individual |
---|
1020 | 1021 | | 502 |
---|
1021 | 1022 | | operation, shall be permitted on multiwire circuits, one pole for each ungrounded conductor, as |
---|
1022 | 1023 | | 503 |
---|
1023 | 1024 | | one multipole disconnect, provided they are equipped with identified handle ties or a master |
---|
1024 | 1025 | | 504 |
---|
1025 | 1026 | | handle to disconnect all conductors of the service with no more than six operations of the hand. |
---|
1026 | 1027 | | 505 |
---|
1027 | 1028 | | (C) Beginning on July 1, 2027, Section 230.71(B) is no longer in effect." |
---|
1028 | 1029 | | 506 |
---|
1029 | 1030 | | [(10)] (15) NEC, Section 314.27(C), is deleted and replaced with the following: "314.27(C) |
---|
1030 | 1031 | | 507 |
---|
1031 | 1032 | | Boxes at Ceiling-Suspended (Paddle) Fan Outlets. Outlet boxes or outlet box systems |
---|
1032 | 1033 | | 508 |
---|
1033 | 1034 | | used as the sole support of a ceiling-suspended (paddle) fan shall be listed, shall be |
---|
1034 | 1035 | | 509 |
---|
1035 | 1036 | | marked by their manufacturer as suitable for this purpose, and shall not support |
---|
1036 | 1037 | | 510 |
---|
1037 | 1038 | | ceiling-suspended (paddle) fans that weigh more than 32 kg (70 lb). For outlet boxes or |
---|
1038 | 1039 | | 511 |
---|
1039 | 1040 | | outlet box systems designed to support ceiling-suspended (paddle) fans that weigh more |
---|
1040 | 1041 | | 512 |
---|
1041 | 1042 | | than 16 kg (35 lb), the required marking shall include the maximum weight to be |
---|
1042 | 1043 | | 513 |
---|
1043 | 1044 | | supported." |
---|
1044 | 1045 | | 514 |
---|
1045 | 1046 | | (16) In NEC, Section 334.24, the last sentence is deleted and replaced with the following: |
---|
1046 | 1047 | | 515 |
---|
1047 | 1048 | | "For flat cables, the minor diameter dimension of the cable shall be used to determine |
---|
1048 | 1049 | | 516 |
---|
1049 | 1050 | | the bending radius when bending on the flat side of the cable. For all other bends, the |
---|
1050 | 1051 | | 517 |
---|
1051 | 1052 | | major diameter dimension shall be used." |
---|
1055 | 1056 | | 519 |
---|
1056 | 1057 | | and Shower Space. Receptacles shall not be installed within or directly over a bathtub or |
---|
1057 | 1058 | | 520 |
---|
1058 | 1059 | | shower stall."] |
---|
1059 | 1060 | | 521 |
---|
1060 | 1061 | | (17) In NEC, Section 334.80, the second paragraph is deleted. |
---|
1061 | 1062 | | 522 |
---|
1062 | 1063 | | (18) In NEC, Section 338.24, the last sentence is deleted and replaced with the following: |
---|
1063 | 1064 | | 523 |
---|
1064 | 1065 | | "For flat cables, the minor diameter dimension of the cable shall be used to determine |
---|
1065 | 1066 | | 524 |
---|
1066 | 1067 | | the bending radius when bending on the flat side of the cable. For all other bends, the |
---|
1067 | 1068 | | 525 |
---|
1068 | 1069 | | major diameter dimension shall be used." |
---|
1069 | 1070 | | 526 |
---|
1070 | 1071 | | (19) In NEC, Section 406.9(B) number (2), the following words are deleted: |
---|
1071 | 1072 | | 527 |
---|
1072 | 1073 | | "be listed weather-resistant type, and installation shall". |
---|
1073 | 1074 | | 528 |
---|
1074 | 1075 | | (20) NEC, Section 700.3(A) is deleted and replaced with the following: |
---|
1075 | 1076 | | 529 |
---|
1076 | 1077 | | "700.3(A) Conductor Witness Test. |
---|
1077 | 1078 | | 530 |
---|
1078 | 1079 | | The authority having jurisdiction shall conduct or witness a test of the complete |
---|
1079 | 1080 | | 531 |
---|
1080 | 1081 | | system upon installation and periodically afterward." |
---|
1081 | 1082 | | 532 |
---|
1082 | 1083 | | Section 6. Section 19-2-107.7 is amended to read: |
---|