Old | New | Differences | |
---|---|---|---|
1 | + | Second Regular Session | |
2 | + | Seventy-fourth General Assembly | |
3 | + | STATE OF COLORADO | |
4 | + | REREVISED | |
5 | + | This Version Includes All Amendments | |
6 | + | Adopted in the Second House | |
7 | + | LLS NO. 24-0281.01 Richard Sweetman x4333 | |
1 | 8 | HOUSE BILL 24-1307 | |
2 | - | BY REPRESENTATIVE(S) Lieder and Hamrick, Amabile, Boesenecker, | |
3 | - | Brown, Clifford, Daugherty, Duran, English, Froelich, Jodeh, Joseph, | |
4 | - | Lindstedt, Mabrey, Marshall, Marvin, Ortiz, Ricks, Rutinel, Snyder, Titone, | |
5 | - | Valdez, Velasco, Willford, Woodrow, Bird, deGruy Kennedy, Hernandez, | |
6 | - | Herod, Kipp, Lindsay, Sirota, Story, Weissman, McCluskie; | |
7 | - | also SENATOR(S) Marchman and Danielson, Buckner, Cutter, Exum, | |
8 | - | Fields, Ginal, Gonzales, Hinrichsen, Jaquez Lewis, Kolker, | |
9 | - | Michaelson Jenet, Priola, Rodriguez, Sullivan, Winter F. | |
9 | + | House Committees Senate Committees | |
10 | + | Education Business, Labor, & Technology | |
11 | + | Appropriations | |
12 | + | A BILL FOR AN ACT | |
10 | 13 | C | |
11 | - | ONCERNING HVAC INFRASTRUCTURE IMPROVEMENT PROJECTS IN | |
12 | - | SCHOOLS | |
13 | - | . | |
14 | - | ||
15 | - | Be it enacted by the General Assembly of the State of Colorado: | |
16 | - | SECTION 1. Legislative declaration. (1) The general assembly | |
17 | - | finds that: | |
18 | - | (a) Students and staff in Colorado's public schools deserve access | |
19 | - | to clean, healthy air along with proper heating and cooling to improve their | |
20 | - | opportunities to learn; | |
21 | - | (b) Indoor air quality is one of several toxic threats to students in | |
22 | - | NOTE: This bill has been prepared for the signatures of the appropriate legislative | |
23 | - | officers and the Governor. To determine whether the Governor has signed the bill | |
24 | - | or taken other action on it, please consult the legislative status sheet, the legislative | |
25 | - | history, or the Session Laws. | |
26 | - | ________ | |
27 | - | Capital letters or bold & italic numbers indicate new material added to existing law; dashes | |
28 | - | through words or numbers indicate deletions from existing law and such material is not part of | |
29 | - | the act. schools; | |
30 | - | (c) The condition of inadequate school facilities can expose students | |
31 | - | and staff to mold and legacy toxins such as lead, asbestos, and industrial | |
32 | - | products and chemicals known as PCBs; poor air quality and temperature | |
33 | - | control; inadequate lighting; and excessive noise; and | |
34 | - | (d) Improving the air quality in schools can result in higher | |
35 | - | attendance, better cognitive function, less asthma and other respiratory | |
36 | - | health problems, and improved academic performance. | |
37 | - | (2) The general assembly further finds that: | |
38 | - | (a) In Colorado, many of the conditions that cause unhealthy indoor | |
39 | - | air and environmental quality impact Colorado school buildings; | |
40 | - | (b) Various Colorado schools have been featured in news stories | |
41 | - | profiling funding shortages, heating and cooling issues, and the need for | |
42 | - | facility improvements; | |
43 | - | (c) The department of education's own Facility Insight Dashboard | |
44 | - | reports the average age of school infrastructure to be forty years; and | |
45 | - | (d) State school buildings receive a poor score on the department of | |
46 | - | education's Facility Condition Index. | |
47 | - | (3) The general assembly further finds that: | |
48 | - | (a) Despite efforts by state agencies and school districts to improve | |
49 | - | indoor environmental quality in classrooms and other school buildings, | |
50 | - | many of Colorado's school districts lack the funding and staff to improve | |
51 | - | facility conditions and thereby improve school health outcomes; | |
52 | - | (b) According to the American Society of Civil Engineers' 2020 | |
53 | - | infrastructure report card, Colorado schools have an approximately $14 | |
54 | - | billion funding gap between the need for infrastructure replacements, | |
55 | - | repairs, or upgrades and money available from regular funding and budget | |
56 | - | processes; | |
57 | - | (c) The current funding sources for schools do not equitably | |
58 | - | PAGE 2-HOUSE BILL 24-1307 distribute funds, leaving many schools in rural and disproportionately | |
59 | - | impacted communities unable to pay for necessary retrofits and updates; | |
60 | - | (d) The passage of the federal "Inflation Reduction Act of 2022" and | |
61 | - | "Bipartisan Infrastructure Law", which was enacted in the federal | |
62 | - | "Infrastructure Investment and Jobs Act", have made billions of dollars in | |
63 | - | federal money available to combine with current and planned state or local | |
64 | - | funding that can help public schools improve air quality, improve student | |
65 | - | performance and staff retention, and realize significant energy savings for | |
66 | - | school districts; | |
67 | - | (e) Accessing this federal money would not only improve air quality | |
68 | - | in schools but also bring billions of dollars in economic investments in | |
69 | - | quality projects to Colorado communities and workers; and | |
70 | - | (f) Unfortunately, many of the schools with the most pressing | |
71 | - | infrastructure improvement needs lack the staff capacity to track, apply for, | |
72 | - | and manage grant funding available at the state and federal level. | |
73 | - | (4) Therefore, the general assembly declares that, in order to help | |
74 | - | schools address health concerns and energy efficiency needs, this act: | |
75 | - | (a) Makes local education providers, including the Colorado school | |
76 | - | for the deaf and the blind, eligible to receive grants from the "Infrastructure | |
77 | - | Investment and Jobs Act" cash fund created in Senate Bill 22-215, which | |
78 | - | was enacted in 2022; | |
79 | - | (b) Authorizes the governor's office to coordinate with outside | |
80 | - | entities to provide local education providers, including the Colorado school | |
81 | - | for the deaf and the blind, with project planning, grant writing, and other | |
82 | - | technical assistance, such as school ventilation and energy efficiency | |
83 | - | verification, as needed; | |
84 | - | (c) Ensures that school districts' federal funding applications remain | |
85 | - | competitive by requiring the use of certified contractors or the negotiation | |
86 | - | of a project labor agreement to complete HVAC infrastructure improvement | |
87 | - | projects receiving federal funding and requiring compliance with the labor | |
88 | - | standards outlined in federal funding opportunities; | |
89 | - | (d) Will save schools money by ensuring that facility improvement | |
90 | - | PAGE 3-HOUSE BILL 24-1307 projects are completed by a highly skilled workforce and result in | |
91 | - | measurable energy efficiency improvements and health improvements for | |
92 | - | students and staff; and | |
93 | - | (e) Allows Colorado's school districts to choose to undergo an | |
94 | - | HVAC assessment and find a pathway to fund any improvements identified | |
95 | - | without mandating that any school must undergo an assessment or HVAC | |
96 | - | improvements. | |
97 | - | SECTION 2. In Colorado Revised Statutes, add 22-32-152 as | |
98 | - | follows: | |
99 | - | 22-32-152. School ventilation and energy efficiency verification | |
100 | - | and repair - definitions - applicability of section - ventilation | |
101 | - | verification assessment - filtration - HVAC assessment report - | |
102 | - | mechanical engineer review - adjustments, repairs, upgrades, and | |
103 | - | replacements - HVAC verification report - periodic inspections and | |
104 | - | ongoing maintenance - certified contractors - grants. (1) Definitions. | |
105 | - | A | |
106 | - | S USED IN THIS SECTION, UNLESS THE CONTEXT OTHERWISE REQUIRES : | |
14 | + | ONCERNING HVAC INFRASTRUCTURE IMPROVEMENT PROJECTS IN101 | |
15 | + | SCHOOLS.102 | |
16 | + | Bill Summary | |
17 | + | (Note: This summary applies to this bill as introduced and does | |
18 | + | not reflect any amendments that may be subsequently adopted. If this bill | |
19 | + | passes third reading in the house of introduction, a bill summary that | |
20 | + | applies to the reengrossed version of this bill will be available at | |
21 | + | http://leg.colorado.gov | |
22 | + | .) | |
23 | + | The bill requires a school district board of education, a charter | |
24 | + | school, an institute charter school, a board of cooperative services, or the | |
25 | + | Colorado school for the deaf and the blind (school administrative entity) | |
26 | + | to satisfy certain requirements concerning installation, inspection, and | |
27 | + | maintenance of heating, ventilation, and air conditioning (HVAC) | |
28 | + | systems in schools if the school administrative entity undertakes HVAC | |
29 | + | SENATE | |
30 | + | 3rd Reading Unamended | |
31 | + | May 7, 2024 | |
32 | + | SENATE | |
33 | + | Amended 2nd Reading | |
34 | + | May 6, 2024 | |
35 | + | HOUSE | |
36 | + | 3rd Reading Unamended | |
37 | + | April 26, 2024 | |
38 | + | HOUSE | |
39 | + | Amended 2nd Reading | |
40 | + | April 25, 2024 | |
41 | + | HOUSE SPONSORSHIP | |
42 | + | Lieder and Hamrick, Amabile, Boesenecker, Brown, Clifford, Daugherty, Duran, English, | |
43 | + | Froelich, Jodeh, Joseph, Lindstedt, Mabrey, Marshall, Marvin, Ortiz, Ricks, Rutinel, Snyder, | |
44 | + | Titone, Valdez, Velasco, Willford, Woodrow | |
45 | + | SENATE SPONSORSHIP | |
46 | + | Marchman and Danielson, Buckner, Cutter, Exum, Fields, Ginal, Gonzales, Hinrichsen, | |
47 | + | Jaquez Lewis, Kolker, Michaelson Jenet, Priola, Rodriguez, Sullivan, Winter F. | |
48 | + | Shading denotes HOUSE amendment. Double underlining denotes SENATE amendment. | |
49 | + | Capital letters or bold & italic numbers indicate new material to be added to existing law. | |
50 | + | Dashes through the words or numbers indicate deletions from existing law. infrastructure improvements using money made available by a federal | |
51 | + | government source or by a federal government source in combination | |
52 | + | with a state government source specifically for such purpose. | |
53 | + | The requirements established in the bill concern: | |
54 | + | ! Ventilation verification assessments, which include | |
55 | + | assessments of an HVAC system's filtration, ventilation | |
56 | + | exhaust, economizers, demand control ventilation, air | |
57 | + | distribution and building pressurization, general | |
58 | + | maintenance requirements, operational controls, and carbon | |
59 | + | dioxide output; | |
60 | + | ! The preparation of HVAC assessment reports; | |
61 | + | ! The review of HVAC assessment reports by mechanical | |
62 | + | engineers, who make recommendations regarding | |
63 | + | necessary repairs and improvements and estimate | |
64 | + | associated costs; | |
65 | + | ! HVAC adjustments, repairs, upgrades, and replacements; | |
66 | + | ! The preparation of HVAC verification reports and the | |
67 | + | submission of the reports to the state board of education; | |
68 | + | and | |
69 | + | ! Periodic inspections and ongoing maintenance. | |
70 | + | The bill establishes mandatory criteria that an HVAC contractor | |
71 | + | must satisfy in order to perform work described in the bill. A school | |
72 | + | administrative entity that undertakes HVAC infrastructure improvements | |
73 | + | using money made available by a federal government source or by a | |
74 | + | federal government source in combination with a state government source | |
75 | + | must do so using only contractors on the certified contractor list | |
76 | + | established by the department of labor and employment. | |
77 | + | The bill allows a school administrative entity to apply for grants | |
78 | + | to pay for HVAC infrastructure improvement projects and establishes | |
79 | + | requirements for school administrative entities that apply for grants from | |
80 | + | federal and state government sources. | |
81 | + | The bill allows the governor's office to expend money from the | |
82 | + | "Infrastructure Investment and Jobs Act" cash fund to provide grant | |
83 | + | writing support and project planning support to school administrative | |
84 | + | entities that are undertaking HVAC infrastructure improvement projects. | |
85 | + | Be it enacted by the General Assembly of the State of Colorado:1 | |
86 | + | SECTION 1. Legislative declaration. (1) The general assembly2 | |
87 | + | finds that:3 | |
88 | + | (a) Students and staff in Colorado's public schools deserve access4 | |
89 | + | to clean, healthy air along with proper heating and cooling to improve5 | |
90 | + | 1307-2- their opportunities to learn;1 | |
91 | + | (b) Indoor air quality is one of several toxic threats to students in2 | |
92 | + | schools;3 | |
93 | + | (c) The condition of inadequate school facilities can expose4 | |
94 | + | students and staff to mold and legacy toxins such as lead, asbestos, and5 | |
95 | + | industrial products and chemicals known as PCBs; poor air quality and6 | |
96 | + | temperature control; inadequate lighting; and excessive noise; and7 | |
97 | + | (d) Improving the air quality in schools can result in higher8 | |
98 | + | attendance, better cognitive function, less asthma and other respiratory9 | |
99 | + | health problems, and improved academic performance.10 | |
100 | + | (2) The general assembly further finds that:11 | |
101 | + | (a) In Colorado, many of the conditions that cause unhealthy12 | |
102 | + | indoor air and environmental quality impact Colorado school buildings;13 | |
103 | + | (b) Various Colorado schools have been featured in news stories14 | |
104 | + | profiling funding shortages, heating and cooling issues, and the need for15 | |
105 | + | facility improvements;16 | |
106 | + | (c) The department of education's own Facility Insight Dashboard17 | |
107 | + | reports the average age of school infrastructure to be forty years; and18 | |
108 | + | (d) State school buildings receive a poor score on the department19 | |
109 | + | of education's Facility Condition Index.20 | |
110 | + | (3) The general assembly further finds that:21 | |
111 | + | (a) Despite efforts by state agencies and school districts to22 | |
112 | + | improve indoor environmental quality in classrooms and other school23 | |
113 | + | buildings, many of Colorado's school districts lack the funding and staff24 | |
114 | + | to improve facility conditions and thereby improve school health25 | |
115 | + | outcomes;26 | |
116 | + | (b) According to the American Society of Civil Engineers' 202027 | |
117 | + | 1307 | |
118 | + | -3- infrastructure report card, Colorado schools have an approximately $141 | |
119 | + | billion funding gap between the need for infrastructure replacements,2 | |
120 | + | repairs, or upgrades and money available from regular funding and budget3 | |
121 | + | processes;4 | |
122 | + | (c) The current funding sources for schools do not equitability5 | |
123 | + | distribute funds, leaving many schools in rural and disproportionately6 | |
124 | + | impacted communities unable to pay for necessary retrofits and updates;7 | |
125 | + | (d) The passage of the federal "Inflation Reduction Act of 2022"8 | |
126 | + | and "Bipartisan Infrastructure Law", which was enacted in the federal9 | |
127 | + | "Infrastructure Investment and Jobs Act", have made billions of dollars10 | |
128 | + | in federal money available to combine with current and planned state or11 | |
129 | + | local funding that can help public schools improve air quality, improve12 | |
130 | + | student performance and staff retention, and realize significant energy13 | |
131 | + | savings for school districts;14 | |
132 | + | (e) Accessing this federal money would not only improve air15 | |
133 | + | quality in schools but also bring billions of dollars in economic16 | |
134 | + | investments in quality projects to Colorado communities and workers;17 | |
135 | + | and18 | |
136 | + | (f) Unfortunately, many of the schools with the most pressing19 | |
137 | + | infrastructure improvement needs lack the staff capacity to track, apply20 | |
138 | + | for, and manage grant funding available at the state and federal level.21 | |
139 | + | (4) Therefore, the general assembly declares that, in order to help22 | |
140 | + | schools address health concerns and energy efficiency needs, this act:23 | |
141 | + | (a) Makes local education providers, including the Colorado24 | |
142 | + | school for the deaf and the blind, eligible to receive grants from the25 | |
143 | + | "Infrastructure Investment and Jobs Act" cash fund created in Senate Bill26 | |
144 | + | 22-215, which was enacted in 2022;27 | |
145 | + | 1307 | |
146 | + | -4- (b) Authorizes the governor's office to coordinate with outside1 | |
147 | + | entities to provide local education providers, including the Colorado2 | |
148 | + | school for the deaf and the blind, with project planning, grant writing, and3 | |
149 | + | other technical assistance, such as school ventilation and energy4 | |
150 | + | efficiency verification, as needed;5 | |
151 | + | (c) Ensures that school districts' federal funding applications6 | |
152 | + | remain competitive by requiring the use of certified contractors or the7 | |
153 | + | negotiation of a project labor agreement to complete HVAC infrastructure8 | |
154 | + | improvement projects receiving federal funding and requiring compliance9 | |
155 | + | with the labor standards outlined in federal funding opportunities; 10 | |
156 | + | (d) Will save schools money by ensuring that facility improvement11 | |
157 | + | projects are completed by a highly skilled workforce and result in12 | |
158 | + | measurable energy efficiency improvements and health improvements for13 | |
159 | + | students and staff; and14 | |
160 | + | (e) Allows Colorado's school districts to choose to undergo an15 | |
161 | + | HVAC assessment and find a pathway to fund any improvements16 | |
162 | + | identified without mandating that any school must undergo an assessment17 | |
163 | + | or HVAC improvements.18 | |
164 | + | SECTION 2. In Colorado Revised Statutes, add 22-32-152 as19 | |
165 | + | follows:20 | |
166 | + | 22-32-152. School ventilation and energy efficiency21 | |
167 | + | verification and repair - definitions - applicability of section -22 | |
168 | + | ventilation verification assessment - filtration - HVAC assessment23 | |
169 | + | report - mechanical engineer review - adjustments, repairs, upgrades,24 | |
170 | + | and replacements - HVAC verification report - periodic inspections25 | |
171 | + | and ongoing maintenance - certified contractors - grants.26 | |
172 | + | (1) Definitions. A | |
173 | + | S USED IN THIS SECTION, UNLESS THE CONTEXT27 | |
174 | + | 1307 | |
175 | + | -5- OTHERWISE REQUIRES:1 | |
107 | 176 | (a) "ANAB" | |
108 | - | MEANS THE AMERICAN NATIONAL STANDARDS | |
109 | - | INSTITUTE NATIONAL ACCREDITATION BOARD. | |
177 | + | MEANS THE AMERICAN NATIONAL STANDARDS2 | |
178 | + | I | |
179 | + | NSTITUTE NATIONAL ACCREDITATION BOARD.3 | |
110 | 180 | (b) "ASHRAE" | |
111 | - | MEANS THE AMERICAN SOCIETY OF HEATING, | |
181 | + | MEANS THE AMERICAN SOCIETY OF HEATING,4 | |
112 | 182 | R | |
113 | - | EFRIGERATION AND AIR-CONDITIONING ENGINEERS. | |
183 | + | EFRIGERATION AND AIR-CONDITIONING ENGINEERS.5 | |
114 | 184 | (c) "C | |
115 | - | ERTIFIED CONTRACTOR" MEANS A CONTRACTOR ON THE | |
116 | - | CERTIFIED CONTRACTOR LIST | |
117 | - | . | |
185 | + | ERTIFIED CONTRACTOR" MEANS A CONTRACTOR ON THE6 | |
186 | + | CERTIFIED CONTRACTOR LIST.7 | |
118 | 187 | (d) "C | |
119 | - | ERTIFIED CONTRACTOR LIST " MEANS THE CERTIFIED | |
120 | - | CONTRACTOR LIST CREATED BY THE DEPARTMENT OF LABOR AND | |
121 | - | EMPLOYMENT PURSUANT TO SECTION | |
122 | - | 40-3.2-105.6 (3)(a). | |
188 | + | ERTIFIED CONTRACTOR LIST " MEANS THE CERTIFIED8 | |
189 | + | CONTRACTOR LIST CREATED BY THE DEPARTMENT OF LABOR AND9 | |
190 | + | EMPLOYMENT PURSUANT TO SECTION 40-3.2-105.6 (3)(a).10 | |
123 | 191 | (e) "C | |
124 | - | ERTIFIED TAB TECHNICIAN" MEANS A | |
125 | - | TO PERFORM TESTING | |
126 | - | ||
192 | + | ERTIFIED TAB TECHNICIAN" MEANS A TECHNICIAN11 | |
193 | + | CERTIFIED TO PERFORM TESTING, ADJUSTING, AND BALANCING OF HVAC12 | |
194 | + | SYSTEMS BY:13 | |
127 | 195 | (I) T | |
128 | - | HE ASSOCIATED AIR BALANCE COUNCIL; | |
196 | + | HE ASSOCIATED AIR BALANCE COUNCIL;14 | |
129 | 197 | (II) T | |
130 | - | HE NATIONAL ENVIRONMENTAL BALANCING BUREAU; | |
131 | - | PAGE 4-HOUSE BILL 24-1307 (III) THE TESTING, ADJUSTING AND BALANCING BUREAU; OR | |
132 | - | (IV) A SUCCESSOR ORGANIZATION OF AN ORGANIZATION NAMED IN | |
133 | - | SUBSECTION | |
134 | - | (1)(e)(I), (1)(e)(II), OR (1)(e)(III) OF THIS SECTION. | |
198 | + | HE NATIONAL ENVIRONMENTAL BALANCING BUREAU;15 | |
199 | + | (III) T | |
200 | + | HE TESTING, ADJUSTING AND BALANCING BUREAU; OR16 | |
201 | + | (IV) A | |
202 | + | SUCCESSOR ORGANIZATION OF AN ORGANIZATION NAMED17 | |
203 | + | IN SUBSECTION (1)(e)(I), (1)(e)(II), OR (1)(e)(III) OF THIS SECTION.18 | |
135 | 204 | (f) "CO2" | |
136 | - | MEANS CARBON DIOXIDE. | |
205 | + | MEANS CARBON DIOXIDE.19 | |
137 | 206 | (g) "D | |
138 | - | EPARTMENT" MEANS THE DEPARTMENT OF EDUCATION | |
139 | - | CREATED IN SECTION | |
140 | - | 24-1-115. | |
207 | + | EPARTMENT" MEANS THE DEPARTMENT OF EDUCATION20 | |
208 | + | CREATED IN SECTION 24-1-115.21 | |
141 | 209 | (h) "HVAC" | |
142 | - | MEANS HEATING , VENTILATION, AND AIR | |
143 | - | CONDITIONING | |
144 | - | . | |
210 | + | MEANS HEATING , VENTILATION, AND AIR22 | |
211 | + | CONDITIONING.23 | |
145 | 212 | (i) "HVAC | |
146 | - | ASSESSMENT REPORT" MEANS THE HVAC ASSESSMENT | |
147 | - | REPORT DESCRIBED IN SUBSECTION | |
148 | - | (4) OF THIS SECTION. | |
149 | - | (j) "I | |
150 | - | NTERNATIONAL MECHANICAL CODE " MEANS THE 2021 | |
151 | - | INTERNATIONAL MECHANICAL CODE PUBLISHED BY THE INTERNATIONAL | |
152 | - | CODE COUNCIL OR THE MOST RECENT VERSION ADOPTED BY THE OFFICE OF | |
153 | - | THE STATE ARCHITECT CREATED IN SECTION | |
154 | - | 24-30-1302.5. | |
155 | - | (k) "ISO/IEC | |
156 | - | 17024 PERSONNEL CERTIFICATION STANDARD " MEANS | |
157 | - | THE | |
158 | - | ISO/IEC 17024 PERSONNEL CERTIFICATION ACCREDITATION STANDARD | |
159 | - | DEVELOPED BY THE | |
160 | - | INTERNATIONAL ORGANIZATION FOR STANDARDIZATION | |
161 | - | AND THE | |
162 | - | INTERNATIONAL ELECTROTECHNICAL COMMISSION FOR THE | |
163 | - | PURPOSE OF CERTIFYING PERSONNEL | |
164 | - | . | |
213 | + | ASSESSMENT REPORT" MEANS THE HVAC ASSESSMENT24 | |
214 | + | REPORT DESCRIBED IN SUBSECTION (4) OF THIS SECTION.25 | |
215 | + | (j) "INTERNATIONAL MECHANICAL CODE" MEANS THE 202126 | |
216 | + | INTERNATIONAL MECHANICAL CODE PUBLISHED BY THE INTERNATIONAL27 | |
217 | + | 1307 | |
218 | + | -6- CODE COUNCIL OR THE MOST RECENT VERSION ADOPTED BY THE OFFICE1 | |
219 | + | OF THE STATE ARCHITECT CREATED IN SECTION 24-30-1302.5.2 | |
220 | + | (k) "ISO/IEC 17024 PERSONNEL CERTIFICATION STANDARD "3 | |
221 | + | MEANS THE ISO/IEC 17024 PERSONNEL CERTIFICATION ACCREDITATION4 | |
222 | + | STANDARD DEVELOPED BY THE INTERNATIONAL ORGANIZATION FOR5 | |
223 | + | S | |
224 | + | TANDARDIZATION AND THE INTERNATIONAL ELECTROTECHNICAL6 | |
225 | + | C | |
226 | + | OMMISSION FOR THE PURPOSE OF CERTIFYING PERSONNEL .7 | |
165 | 227 | (l) "L | |
166 | 228 | OCAL EDUCATION PROVIDER " MEANS: | |
229 | + | 8 | |
167 | 230 | (I) A | |
168 | 231 | LOCAL EDUCATION PROVIDER , AS DEFINED IN SECTION | |
169 | - | 22-16-103 (4); AND | |
170 | - | (II) THE COLORADO SCHOOL FOR THE DEAF AND THE BLIND CREATED | |
171 | - | IN SECTION | |
172 | - | 22-80-102. | |
173 | - | (m) "M | |
174 | - | ECHANICAL ENGINEER" MEANS A PROFESSIONAL ENGINEER | |
175 | - | WHO IS LICENSED PURSUANT TO PART | |
176 | - | 2 OF ARTICLE 120 OF TITLE 12 AND HAS | |
177 | - | PROFESSIONAL EXPERIENCE WITH | |
178 | - | HVAC SYSTEMS. | |
179 | - | (n) "MERV" | |
180 | - | MEANS MINIMUM EFFICIENCY REPORTING VALUE , AS | |
181 | - | PAGE 5-HOUSE BILL 24-1307 ESTABLISHED BY ANAB/ASHRAE STANDARD 52.2-2017, "METHOD OF | |
182 | - | TESTING GENERAL VENTILATION AIR-CLEANING DEVICES FOR REMOVAL | |
183 | - | EFFICIENCY BY PARTICLE SIZE". | |
184 | - | (o) "NO | |
185 | - | X" HAS THE MEANING SET FORTH IN SECTION 25-7-1502 (8). | |
186 | - | (p) "O | |
187 | - | CCUPIED AREAS" MEANS THE CLASSROOMS , AUDITORIUMS, | |
188 | - | GYMNASIUMS, CAFETERIAS, NURSES' OFFICES, RESTROOMS, AND OFFICES OF | |
189 | - | A SCHOOL | |
190 | - | . | |
191 | - | (q) "P | |
192 | - | PM" MEANS PARTS PER MILLION. | |
193 | - | (r) "P | |
194 | - | ROJECT LABOR AGREEMENT " HAS THE MEANING SET FORTH IN | |
195 | - | 48 CFR 52.222-34. | |
196 | - | (s) "Q | |
197 | - | UALIFIED ADJUSTING PERSONNEL" MEANS: | |
232 | + | 9 | |
233 | + | 22-16-103 | |
234 | + | (4); AND | |
235 | + | 10 | |
236 | + | (II) T | |
237 | + | HE COLORADO SCHOOL FOR THE DEAF AND THE BLIND | |
238 | + | 11 | |
239 | + | CREATED IN SECTION 22-80-102.12 | |
240 | + | (m) "MECHANICAL ENGINEER" MEANS A PROFESSIONAL ENGINEER13 | |
241 | + | WHO IS LICENSED PURSUANT TO PART 2 OF ARTICLE 120 OF TITLE 12 AND14 | |
242 | + | HAS PROFESSIONAL EXPERIENCE WITH HVAC SYSTEMS.15 | |
243 | + | (n) "MERV" MEANS MINIMUM EFFICIENCY REPORTING VALUE , AS16 | |
244 | + | ESTABLISHED BY ANAB/ASHRAE STANDARD 52.2-2017, "METHOD OF17 | |
245 | + | T | |
246 | + | ESTING GENERAL VENTILATION AIR-CLEANING DEVICES FOR REMOVAL18 | |
247 | + | E | |
248 | + | FFICIENCY BY PARTICLE SIZE".19 | |
249 | + | (o) | |
250 | + | "NOX" HAS THE MEANING SET FORTH IN SECTION 25-7-150220 | |
251 | + | (8).21 | |
252 | + | (p) "OCCUPIED AREAS" MEANS THE CLASSROOMS, AUDITORIUMS,22 | |
253 | + | GYMNASIUMS, CAFETERIAS, NURSES' OFFICES, RESTROOMS, AND OFFICES23 | |
254 | + | OF A SCHOOL.24 | |
255 | + | (q) "PPM" MEANS PARTS PER MILLION.25 | |
256 | + | (r) "PROJECT LABOR AGREEMENT " HAS THE MEANING SET FORTH26 | |
257 | + | IN 48 CFR 52.222-34.27 | |
258 | + | 1307 | |
259 | + | -7- (s) "QUALIFIED ADJUSTING PERSONNEL" MEANS:1 | |
198 | 260 | (I) A | |
199 | - | CERTIFIED TAB TECHNICIAN; OR | |
200 | - | (II) A WORKER WHO IS UNDER THE DIRECT SUPERVISION OF A | |
201 | - | CERTIFIED | |
202 | - | TAB TECHNICIAN. | |
203 | - | (t) "Q | |
204 | - | UALIFIED PERSONNEL" MEANS QUALIFIED TESTING PERSONNEL , | |
205 | - | QUALIFIED ADJUSTING PERSONNEL , OR OTHER WORKFORCE THAT IS HIRED BY | |
206 | - | AND UNDER THE DIRECT SUPERVISION OF A CERTIFIED CONTRACTOR FOR THE | |
207 | - | PURPOSE OF PERFORMING | |
208 | - | HVAC WORK. | |
209 | - | (u) "Q | |
210 | - | UALIFIED TESTING PERSONNEL" MEANS: | |
261 | + | CERTIFIED TAB TECHNICIAN; OR2 | |
262 | + | (II) A | |
263 | + | WORKER WHO IS UNDER THE DIRECT SUPERVISION OF A3 | |
264 | + | CERTIFIED TAB TECHNICIAN.4 | |
265 | + | (t) | |
266 | + | "QUALIFIED PERSONNEL" MEANS QUALIFIED TESTING5 | |
267 | + | PERSONNEL, QUALIFIED ADJUSTING PERSONNEL , OR OTHER WORKFORCE6 | |
268 | + | THAT IS HIRED BY AND UNDER THE DIRECT SUPERVISION OF A CERTIFIED7 | |
269 | + | CONTRACTOR FOR THE PURPOSE OF PERFORMING HVAC WORK.8 | |
270 | + | (u) "QUALIFIED TESTING PERSONNEL" MEANS:9 | |
211 | 271 | (I) A | |
212 | - | CERTIFIED TAB TECHNICIAN; OR | |
213 | - | (II) AN INDIVIDUAL CERTIFIED TO PERFORM VENTILATION | |
214 | - | ASSESSMENTS OF | |
215 | - | HVAC SYSTEMS BY THE INTERNATIONAL CERTIFICATION | |
216 | - | BOARD OR THROUGH AN EQUIVALENT CERTIFICATION PROGRAM OR BODY | |
217 | - | ACCREDITED UNDER THE | |
218 | - | ISO/IEC 17024 PERSONNEL CERTIFICATION | |
219 | - | STANDARD | |
220 | - | . | |
221 | - | (v) "R | |
222 | - | EGISTERED APPRENTICESHIP PROGRAM " HAS THE MEANING SET | |
223 | - | FORTH IN SECTION | |
224 | - | 8-15.7-101 (13). | |
225 | - | PAGE 6-HOUSE BILL 24-1307 (w) "SCHOOL" MEANS AN EDUCATIONAL FACILITY OPERATED BY A | |
226 | - | LOCAL EDUCATION PROVIDER | |
227 | - | . | |
228 | - | (x) "TAB" | |
229 | - | MEANS TESTING, ADJUSTING, AND BALANCING OF AN | |
230 | - | HVAC SYSTEM. | |
272 | + | CERTIFIED TAB TECHNICIAN; OR10 | |
273 | + | (II) A | |
274 | + | N INDIVIDUAL CERTIFIED TO PERFORM VENTILATION11 | |
275 | + | ASSESSMENTS OF HVAC SYSTEMS BY THE INTERNATIONAL CERTIFICATION12 | |
276 | + | B | |
277 | + | OARD OR THROUGH AN EQUIVALENT CERTIFICATION PROGRAM OR BODY13 | |
278 | + | ACCREDITED UNDER THE ISO/IEC 17024 PERSONNEL CERTIFICATION14 | |
279 | + | STANDARD.15 | |
280 | + | (v) | |
281 | + | "REGISTERED APPRENTICESHIP PROGRAM " HAS THE MEANING16 | |
282 | + | SET FORTH IN SECTION 8-15.7-101 (13).17 | |
283 | + | (w) "SCHOOL" MEANS AN EDUCATIONAL FACILITY OPERATED BY18 | |
284 | + | A LOCAL EDUCATION PROVIDER .19 | |
285 | + | 20 | |
286 | + | 21 | |
287 | + | (x) "TAB" MEANS TESTING, ADJUSTING, AND BALANCING OF AN22 | |
288 | + | HVAC | |
289 | + | SYSTEM.23 | |
231 | 290 | (2) Applicability of section. (a) O | |
232 | - | N AND AFTER THE | |
233 | - | DATE OF THIS SECTION | |
234 | - | ||
235 | - | HVAC | |
236 | - | ||
237 | - | GOVERNMENT SOURCE | |
238 | - | ||
239 | - | ||
240 | - | ||
241 | - | ||
242 | - | HVAC INFRASTRUCTURE IMPROVEMENTS . | |
291 | + | N AND AFTER THE EFFECTIVE24 | |
292 | + | DATE OF THIS SECTION, IF A LOCAL EDUCATION PROVIDER | |
293 | + | UNDERTAKES25 | |
294 | + | HVAC | |
295 | + | INFRASTRUCTURE IMPROVEMENTS AT A SCHOOL USING MONEY26 | |
296 | + | MADE AVAILABLE BY A FEDERAL GOVERNMENT SOURCE OR BY A FEDERAL27 | |
297 | + | 1307 | |
298 | + | -8- GOVERNMENT SOURCE IN COMBINATION WITH A STATE GOVERNMENT1 | |
299 | + | SOURCE SPECIFICALLY FOR SUCH PURPOSE , THE LOCAL EDUCATION2 | |
300 | + | PROVIDER SHALL COMPLY WITH THE PROCEDURES SET FORTH IN THIS3 | |
301 | + | SECTION IN IMPLEMENTING THE HVAC INFRASTRUCTURE IMPROVEMENTS .4 | |
243 | 302 | (b) N | |
244 | - | OTWITHSTANDING ANY PROVISION OF THIS SECTION TO THE | |
245 | - | CONTRARY | |
246 | - | , A LOCAL EDUCATION PROVIDER IS NOT REQUIRED TO SATISFY | |
247 | - | THE REQUIREMENTS OF THIS SECTION UNLESS THE LOCAL EDUCATION | |
248 | - | PROVIDER RECEIVES MONEY FROM A FEDERAL GOVERNMENT SOURCE OR | |
249 | - | FROM A FEDERAL GOVERNMENT SOURCE IN COMBINATION WITH A STATE | |
250 | - | GOVERNMENT SOURCE | |
251 | - | , WHICH MONEY IS MADE AVAILABLE FOR THE SPECIFIC | |
252 | - | PURPOSE OF IMPLEMENTING | |
253 | - | HVAC SYSTEM IMPROVEMENTS. | |
303 | + | OTWITHSTANDING ANY PROVISION OF THIS SECTION TO THE5 | |
304 | + | CONTRARY, A LOCAL EDUCATION PROVIDER | |
305 | + | IS NOT REQUIRED TO SATISFY6 | |
306 | + | THE REQUIREMENTS OF THIS SECTION UNLESS THE LOCAL EDUCATION7 | |
307 | + | PROVIDER RECEIVES MONEY FROM A FEDERAL GOVERNMENT SOURCE OR8 | |
308 | + | FROM A FEDERAL GOVERNMENT SOURCE IN COMBINATION WITH A STATE9 | |
309 | + | GOVERNMENT SOURCE , WHICH MONEY IS MADE AVAILABLE FOR THE10 | |
310 | + | SPECIFIC PURPOSE OF IMPLEMENTING HVAC SYSTEM IMPROVEMENTS.11 | |
254 | 311 | (3) Ventilation verification assessment. Q | |
255 | - | UALIFIED PERSONNEL | |
256 | - | SHALL PERFORM ALL OF THE FOLLOWING | |
257 | - | : | |
312 | + | UALIFIED PERSONNEL12 | |
313 | + | SHALL PERFORM ALL OF THE FOLLOWING :13 | |
258 | 314 | (a) Filtration. MERV | |
259 | - | 13 OR BETTER FILTRATION MUST BE | |
260 | - | INSTALLED IN A SCHOOL | |
261 | - | 'S HVAC SYSTEM WHERE FEASIBLE. QUALIFIED | |
262 | - | PERSONNEL SHALL | |
263 | - | : | |
315 | + | 13 OR BETTER FILTRATION MUST BE14 | |
316 | + | INSTALLED IN A SCHOOL'S HVAC SYSTEM WHERE FEASIBLE. QUALIFIED15 | |
317 | + | PERSONNEL SHALL:16 | |
264 | 318 | (I) R | |
265 | - | EVIEW SYSTEM CAPACITY AND AIRFLOW TO DETERMINE THE | |
266 | - | HIGHEST | |
267 | - | MERV FILTRATION THAT CAN BE INSTALLED WITHOUT ADVERSELY | |
268 | - | IMPACTING EQUIPMENT | |
269 | - | ; | |
319 | + | EVIEW SYSTEM CAPACITY AND AIRFLOW TO DETERMINE THE17 | |
320 | + | HIGHEST MERV FILTRATION THAT CAN BE INSTALLED WITHOUT18 | |
321 | + | ADVERSELY IMPACTING EQUIPMENT ;19 | |
270 | 322 | (II) R | |
271 | - | EPLACE OR UPGRADE FILTERS WHERE NEEDED AND | |
272 | - | THAT FILTERS ARE INSTALLED CORRECTLY | |
273 | - | ||
274 | - | ||
275 | - | FREQUENCY OF FILTER REPLACEMENTS , OR UPGRADES TO ALLOW | |
276 | - | PROTECTIVE FILTRATION AND RECORD THE RECOMMENDATIONS | |
277 | - | ||
323 | + | EPLACE OR UPGRADE FILTERS WHERE NEEDED AND VERIFY20 | |
324 | + | THAT FILTERS ARE INSTALLED CORRECTLY ; AND21 | |
325 | + | (III) I | |
326 | + | SSUE RECOMMENDATIONS FOR ADDITIONAL MAINTENANCE ,22 | |
327 | + | FREQUENCY OF FILTER REPLACEMENTS , OR UPGRADES TO ALLOW FOR23 | |
328 | + | MORE PROTECTIVE FILTRATION AND RECORD THE RECOMMENDATIONS IN24 | |
329 | + | THE HVAC ASSESSMENT REPORT.25 | |
278 | 330 | (b) Ventilation and exhaust. A | |
279 | - | FTER ASSESSING THE FILTRATION AS | |
280 | - | DESCRIBED IN SUBSECTION | |
281 | - | (3)(a) OF THIS SECTION, QUALIFIED PERSONNEL | |
282 | - | SHALL ASSESS THE VENTILATION RATES IN THE SCHOOL | |
283 | - | 'S OCCUPIED AREAS | |
284 | - | TO DETERMINE WHETHER THEY MEET THE MINIMUM VENTILATION RATE | |
285 | - | REQUIREMENTS SET FORTH IN THE INTERNATIONAL MECHANICAL CODE | |
286 | - | . | |
287 | - | A | |
288 | - | SSESSMENT OF THE VENTILATION AND EXHAUST MUST INCLUDE ALL THE | |
289 | - | FOLLOWING | |
290 | - | : | |
331 | + | FTER ASSESSING THE FILTRATION26 | |
332 | + | AS DESCRIBED IN SUBSECTION (3)(a) OF THIS SECTION, QUALIFIED27 | |
333 | + | 1307 | |
334 | + | -9- PERSONNEL SHALL ASSESS THE VENTILATION RATES IN THE SCHOOL 'S1 | |
335 | + | OCCUPIED AREAS TO DETERMINE WHETHER THEY MEET THE MINIMUM2 | |
336 | + | VENTILATION RATE REQUIREMENTS SET FORTH IN THE INTERNATIONAL3 | |
337 | + | MECHANICAL CODE. ASSESSMENT OF THE VENTILATION AND EXHAUST4 | |
338 | + | MUST INCLUDE ALL THE FOLLOWING :5 | |
291 | 339 | (I) C | |
292 | - | ALCULATION OF THE ESTIMATED MINIMUM OUTSIDE AIR | |
293 | - | VENTILATION RATES FOR EACH OCCUPIED AREA BASED ON THE MAXIMUM | |
294 | - | ANTICIPATED OCCUPANCY AND THE MINIMUM REQUIRED VENTILATION RATE | |
295 | - | PER OCCUPANT | |
296 | - | . CALCULATIONS MUST BE BASED ON MAXIMUM ANTICIPATED | |
297 | - | CLASSROOM OR OTHER OCCUPIED AREA OCCUPANCY RATES AND | |
298 | - | DETERMINED BY THE INTERNATIONAL MECHANICAL CODE | |
299 | - | ; | |
340 | + | ALCULATION OF THE ESTIMATED MINIMUM OUTSIDE AIR6 | |
341 | + | VENTILATION RATES FOR EACH OCCUPIED AREA BASED ON THE MAXIMUM7 | |
342 | + | ANTICIPATED OCCUPANCY AND THE MINIMUM REQUIRED VENTILATION8 | |
343 | + | RATE PER OCCUPANT. CALCULATIONS MUST BE BASED ON MAXIMUM9 | |
344 | + | ANTICIPATED CLASSROOM OR OTHER OCCUPIED AREA OCCUPANCY RATES10 | |
345 | + | AND DETERMINED BY THE INTERNATIONAL MECHANICAL CODE ;11 | |
300 | 346 | (II) M | |
301 | - | EASUREMENT OF OUTSIDE AIR AND VERIFICATION THAT THE | |
302 | - | SYSTEM PROVIDES THE MINIMUM OUTSIDE AIR VENTILATION RATES | |
303 | - | CALCULATED PURSUANT TO SUBSECTION | |
304 | - | (3)(b)(I) OF THIS SECTION; | |
347 | + | EASUREMENT OF OUTSIDE AIR AND VERIFICATION THAT THE12 | |
348 | + | SYSTEM PROVIDES THE MINIMUM OUTSIDE AIR VENTILATION RATES13 | |
349 | + | CALCULATED PURSUANT TO SUBSECTION (3)(b)(I) OF THIS SECTION;14 | |
305 | 350 | (III) V | |
306 | - | ERIFICATION OF COIL VELOCITIES AND UNIT DISCHARGE AIR | |
307 | - | TEMPERATURES REQUIRED TO MAINTAIN DESIRED INDOOR CONDITIONS AND | |
308 | - | TO AVOID MOISTURE CARRYOVER FROM COOLING COILS | |
309 | - | ; | |
351 | + | ERIFICATION OF COIL VELOCITIES AND UNIT DISCHARGE AIR15 | |
352 | + | TEMPERATURES REQUIRED TO MAINTAIN DESIRED INDOOR CONDITIONS16 | |
353 | + | AND TO AVOID MOISTURE CARRYOVER FROM COOLING COILS ;17 | |
310 | 354 | (IV) V | |
311 | - | ERIFICATION THAT SEPARATION BETWEEN OUTDOOR AIR | |
312 | - | INTAKES AND EXHAUST DISCHARGE OUTLETS MEETS THE REQUIREMENTS OF | |
313 | - | THE INTERNATIONAL MECHANICAL CODE | |
314 | - | ; | |
355 | + | ERIFICATION THAT SEPARATION BETWEEN OUTDOOR AIR18 | |
356 | + | INTAKES AND EXHAUST DISC HARGE OUTLETS MEETS THE REQUIREMENTS19 | |
357 | + | OF THE INTERNATIONAL MECHANICAL CODE ;20 | |
315 | 358 | (V) C | |
316 | - | ONFIRMATION THAT THE AIR HANDLING UNIT IS BRINGING IN | |
317 | - | OUTDOOR AIR AND REMOVING EXHAUST AIR AS INTENDED BY THE SYSTEM | |
318 | - | DESIGN | |
319 | - | ; AND | |
320 | - | (VI) MEASUREMENT OF ALL EXHAUST AIR VOLUME FOR EXHAUST | |
321 | - | FANS | |
322 | - | , SUCH AS RESTROOM EXHAUST FANS , INCLUDING DOCUMENTATION OF | |
323 | - | ANY DISCREPANCIES FROM SYSTEM DESIGN | |
324 | - | . | |
359 | + | ONFIRMATION THAT THE AIR HANDLING UNIT IS BRINGING IN21 | |
360 | + | OUTDOOR AIR AND REMOVING EXHAUST AIR AS INTENDED BY THE SYSTEM22 | |
361 | + | DESIGN; AND23 | |
362 | + | (VI) M | |
363 | + | EASUREMENT OF ALL EXHAUST AIR VOLUME FOR EXHAUST24 | |
364 | + | FANS, SUCH AS RESTROOM EXHAUST FANS , INCLUDING DOCUMENTATION25 | |
365 | + | OF ANY DISCREPANCIES FROM SYSTEM DESIGN .26 | |
325 | 366 | (c) Economizers. F | |
326 | - | OR HVAC SYSTEMS WITH ECONOMIZERS , | |
327 | - | QUALIFIED PERSONNEL SHALL TEST SYSTEM ECONOMIZER DAMPERS FOR | |
328 | - | PROPER OPERATION | |
329 | - | . ECONOMIZER DAMPERS AND CONTROLS THAT ARE NOT | |
330 | - | PAGE 8-HOUSE BILL 24-1307 PROPERLY FUNCTIONING SHALL BE REPAIRED BY A CERTIFIED CONTRACTOR | |
331 | - | AND THE CERTIFIED CONTRACTOR | |
332 | - | 'S QUALIFIED PERSONNEL. QUALIFIED | |
333 | - | PERSONNEL SHALL RECORD RECOMMENDATIONS FOR ADDITIONAL | |
334 | - | MAINTENANCE | |
335 | - | , REPLACEMENT, OR UPGRADES IN THE HVAC ASSESSMENT | |
336 | - | REPORT | |
337 | - | . | |
367 | + | OR HVAC SYSTEMS WITH ECONOMIZERS ,27 | |
368 | + | 1307 | |
369 | + | -10- QUALIFIED PERSONNEL SHALL TEST SYSTEM ECONOMIZER DAMPERS FOR1 | |
370 | + | PROPER OPERATION. ECONOMIZER DAMPERS AND CONTROLS THAT ARE2 | |
371 | + | NOT PROPERLY FUNCTIONING SHALL BE REPAIRED BY A CERTIFIED3 | |
372 | + | CONTRACTOR AND THE CERTIFIED CONTRACTOR 'S QUALIFIED PERSONNEL.4 | |
373 | + | Q | |
374 | + | UALIFIED PERSONNEL SHALL RECORD RECOMME NDATIONS FOR5 | |
375 | + | ADDITIONAL MAINTENANCE , REPLACEMENT, OR UPGRADES IN THE HVAC6 | |
376 | + | ASSESSMENT REPORT.7 | |
338 | 377 | (d) Demand control ventilation. (I) I | |
339 | - | F DEMAND CONTROL | |
340 | - | VENTILATION SYSTEMS ARE INSTALLED | |
341 | - | , QUALIFIED PERSONNEL SHALL | |
342 | - | VERIFY THEIR PROPER OPERATION | |
343 | - | . | |
378 | + | F DEMAND CONTROL8 | |
379 | + | VENTILATION SYSTEMS ARE INSTALLED , QUALIFIED PERSONNEL SHALL9 | |
380 | + | VERIFY THEIR PROPER OPERATION.10 | |
344 | 381 | (II) D | |
345 | - | EMAND CONTROL VENTILATION SYSTEMS THAT ARE NOT | |
346 | - | PROPERLY FUNCTIONING SHALL BE REPAIRED BY A CERTIFIED CONTRACTOR | |
347 | - | AND THE CERTIFIED CONTRACTOR | |
348 | - | 'S QUALIFIED PERSONNEL. | |
382 | + | EMAND CONTROL VENTILATION SYSTEMS THAT ARE NOT11 | |
383 | + | PROPERLY FUNCTIONING SHALL BE REPAIRED BY A CERTIFIED CONTRACTOR12 | |
384 | + | AND THE CERTIFIED CONTRACTOR 'S QUALIFIED PERSONNEL.13 | |
349 | 385 | (III) I | |
350 | - | F A DEMAND CONTROL VENTILATION SYSTEM IS RECOMMENDED | |
351 | - | TO BE DISABLED OR IS UNABLE TO PROVIDE RECOMMENDED VENTILATION | |
352 | - | RATES | |
353 | - | , THE HVAC SYSTEM MUST BE CONFIGURED TO MEET THE MINIMUM | |
354 | - | VENTILATION RATE REQUIREMENTS WITHOUT USE OF THE DEMAND CONTROL | |
355 | - | VENTILATION SYSTEM AND TESTED AND ADJUSTED TO ACHIEVE THE | |
356 | - | ESTIMATED MINIMUM OUTSIDE AIR VENTILATION RATE | |
357 | - | , AS DESCRIBED IN | |
358 | - | SUBSECTION | |
359 | - | (3)(b)(I) OF THIS SECTION. | |
386 | + | F A DEMAND CONTROL VENTILATION SYSTEM IS14 | |
387 | + | RECOMMENDED TO BE DISABLED OR IS UNABLE TO PROVIDE15 | |
388 | + | RECOMMENDED VENTILATION RATES , THE HVAC SYSTEM MUST BE16 | |
389 | + | CONFIGURED TO MEET THE MINIMUM VENTILATION RATE REQUIREMENTS17 | |
390 | + | WITHOUT USE OF THE DEMAND CONTROL VENTILATION SYSTEM AND18 | |
391 | + | TESTED AND ADJUSTED TO ACHIEVE THE ESTIMATED MINIMUM OUTSIDE19 | |
392 | + | AIR VENTILATION RATE, AS DESCRIBED IN SUBSECTION (3)(b)(I) OF THIS20 | |
393 | + | SECTION.21 | |
360 | 394 | (IV) Q | |
361 | - | UALIFIED PERSONNEL SHALL RECORD | |
362 | - | ADDITIONAL MAINTENANCE | |
363 | - | ||
364 | - | ASSESSMENT REPORT. | |
395 | + | UALIFIED PERSONNEL SHALL RECORD RECOMMENDATIONS22 | |
396 | + | FOR ADDITIONAL MAINTENANCE , REPLACEMENT, OR UPGRADES IN THE23 | |
397 | + | HVAC | |
398 | + | ASSESSMENT REPORT.24 | |
365 | 399 | (e) Air distribution and building pressurization. (I) Q | |
366 | - | UALIFIED | |
367 | - | PERSONNEL SHALL | |
368 | - | : | |
400 | + | UALIFIED25 | |
401 | + | PERSONNEL SHALL:26 | |
369 | 402 | (A) P | |
370 | - | ERFORM SURVEY READINGS OF INLETS AND OUTLETS | |
371 | - | ||
372 | - | IS | |
373 | - | ; | |
403 | + | ERFORM SURVEY READINGS OF INLETS AND OUTLETS TO27 | |
404 | + | 1307 | |
405 | + | -11- VERIFY THAT ALL VENTILATION IS REACHING THE SERVED ZONES AND1 | |
406 | + | THAT THERE IS ADEQUATE AIR DISTRIBUTION ;2 | |
374 | 407 | (B) V | |
375 | - | ERIFY THAT INLETS AND OUTLETS ARE BALANCED WITHIN | |
376 | - | TOLERANCE OF THE SYSTEM DESIGN | |
377 | - | ; AND | |
378 | - | (C) DOCUMENT READ VALUES AND DEFICIENCIES . IF THE ORIGINAL | |
379 | - | SYSTEM DESIGN VALUES ARE NOT AVAILABLE | |
380 | - | , QUALIFIED PERSONNEL SHALL | |
381 | - | DOCUMENT AVAILABLE INFORMATION AND NOTE THE UNAVAILABILITY OF | |
382 | - | SYSTEM DESIGN VALUES IN THE | |
383 | - | HVAC ASSESSMENT REPORT. | |
384 | - | PAGE 9-HOUSE BILL 24-1307 (II) QUALIFIED PERSONNEL SHALL VERIFY BUILDING AND SPACE | |
385 | - | PRESSURE TO ENSURE THAT | |
386 | - | : | |
408 | + | ERIFY THAT INLETS AND OUTLETS ARE BALANCED WITHIN3 | |
409 | + | TOLERANCE OF THE SYSTEM DESIGN ; AND4 | |
410 | + | (C) D | |
411 | + | OCUMENT READ VALUES AND DEFICIENCIES . IF THE ORIGINAL5 | |
412 | + | SYSTEM DESIGN VALUES ARE NOT AVAILABLE , QUALIFIED PERSONNEL6 | |
413 | + | SHALL DOCUMENT AVAILABLE INFORMATION AND NOTE THE7 | |
414 | + | UNAVAILABILITY OF SYSTEM DESIGN VALUES IN THE HVAC ASSESSMENT8 | |
415 | + | REPORT.9 | |
416 | + | (II) Q | |
417 | + | UALIFIED PERSONNEL SHALL VERIFY BUILDING AND SPACE10 | |
418 | + | PRESSURE TO ENSURE THAT:11 | |
387 | 419 | (A) T | |
388 | - | HE PRESSURE DIFFERENTIAL IS WITHIN TOLERANCE | |
389 | - | IF KNOWN; | |
420 | + | HE PRESSURE DIFFERENTIAL IS WITHIN TOLERANCE OF12 | |
421 | + | DESIGN, IF KNOWN;13 | |
390 | 422 | (B) T | |
391 | - | HE SCHOOL BUILDING IS NOT OVER PRESSURIZED ; | |
392 | - | (C) | |
393 | - | ||
394 | - | ||
395 | - | OR AS OTHERWISE DESIGNED. | |
423 | + | HE SCHOOL BUILDING IS NOT OVER PRESSURIZED ; AND14 | |
424 | + | (C) I | |
425 | + | F APPLICABLE, ROOMS DESIGNATED FOR TEMPORARY15 | |
426 | + | OCCUPATION BY SICK STUDENTS OR STAFF MAINTAIN A NEGATIVE16 | |
427 | + | PRESSURE, OR AS OTHERWISE DESIGNED.17 | |
396 | 428 | (f) General maintenance. Q | |
397 | - | UALIFIED PERSONNEL SHALL VERIFY | |
398 | - | COIL CONDITION | |
399 | - | , CONDENSATE DRAINAGE, COOLING COIL AIR TEMPERATURE | |
400 | - | DIFFERENTIAL | |
401 | - | (ENTERING AND LEAVING DRY BULB ), HEAT EXCHANGER AIR | |
402 | - | TEMPERATURE DIFFERENTIAL | |
403 | - | (ENTERING AND LEAVING DRY BULB ), AND | |
404 | - | DRIVE ASSEMBLY CONDITION | |
405 | - | . QUALIFIED PERSONNEL SHALL RECORD | |
406 | - | RECOMMENDATIONS FOR ADDITIONAL MAINTENANCE | |
407 | - | , REPLACEMENT, OR | |
408 | - | UPGRADES IN THE | |
409 | - | HVAC ASSESSMENT REPORT. | |
429 | + | UALIFIED PERSONNEL SHALL VERIFY18 | |
430 | + | COIL CONDITION, CONDENSATE DRAI NAGE , COOLING COIL AIR19 | |
431 | + | TEMPERATURE DIFFERENTIAL (ENTERING AND LEAVING DRY BULB ), HEAT20 | |
432 | + | EXCHANGER AIR TEMPERATURE DIFFERENTIAL (ENTERING AND LEAVING21 | |
433 | + | DRY BULB), AND DRIVE ASSEMBLY CONDITION . QUALIFIED PERSONNEL22 | |
434 | + | SHALL RECORD RECOMMENDATIONS FOR ADDITIONAL MAINTENANCE ,23 | |
435 | + | REPLACEMENT, OR UPGRADES IN THE HVAC ASSESSMENT REPORT.24 | |
410 | 436 | (g) Operational controls. Q | |
411 | - | UALIFIED PERSONNEL SHALL REVIEW | |
412 | - | CONTROL SEQUENCES TO VERIFY THAT SYSTEMS WILL MAINTAIN INTENDED | |
413 | - | VENTILATION | |
414 | - | , TEMPERATURE, AND HUMIDITY CONDITIONS DURING SCHOOL | |
415 | - | OPERATION | |
416 | - | . | |
437 | + | UALIFIED PERSONNEL SHALL REVIEW25 | |
438 | + | CONTROL SEQUENCES TO VERIFY THAT SYSTEMS WILL MAINTAIN INTENDED26 | |
439 | + | VENTILATION, TEMPERATURE, AND HUMIDITY CONDITIONS DURING SCHOOL27 | |
440 | + | 1307 | |
441 | + | -12- OPERATION.1 | |
417 | 442 | (h) CO2 monitoring. (I) A | |
418 | - | S AN INDICATOR OF | |
419 | - | THROUGHOUT THE | |
420 | - | ||
421 | - | QUALIFIED PERSONNEL | |
422 | - | ||
443 | + | S AN INDICATOR OF PROPER2 | |
444 | + | VENTILATION THROUGHOUT THE SCHOOL YEAR , | |
445 | + | OCCUPIED AREAS, AS3 | |
446 | + | DETERMINED BY QUALIFIED PERSONNEL, MUST BE EQUIPPED WITH A CO24 | |
447 | + | MONITOR THAT:5 | |
423 | 448 | (A) I | |
424 | - | S HARDWIRED, PLUG-IN, OR BATTERY OPERATED AND MOUNTED | |
425 | - | TO THE WALL AT LEAST THREE FEET BUT LESS THAN SIX FEET ABOVE THE | |
426 | - | FLOOR AND AT LEAST FIVE FEET AWAY FROM THE DOOR AND ANY OPERABLE | |
427 | - | WINDOWS | |
428 | - | ; | |
449 | + | S HARDWIRED, PLUG-IN, OR BATTERY OPERATED AND6 | |
450 | + | MOUNTED TO THE WALL AT LEAST THREE FEET BUT LESS THAN SIX FEET7 | |
451 | + | ABOVE THE FLOOR AND AT LEAST FIVE FEET AWAY FROM THE DOOR AND8 | |
452 | + | ANY OPERABLE WINDOWS ;9 | |
429 | 453 | (B) D | |
430 | - | ISPLAYS THE CO2 READINGS TO THE SCHOOL FACILITIES | |
431 | - | MANAGER OR DESIGNATED STAFF MEMBER THROUGH A DISPLAY ON THE | |
432 | - | DEVICE OR OTHER MEANS | |
433 | - | , SUCH AS A WEB-BASED APPLICATION OR CELL | |
434 | - | PHONE APPLICATION | |
435 | - | ; | |
454 | + | ISPLAYS THE CO2 READINGS TO THE SCHOOL FACILITIES10 | |
455 | + | MANAGER OR DESIGNATED STAFF MEMBER THROUGH A DISPLAY ON THE11 | |
456 | + | DEVICE OR OTHER MEANS, SUCH AS A WEB-BASED APPLICATION OR CELL12 | |
457 | + | PHONE APPLICATION;13 | |
436 | 458 | (C) N | |
437 | - | OTIFIES THE SCHOOL FACILITIES MANAGER OR DESIGNATED | |
438 | - | PAGE 10-HOUSE BILL 24-1307 STAFF MEMBER THROUGH A VISUAL INDICATOR OR OTHER ALERT , SUCH AS | |
439 | - | AN E | |
440 | - | -MAIL, A TEXT, OR A CELL PHONE APPLICATION, WHEN CO2 LEVELS IN | |
441 | - | THE OCCUPIED AREAS | |
442 | - | , AS DETERMINED BY QUALIFIED PERSONNEL , HAVE | |
443 | - | EXCEEDED ONE THOUSAND ONE HUNDRED PPM | |
444 | - | ; | |
459 | + | OTIFIES THE SCHOOL FACILITIES MANAGER OR DESIGNATED14 | |
460 | + | STAFF MEMBER THROUGH A VISUAL INDICATOR OR OTHER ALERT , SUCH AS15 | |
461 | + | AN E-MAIL, A TEXT, OR A CELL PHONE APPLICATION, WHEN CO2 LEVELS IN16 | |
462 | + | THE | |
463 | + | OCCUPIED AREAS, AS DETERMINED BY QUALIFIED PERSONNEL, HAVE17 | |
464 | + | EXCEEDED ONE THOUSAND ONE HUNDRED PPM ;18 | |
445 | 465 | (D) M | |
446 | - | AINTAINS A RECORD OF PREVIOUS DATA , WHICH RECORD | |
447 | - | INCLUDES AT LEAST THE MAXIMUM | |
448 | - | CO2 CONCENTRATION MEASURED ; | |
466 | + | AINTAINS A RECORD OF PREVIOUS DATA , WHICH RECORD19 | |
467 | + | INCLUDES AT LEAST THE MAXIMUM CO2 CONCENTRATION MEASURED ;20 | |
449 | 468 | (E) H | |
450 | - | AS A MEASUREMENT RANGE OF AT LEAST FOUR HUNDRED TO | |
451 | - | FIVE THOUSAND PPM | |
452 | - | ; AND | |
453 | - | (F) IS CERTIFIED BY THE MANUFACTURER TO BE ACCURATE WITHIN | |
454 | - | SEVENTY | |
455 | - | -FIVE PPM AT ONE THOUSAND PPM CO2 CONCENTRATION AND TO | |
456 | - | REQUIRE CALIBRATION NO MORE FREQUENTLY THAN ONCE EVERY FIVE | |
457 | - | YEARS | |
458 | - | . | |
469 | + | AS A MEASUREMENT RANGE OF AT LEAST FOUR HUNDRED TO21 | |
470 | + | FIVE THOUSAND PPM; AND22 | |
471 | + | (F) I | |
472 | + | S CERTIFIED BY THE MANUFACTURER TO BE ACCURATE WITHIN23 | |
473 | + | SEVENTY-FIVE PPM AT ONE THOUSAND PPM CO2 CONCENTRATION AND TO24 | |
474 | + | REQUIRE CALIBRATION NO MORE FREQUENTLY THAN ONCE EVERY FIVE25 | |
475 | + | YEARS.26 | |
459 | 476 | (II) Q | |
460 | - | UALIFIED PERSONNEL SHALL VERIFY THAT THE CO2 MONITORS | |
461 | - | ARE ACCURATE WITHIN SEVENTY | |
462 | - | -FIVE PPM AT ONE THOUSAND PPM CO2. | |
477 | + | UALIFIED PERSONNEL SHALL VERIFY THAT THE CO227 | |
478 | + | 1307 | |
479 | + | -13- MONITORS ARE ACCURATE WITHIN SEVENTY -FIVE PPM AT ONE THOUSAND1 | |
480 | + | PPM CO2.2 | |
463 | 481 | (III) I | |
464 | - | N SCHOOLS WHERE THERE IS LIMITED OR NO EXISTING | |
465 | - | MECHANICAL VENTILATION | |
466 | - | , THE ASSESSMENT OF CO2 MONITORING MUST | |
467 | - | FOCUS ON DOCUMENTING EXISTING CONDITIONS AND PROVIDING THE | |
468 | - | MECHANICAL ENGINEER WITH THE INFORMATION NEEDED TO PROVIDE | |
469 | - | MECHANICAL VENTILATION UPGRADE RECOMMENDATIONS | |
470 | - | , IF NEEDED, TO | |
471 | - | ENSURE PROPER VENTILATION AND INDOOR AIR QUALITY | |
472 | - | . OCCUPIED AREAS | |
473 | - | WITH LIMITED OR NO EXISTING MECHANICAL VENTILATION MUST HAVE | |
474 | - | CO2 | |
475 | - | MONITORS INSTALLED. | |
482 | + | N SCHOOLS WHERE THERE IS LIMITED OR NO EXISTING3 | |
483 | + | MECHANICAL VENTILATION, THE ASSESSMENT OF CO2 MONITORING MUST4 | |
484 | + | FOCUS ON DOCUMENTING EXISTING CONDITIONS AND PROVIDING THE5 | |
485 | + | MECHANICAL ENGINEER WITH THE INFORMATION NEEDED TO PROVIDE6 | |
486 | + | MECHANICAL VENTILATION UPGRADE RECOMMENDATIONS , IF NEEDED, TO7 | |
487 | + | ENSURE PROPER VENTILATION AND INDOOR AIR QUALITY . | |
488 | + | OCCUPIED8 | |
489 | + | AREAS WITH LIMITED OR NO EXISTING MECHANICAL VENTILATION MUST9 | |
490 | + | HAVE CO2 MONITORS INSTALLED.10 | |
476 | 491 | (IV) I | |
477 | - | N THE HVAC ASSESSMENT REPORT, QUALIFIED PERSONNEL | |
478 | - | SHALL INCLUDE VERIFICATION OF THE INSTALLATION OF | |
479 | - | CO2 MONITORS IN | |
480 | - | OCCUPIED AREAS | |
481 | - | , AS APPLICABLE. | |
492 | + | N THE HVAC ASSESSMENT REPORT, QUALIFIED PERSONNEL11 | |
493 | + | SHALL INCLUDE VERIFICATION OF THE INSTALLATION OF CO2 MONITORS12 | |
494 | + | IN | |
495 | + | OCCUPIED AREAS, AS APPLICABLE.13 | |
482 | 496 | (4) HVAC assessment report. Q | |
483 | - | UALIFIED PERSONNEL SHALL | |
484 | - | PREPARE AN | |
485 | - | HVAC ASSESSMENT REPORT FOR REVIEW BY A MECHANICAL | |
486 | - | ENGINEER | |
487 | - | . THE HVAC ASSESSMENT REPORT MUST INCLUDE ALL OF THE | |
488 | - | FOLLOWING INFORMATION | |
489 | - | : | |
497 | + | UALIFIED PERSONNEL SHALL14 | |
498 | + | PREPARE AN HVAC ASSESSMENT REPORT FOR REVIEW BY A MECHANICAL15 | |
499 | + | ENGINEER. THE HVAC ASSESSMENT REPORT MUST INCLUDE ALL OF THE16 | |
500 | + | FOLLOWING INFORMATION :17 | |
490 | 501 | (a) T | |
491 | - | HE NAME AND ADDRESS OF THE | |
492 | - | CONTRACTOR COMPLETING THE WORK | |
493 | - | ||
494 | - | ||
495 | - | ||
502 | + | HE NAME AND ADDRESS OF THE SCHOOL AND THE CERTIFIED18 | |
503 | + | CONTRACTOR COMPLETING THE WORK , INCLUDING THE NAME OF THE19 | |
504 | + | QUALIFIED PERSONNEL PREPARING THE ASSESSMENT REPORT AND THE20 | |
505 | + | NAME OF THE MECHANICAL ENGINEER CERTIFYING THE ASSESSMENT21 | |
506 | + | REPORT;22 | |
496 | 507 | (b) A | |
497 | - | DESCRIPTION OF ASSESSMENT, MAINTENANCE, ADJUSTMENT, | |
498 | - | AND REPAIR ACTIVITIES AND OUTCOMES ; | |
508 | + | DESCRIPTION OF ASSESSMENT, MAINTENANCE, ADJUSTMENT,23 | |
509 | + | AND REPAIR ACTIVITIES AND OUTCOMES ;24 | |
499 | 510 | (c) D | |
500 | - | OCUMENTATION OF HVAC EQUIPMENT MODEL NUMBERS , | |
501 | - | SERIAL NUMBERS, GENERAL CONDITION OF UNITS, AND ANY | |
502 | - | INFORMATION THAT COULD BE USED TO ASSESS REPLACEMENT AND | |
503 | - | ||
504 | - | ||
505 | - | ; | |
511 | + | OCUMENTATION OF HVAC EQUIPMENT MODEL NUMBERS ,25 | |
512 | + | SERIAL NUMBERS, GENERAL CONDITION OF UNITS, AND ANY ADDITIONAL26 | |
513 | + | INFORMATION THAT COULD BE USED TO ASSESS REPLACEMENT AND REPAIR27 | |
514 | + | 1307 | |
515 | + | -14- OPTIONS GIVEN THE POTENTIAL FOR INCREASED ENERGY EFFICIENCY1 | |
516 | + | BENEFITS;2 | |
506 | 517 | (d) V | |
507 | - | ERIFICATION THAT EITHER: | |
518 | + | ERIFICATION THAT EITHER:3 | |
508 | 519 | (I) MERV | |
509 | - | 13 FILTERS HAVE BEEN INSTALLED; OR | |
510 | - | (II) THE MAXIMUM MERV-RATED FILTER THAT THE SYSTEM IS ABLE | |
511 | - | TO EFFECTIVELY HANDLE HAS BEEN INSTALLED | |
512 | - | , INCLUDING AN INDICATION | |
513 | - | OF THE | |
514 | - | MERV RATING OF THAT FILTER; | |
520 | + | 13 FILTERS HAVE BEEN INSTALLED; OR4 | |
521 | + | (II) T | |
522 | + | HE MAXIMUM MERV-RATED FILTER THAT THE SYSTEM IS5 | |
523 | + | ABLE TO EFFECTIVELY HANDLE HAS BEEN INSTALLED , INCLUDING AN6 | |
524 | + | INDICATION OF THE MERV RATING OF THAT FILTER;7 | |
515 | 525 | (e) V | |
516 | - | ERIFICATION THAT ALL REQUIREMENTS DESCRIBED IN | |
517 | - | SUBSECTION | |
518 | - | ||
519 | - | ||
526 | + | ERIFICATION THAT ALL REQUIREMENTS DESCRIBED IN THIS8 | |
527 | + | SUBSECTION (4) HAVE BEEN SATISFIED, INCLUDING INSTALLATION OF CO29 | |
528 | + | MONITORS IN | |
529 | + | OCCUPIED AREAS;10 | |
520 | 530 | (f) T | |
521 | - | HE VERIFIED VENTILATION RATES FOR OCCUPIED AREAS AND | |
522 | - | WHETHER THOSE RATES MEET THE ESTIMATED REQUIREMENTS SET FORTH IN | |
523 | - | THE INTERNATIONAL MECHANICAL CODE | |
524 | - | ; | |
531 | + | HE VERIFIED VENTILATION RATES FOR OCCUPIED AREAS AND11 | |
532 | + | WHETHER THOSE RATES MEET THE ESTIMATED REQUIREMENTS SET FORTH12 | |
533 | + | IN THE INTERNATIONAL MECHANICAL CODE ;13 | |
525 | 534 | (g) T | |
526 | - | HE VERIFIED EXHAUST FOR OCCUPIED AREAS AND WHETHER | |
527 | - | THOSE RATES MEET THE REQUIREMENTS OF THE SYSTEM | |
528 | - | 'S DESIGN; AND | |
529 | - | (h) DOCUMENTATION OF SYSTEM DEFICIENCIES AND | |
530 | - | RECOMMENDATIONS FOR ADDITIONAL MAINTENANCE | |
531 | - | , REPLACEMENT, OR | |
532 | - | UPGRADES TO IMPROVE ENERGY EFFICIENCY | |
533 | - | , NOX EMISSIONS, GREENHOUSE | |
534 | - | GAS EMISSIONS | |
535 | - | , SAFETY, OR PERFORMANCE, IF ANY. | |
535 | + | HE VERIFIED EXHAUST FOR OCCUPIED AREAS AND WHETHER14 | |
536 | + | THOSE RATES MEET THE REQUIREMENTS OF THE SYSTEM 'S DESIGN; AND15 | |
537 | + | (h) D | |
538 | + | OCUMENTATION OF SYSTEM DEFICIENCIES AND16 | |
539 | + | RECOMMENDATIONS FOR ADDITIONAL MAINTENANCE , REPLACEMENT, OR17 | |
540 | + | UPGRADES TO IMPROVE ENERGY EFFICIENCY , | |
541 | + | NOX EMISSIONS,18 | |
542 | + | GREENHOUSE GAS EMISSIONS, SAFETY, OR PERFORMANCE, IF ANY.19 | |
536 | 543 | (5) Mechanical engineer review. A | |
537 | - | MECHANICAL ENGINEER SHALL: | |
544 | + | MECHANICAL ENGINEER20 | |
545 | + | SHALL:21 | |
538 | 546 | (a) R | |
539 | - | EVIEW THE HVAC ASSESSMENT REPORT; | |
547 | + | EVIEW THE HVAC ASSESSMENT REPORT;22 | |
540 | 548 | (b) V | |
541 | - | ERIFY OR ADJUST THE ESTIMATED MINIMUM OUTSIDE | |
542 | - | ||
549 | + | ERIFY OR ADJUST THE ESTIMATED MINIMUM OUTSIDE AIR23 | |
550 | + | VENTILATION RATES;24 | |
543 | 551 | (c) D | |
544 | - | ETERMINE WHAT, IF ANY, ADDITIONAL ADJUSTMENTS, REPAIRS, | |
545 | - | UPGRADES, OR REPLACEMENTS ARE NECESSARY TO MEET THE MINIMUM | |
546 | - | VENTILATION AND FILTRATION REQUIREMENTS OF THE INTERNATIONAL | |
547 | - | MECHANICAL CODE | |
548 | - | ; | |
549 | - | (d) R | |
550 | - | ECOMMEND A PATHWAY FOR REDUCING NOX EMISSIONS AND | |
551 | - | GREENHOUSE GAS EMISSIONS | |
552 | - | ; AND | |
553 | - | (e) PROVIDE A COST ESTIMATE FOR ALL RECOMMENDED WORK . | |
552 | + | ETERMINE WHAT, IF ANY, ADDITIONAL ADJUSTMENTS ,25 | |
553 | + | REPAIRS, UPGRADES, OR REPLACEMENTS ARE NECESSARY TO MEET THE26 | |
554 | + | MINIMUM VENTILATION AND FILTRATION REQUIREMENTS OF THE27 | |
555 | + | 1307 | |
556 | + | -15- INTERNATIONAL MECHANICAL CODE ; 1 | |
557 | + | (d) RECOMMEND A PATHWAY FOR REDUCING NOX EMISSIONS AND2 | |
558 | + | GREENHOUSE GAS EMISSIONS; AND3 | |
559 | + | (e) PROVIDE A COST ESTIMATE FOR ALL RECOMMENDED WORK .4 | |
554 | 560 | (6) Adjustments, repairs, upgrades, and replacements. A | |
555 | - | LL | |
556 | - | HVAC REPAIRS, UPGRADES, AND REPLACEMENTS SHALL BE PERFORMED BY | |
557 | - | A CERTIFIED CONTRACTOR AND THE CERTIFIED CONTRACTOR | |
558 | - | 'S QUALIFIED | |
559 | - | PERSONNEL | |
560 | - | . ALL HVAC ADJUSTMENTS SHALL BE PERFORMED BY QUALIFIED | |
561 | - | ADJUSTING PERSONNEL | |
562 | - | . | |
561 | + | LL5 | |
562 | + | HVAC | |
563 | + | REPAIRS, UPGRADES, AND REPLACEMENTS SHALL BE PERFORMED6 | |
564 | + | BY A CERTIFIED CONTRACTOR AND THE CERTIFIED CONTRACTOR 'S7 | |
565 | + | QUALIFIED PERSONNEL. ALL HVAC ADJUSTMENTS SHALL BE PERFORMED8 | |
566 | + | BY QUALIFIED ADJUSTING PERSONNEL .9 | |
563 | 567 | (7) HVAC verification report. (a) T | |
564 | - | HE CERTIFIED CONTRACTOR OR | |
565 | - | A MEMBER OF THE CERTIFIED CONTRACTOR | |
566 | - | 'S QUALIFIED PERSONNEL SHALL | |
567 | - | PREPARE AN | |
568 | - | HVAC VERIFICATION REPORT, AND THE LOCAL EDUCATION | |
569 | - | PROVIDER SHALL SUBMIT THE | |
570 | - | HVAC VERIFICATION REPORT TO THE | |
571 | - | DEPARTMENT WITHIN THIRTY DAYS AFTER COMPLETION OF ALL WORK | |
572 | - | DESCRIBED IN SUBSECTIONS | |
573 | - | (3) TO (6) OF THIS SECTION. | |
568 | + | HE CERTIFIED CONTRACTOR10 | |
569 | + | OR A MEMBER OF THE CERTIFIED CONTRACTOR 'S QUALIFIED PERSONNEL11 | |
570 | + | SHALL PREPARE AN HVAC VERIFICATION REPORT, AND THE LOCAL | |
571 | + | 12 | |
572 | + | EDUCATION PROVIDER SHALL SUBMIT THE HVAC VERIFICATION REPORT13 | |
573 | + | TO THE DEPARTMENT WITHIN THIRTY DAYS AFTER COMPLETION OF ALL14 | |
574 | + | WORK DESCRIBED IN SUBSECTIONS (3) TO (6) OF THIS SECTION.15 | |
574 | 575 | (b) T | |
575 | - | HE HVAC VERIFICATION REPORT MUST INCLUDE ALL OF THE | |
576 | - | FOLLOWING INFORMATION | |
577 | - | : | |
576 | + | HE HVAC VERIFICATION REPORT MUST INCLUDE ALL OF THE16 | |
577 | + | FOLLOWING INFORMATION :17 | |
578 | 578 | (I) T | |
579 | - | HE NAME AND ADDRESS OF THE SC HOOL AND THE PERSON | |
580 | - | PREPARING AND CERTIFYING THE REPORT | |
581 | - | ; | |
579 | + | HE NAME AND ADDRESS OF THE SCHOOL AND THE PERSON18 | |
580 | + | PREPARING AND CERTIFYING THE REPORT ;19 | |
582 | 581 | (II) A | |
583 | - | DESCRIPTION OF ASSESSMENT, MAINTENANCE, ADJUSTMENT, | |
584 | - | REPAIR, UPGRADE, AND REPLACEMENT ACTIVITIES AND OUTCOMES ; | |
582 | + | DESCRIPTION OF ASSESSMENT, MAINTENANCE, ADJUSTMENT,20 | |
583 | + | REPAIR, UPGRADE, AND REPLACEMENT ACTIVITIES AND OUTCOMES ;21 | |
585 | 584 | (III) V | |
586 | - | ERIFICATION THAT THE CERTIFIED CONTRACTOR OR THE | |
587 | - | CERTIFIED CONTRACTOR | |
588 | - | 'S QUALIFIED PERSONNEL HAS COMPLIED WITH ALL | |
589 | - | REQUIREMENTS OF THIS SECTION | |
590 | - | ; | |
585 | + | ERIFICATION THAT THE CERTIFIED CONTRACTOR OR THE22 | |
586 | + | CERTIFIED CONTRACTOR'S QUALIFIED PERSONNEL HAS COMPLIED WITH ALL23 | |
587 | + | REQUIREMENTS OF THIS SECTION;24 | |
591 | 588 | (IV) V | |
592 | - | ERIFICATION THAT EITHER: | |
593 | - | PAGE 13-HOUSE BILL 24-1307 (A) MERV 13 FILTERS HAVE BEEN INSTALLED; OR | |
594 | - | (B) THE MAXIMUM MERV-RATED FILTER THAT THE SYSTEM IS ABLE | |
595 | - | TO EFFECTIVELY HANDLE HAS BEEN INSTALLED | |
596 | - | , INCLUDING AN INDICATION | |
597 | - | OF THE | |
598 | - | MERV RATING OF THAT FILTER; | |
589 | + | ERIFICATION THAT EITHER:25 | |
590 | + | (A) MERV | |
591 | + | 13 FILTERS HAVE BEEN INSTALLED; OR26 | |
592 | + | (B) T | |
593 | + | HE MAXIMUM MERV-RATED FILTER THAT THE SYSTEM IS27 | |
594 | + | 1307 | |
595 | + | -16- ABLE TO EFFECTIVELY HANDLE HAS BEEN INSTALLED , INCLUDING AN1 | |
596 | + | INDICATION OF THE MERV RATING OF THAT FILTER;2 | |
599 | 597 | (V) T | |
600 | - | HE VERIFIED VENTILATION RATES FOR OCCUPIED AREAS AND | |
601 | - | WHETHER THOSE RATES MEET THE REQUIREMENTS SET FORTH IN THE | |
602 | - | INTERNATIONAL MECHANICAL CODE | |
603 | - | . IF VENTILATION RATES DO NOT MEET | |
604 | - | APPLICABLE GUIDANCE | |
605 | - | , THEN THE HVAC VERIFICATION REPORT MUST | |
606 | - | INCLUDE AN EXPLANATION OF WHY THE CURRENT SYSTEM IS UNABLE TO | |
607 | - | MEET THOSE RATES | |
608 | - | . | |
598 | + | HE VERIFIED VENTILATION RATES FOR OCCUPIED AREAS AND3 | |
599 | + | WHETHER THOSE RATES MEET THE REQUIREMENTS SET FORTH IN THE4 | |
600 | + | INTERNATIONAL MECHANICAL CODE . IF VENTILATION RATES DO NOT MEET5 | |
601 | + | APPLICABLE GUIDANCE, THEN THE HVAC VERIFICATION REPORT MUST6 | |
602 | + | INCLUDE AN EXPLANATION OF WHY THE CURRENT SYSTEM IS UNABLE TO7 | |
603 | + | MEET THOSE RATES.8 | |
609 | 604 | (VI) T | |
610 | - | HE VERIFIED EXHAUST RATES FOR OCCUPIED AREAS AND | |
611 | - | WHETHER THOSE RATES MEET THE REQUIREMENTS SET FORTH IN THE | |
612 | - | SYSTEM | |
613 | - | 'S DESIGN; | |
605 | + | HE VERIFIED EXHAUST RATES FOR OCCUPIED AREAS AND9 | |
606 | + | WHETHER THOSE RATES MEET THE REQUIREMENTS SET FORTH IN THE10 | |
607 | + | SYSTEM'S DESIGN;11 | |
614 | 608 | (VII) D | |
615 | - | OCUMENTATION OF REPAIRS, UPGRADES, OR REPLACEMENTS | |
616 | - | PERFORMED IN RESPONSE TO | |
617 | - | : | |
609 | + | OCUMENTATION OF REPAIRS , UPGRADES, OR12 | |
610 | + | REPLACEMENTS PERFORMED IN RESPONSE TO :13 | |
618 | 611 | (A) T | |
619 | - | HE HVAC ASSESSMENT REPORT; | |
620 | - | (B) | |
621 | - | ||
622 | - | (5) OF THIS SECTION; | |
612 | + | HE HVAC ASSESSMENT REPORT; AND14 | |
613 | + | (B) T | |
614 | + | HE MECHANICAL ENGINEER 'S RECOMMENDATIONS MADE15 | |
615 | + | PURSUANT TO SUBSECTION (5) OF THIS SECTION;16 | |
623 | 616 | (VIII) D | |
624 | - | OCUMENTATION OF RECOMMENDATIONS FOR ADDITIONAL | |
625 | - | MAINTENANCE | |
626 | - | , REPAIRS, REPLACEMENTS, OR UPGRADES TO IMPROVE | |
627 | - | ENERGY EFFICIENCY | |
628 | - | , NOX EMISSIONS, GREENHOUSE GAS EMISSIONS, SAFETY, | |
629 | - | OR PERFORMANCE; | |
630 | - | (IX) D | |
631 | - | OCUMENTATION OF THE MECHANICAL ENGINEER 'S | |
632 | - | RECOMMENDED PATHWAY FOR REDUCING | |
633 | - | NOX EMISSIONS AND GREENHOUSE | |
634 | - | GAS EMISSIONS | |
635 | - | ; | |
636 | - | (X) D | |
637 | - | OCUMENTATION OF INITIAL OPERATING VERIFICATIONS , | |
638 | - | ADJUSTMENTS, AND FINAL OPERATING VERIFICATIONS AND DOCUMENTATION | |
639 | - | OF ANY ADJUSTMENTS OR REPAIRS PERFORMED | |
640 | - | ; | |
641 | - | (XI) V | |
642 | - | ERIFICATION OF INSTALLATION OF CO2 MONITORS, INCLUDING | |
643 | - | THE NUMBER OF MONITORS INSTALLED AND VERIFIED AND THE MAKE AND | |
644 | - | PAGE 14-HOUSE BILL 24-1307 MODEL OF EACH MONITOR; AND | |
645 | - | (XII) VERIFICATION THAT ALL WORK HAS BEEN PERFORMED BY A | |
646 | - | CERTIFIED CONTRACTOR OR THE CERTIFIED CONTRACTOR | |
647 | - | 'S QUALIFIED | |
648 | - | PERSONNEL | |
649 | - | , INCLUDING THE CONTRACTOR'S NAME, THE NAMES OF QUALIFIED | |
650 | - | PERSONNEL | |
651 | - | , CERTIFICATION NUMBERS OF ANY QUALIFIED PERSONNEL , AND | |
652 | - | VERIFICATION THAT ALL CONSTRUCTION WORK HAS BEEN PERFORMED BY A | |
653 | - | CERTIFIED CONTRACTOR AND THE CERTIFIED CONTRACTOR | |
654 | - | 'S QUALIFIED | |
655 | - | PERSONNEL | |
656 | - | . | |
617 | + | OCUMENTATION OF RECOMMENDATIONS FOR ADDITIONAL17 | |
618 | + | MAINTENANCE, REPAIRS, REPLACEMENTS, OR UPGRADES TO IMPROVE18 | |
619 | + | ENERGY EFFICIENCY, | |
620 | + | NOX EMISSIONS, GREENHOUSE GAS EMISSIONS,19 | |
621 | + | SAFETY, OR PERFORMANCE;20 | |
622 | + | (IX) DOCUMENTATION OF THE MECHANICAL ENGINEER'S21 | |
623 | + | RECOMMENDED PATHWAY FOR REDUCING NOX EMISSIONS AND22 | |
624 | + | GREENHOUSE GAS EMISSIONS;23 | |
625 | + | (X) DOCUMENTATION OF INITIAL OPERATING VERIFICATIONS ,24 | |
626 | + | ADJUSTMENTS, AND FINAL OPERATING VERIFICATIONS AND25 | |
627 | + | DOCUMENTATION OF ANY ADJUSTMENTS OR REPAIRS PERFORMED ;26 | |
628 | + | (XI) VERIFICATION OF INSTALLATION OF CO2 MONITORS,27 | |
629 | + | 1307 | |
630 | + | -17- INCLUDING THE NUMBER OF MONITORS INSTALLED AND VERIFIED AND THE1 | |
631 | + | MAKE AND MODEL OF EACH MONITOR ; AND2 | |
632 | + | (XII) VERIFICATION THAT ALL WORK HAS BEEN PERFORMED BY A3 | |
633 | + | CERTIFIED CONTRACTOR OR THE CERTIFIED CONTRACTOR 'S QUALIFIED4 | |
634 | + | PERSONNEL, INCLUDING THE CONTRACTOR 'S NAME, THE NAMES OF5 | |
635 | + | QUALIFIED PERSONNEL, CERTIFICATION NUMBERS OF ANY QUALIFIED6 | |
636 | + | PERSONNEL, AND VERIFICATION THAT ALL CONSTRUCTION WORK HAS BEEN7 | |
637 | + | PERFORMED BY A CERTIFIED CONTRACTOR AND THE CERTIFIED8 | |
638 | + | CONTRACTOR'S QUALIFIED PERSONNEL.9 | |
657 | 639 | (c) T | |
658 | - | HE LOCAL EDUCATION PROVIDER SHALL MAINTAIN A COPY OF | |
659 | - | THE | |
660 | - | HVAC VERIFICATION REPORT FOR AT LEAST FIVE YEARS AND MAKE IT | |
661 | - | AVAILABLE TO THE PUBLIC UPON REQUEST | |
662 | - | . | |
640 | + | HE LOCAL EDUCATION PROVIDER | |
641 | + | SHALL MAINTAIN A COPY OF10 | |
642 | + | THE HVAC VERIFICATION REPORT FOR AT LEAST FIVE YEARS AND MAKE11 | |
643 | + | IT AVAILABLE TO THE PUBLIC UPON REQUEST .12 | |
663 | 644 | (8) Periodic inspections and ongoing maintenance. (a) A | |
664 | - | T LEAST | |
665 | - | ONCE EVERY FIVE YEARS | |
666 | - | , QUALIFIED PERSONNEL SHALL PERFORM THE | |
667 | - | DUTIES CONCERNING ASSESSMENT | |
668 | - | , MAINTENANCE , ADJUSTMENT, | |
669 | - | OPERATIONAL CONTROLS, AND CO2 MONITORS DESCRIBED IN SUBSECTIONS | |
670 | - | (3) TO (6) OF THIS SECTION. | |
671 | - | (b) F | |
672 | - | OR CO2 MONITORS INSTALLED IN OCCUPIED AREAS , AS | |
673 | - | DETERMINED BY QUALIFIED PERSONNEL | |
674 | - | , IF THE CO2 CONCENTRATION | |
675 | - | ALARM SET POINT IS EXCEEDED FOR MORE THAN FIFTEEN MINUTES MORE | |
676 | - | THAN FOUR TIMES IN A MONTH | |
677 | - | , QUALIFIED ADJUSTING PERSONNEL SHALL | |
678 | - | EITHER ADJUST THE OCCUPIED AREA | |
679 | - | 'S VENTILATION RATES OR INSTALL A | |
680 | - | DIRECT OUTSIDE AIRFLOW MEASUREMENT DEVICE AND VERIFY ITS | |
681 | - | ACCURACY TO ENSURE PEAK | |
682 | - | CO2 CONCENTRATIONS IN THE OCCUPIED AREA | |
683 | - | REMAIN BELOW THE SET POINT | |
684 | - | . | |
645 | + | T13 | |
646 | + | LEAST ONCE EVERY FIVE YEARS, QUALIFIED PERSONNEL SHALL PERFORM14 | |
647 | + | THE DUTIES CONCERNING ASSESSMENT , MAINTENANCE, ADJUSTMENT,15 | |
648 | + | OPERATIONAL CONTROLS , AND CO2 MONITORS DESCRIBED IN16 | |
649 | + | SUBSECTIONS (3) TO (6) OF THIS SECTION.17 | |
650 | + | (b) | |
651 | + | FOR CO2 MONITORS INSTALLED IN OCCUPIED AREAS, AS18 | |
652 | + | DETERMINED BY QUALIFIED PERSONNEL, IF THE CO2 CONCENTRATION19 | |
653 | + | ALARM SET POINT IS EXCEEDED FO R MORE THAN FIFTEEN MINUTES MORE20 | |
654 | + | THAN FOUR TIMES IN A MONTH, QUALIFIED ADJUSTING PERSONNEL SHALL21 | |
655 | + | EITHER ADJUST THE OCCUPIED AREA'S VENTILATION RATES OR INSTALL A22 | |
656 | + | DIRECT OUTSIDE AIRFLOW MEASUREMENT DEVICE AND VERIFY ITS23 | |
657 | + | ACCURACY TO ENSURE PEAK CO2 CONCENTRATIONS IN THE OCCUPIED24 | |
658 | + | AREA REMAIN BELOW THE SET POINT .25 | |
685 | 659 | (c) E | |
686 | - | ACH LOCAL EDUCATION PROVIDER SHALL : | |
660 | + | ACH LOCAL EDUCATION PROVIDER | |
661 | + | SHALL:26 | |
687 | 662 | (I) R | |
688 | - | ECORD EACH INCIDENT IN WHICH A CO2 CONCENTRATION | |
689 | - | ALARM SET POINT WAS BREACHED | |
690 | - | ; | |
663 | + | ECORD EACH INCIDENT IN WHICH A | |
664 | + | CO2 CONCENTRATION27 | |
665 | + | 1307 | |
666 | + | -18- ALARM SET POINT WAS BREACHED ;1 | |
691 | 667 | (II) R | |
692 | - | ETAIN EACH RECORD FOR AT LEAST FIVE YEARS ; AND | |
693 | - | (III) MAKE THE RECORDS AVAILABLE TO THE PUBLIC UPON REQUEST . | |
668 | + | ETAIN EACH RECORD FOR AT LEAST FIVE YEARS ; AND2 | |
669 | + | (III) M | |
670 | + | AKE THE RECORDS AVAILABLE TO THE PUBLIC UPON3 | |
671 | + | REQUEST.4 | |
694 | 672 | (9) Certified contractors. (a) I | |
695 | 673 | F A LOCAL EDUCATION PROVIDER | |
696 | - | UNDERTAKES | |
697 | - | HVAC INFRASTRUCTURE IMPROVEMENTS AS DESCRIBED IN | |
698 | - | PAGE 15-HOUSE BILL 24-1307 THIS SECTION USING MONEY MADE AVAILABLE BY FEDERAL GOVERNMENT | |
699 | - | SOURCES OR FEDERAL GOVERNMENT SOURCES IN COMBINATION WITH STATE | |
700 | - | GOVERNMENT SOURCES SPECIFICALLY FOR SUCH PURPOSE | |
701 | - | , THE LOCAL | |
702 | - | EDUCATION PROVIDER SHALL | |
703 | - | : | |
674 | + | 5 | |
675 | + | UNDERTAKES HVAC INFRASTRUCTURE IMPROVEMENTS AS DESCRIBED IN6 | |
676 | + | THIS SECTION USING MONEY MADE AVAILABLE BY FEDERAL GOVERNMENT7 | |
677 | + | SOURCES OR FEDERAL GOVERNMENT SOURCES IN COMBINATION WITH8 | |
678 | + | STATE GOVERNMENT SOURCES SPECIFICALLY FOR SUCH PURPOSE , THE9 | |
679 | + | LOCAL EDUCATION PROVIDER SHALL:10 | |
704 | 680 | (I) O | |
705 | 681 | BTAIN AND MAKE USE OF THE CERTIFIED CONTRACTOR LIST TO | |
706 | - | ASSIST IN CONTRACTOR SELECTION AND ENSURE COMPLIANCE WITH FEDERAL | |
707 | - | FUNDING REQUIREMENTS | |
708 | - | ; AND | |
709 | - | (II) EMPLOY ONLY CERTIFIED CONTRACTORS OR CONTRACTORS THAT | |
710 | - | USE PREVAILING WAGES AND APPRENTICES REGISTERED WITH THE FEDERAL | |
711 | - | DEPARTMENT OF LABOR OR THE STATE APPRENTICESHIP AGENCY CREATED | |
712 | - | IN SECTION | |
713 | - | 8-15.7-102 FOR THE PERFORMANCE OF THE HVAC | |
714 | - | INFRASTRUCTURE IMPROVEMENTS . | |
682 | + | 11 | |
683 | + | ASSIST IN CONTRACTOR SELECTION AND ENSURE COMPLIANCE WITH12 | |
684 | + | FEDERAL FUNDING REQUIREMENTS ; AND13 | |
685 | + | (II) E | |
686 | + | MPLOY ONLY CERTIFIED CONTRACTORS OR CONTRACTORS | |
687 | + | 14 | |
688 | + | THAT USE PREVAILING WAGES AND APPRENTICES REGISTERED WITH THE15 | |
689 | + | FEDERAL DEPARTMENT OF LABOR OR THE STATE APPRENTICESHIP AGENCY16 | |
690 | + | CREATED IN SECTION 8-15.7-102 FOR THE PERFORMANCE OF THE HVAC17 | |
691 | + | INFRASTRUCTURE IMPROVEMENTS .18 | |
715 | 692 | (b) T | |
716 | - | HE DEPARTMENT SHALL PUBLISH THE CERTIFIED | |
717 | - | LIST ON ITS WEBSITE AND INCLUDE OR REFERENCE THE LIST IN ALL OF | |
718 | - | RELEVANT MARKETING MATERIAL FOR SCHOOL | |
693 | + | HE DEPARTMENT SHALL PUBLISH THE CERTIFIED CONTRACTOR19 | |
694 | + | LIST ON ITS WEBSITE AND INCLUDE OR REFERENCE THE LIST IN ALL OF THE20 | |
695 | + | RELEVANT MARKETING MATERIAL FOR SCHOOL INFRASTRUCTURE21 | |
719 | 696 | IMPROVEMENT PROGRAMS TO ASSIST IN CONTRACTOR SELECTION AND | |
720 | - | ||
721 | - | . | |
697 | + | 22 | |
698 | + | ENSURE COMPLIANCE WITH FEDERAL FUNDING REQUIREMENTS .23 | |
722 | 699 | (c) T | |
723 | - | HE REQUIREMENT DESCRIBED IN SUBSECTION (9)(a) OF THIS | |
724 | - | SECTION DOES NOT APPLY TO MECHANICAL | |
725 | - | , PLUMBING, AND ELECTRICAL | |
726 | - | WORK THAT IS PERFORMED PURSUANT TO A PROJECT LABOR AGREEMENT | |
727 | - | , | |
728 | - | WHICH ALLOWS A CONTRACTOR AND ALL SUBCONTRACTORS TO COMPETE | |
729 | - | FOR CONTRACTS AND SUBCONTRACTS WITHOUT REGARD TO WHETHER THEY | |
730 | - | ARE PARTIES TO A COLLECTIVE BARGAINING AGREEMENT | |
731 | - | . | |
700 | + | HE REQUIREMENT DESCRIBED IN SUBSECTION (9)(a) OF THIS24 | |
701 | + | SECTION DOES NOT APPLY TO MECHANICAL , PLUMBING, AND ELECTRICAL25 | |
702 | + | WORK THAT IS PERFORMED PURSUANT TO A PROJECT LABOR AGREEMENT , | |
703 | + | 26 | |
704 | + | WHICH ALLOWS A CONTRACTOR AND ALL SUBCONTRACTORS TO COMPETE27 | |
705 | + | 1307 | |
706 | + | -19- FOR CONTRACTS AND SUBCONTRACTS WITHOUT REGARD TO WHETHER1 | |
707 | + | THEY ARE PARTIES TO A COLLECTIVE BARGAINING AGREEMENT .2 | |
732 | 708 | (10) Grants. (a) T | |
733 | - | O ACQUIRE MONEY TO PAY FOR HVAC | |
734 | - | INFRASTRUCTURE IMPROVEMENT PROJECTS AS DESCRIBED IN THIS SECTION , | |
735 | - | A LOCAL EDUCATION PROVIDER MAY : | |
709 | + | O ACQUIRE MONEY TO PAY FOR HVAC3 | |
710 | + | INFRASTRUCTURE IMPROVEMENT PROJECTS AS DESCRIBED IN THIS4 | |
711 | + | SECTION, A LOCAL EDUCATION PROVIDER | |
712 | + | MAY:5 | |
736 | 713 | (I) S | |
737 | - | EEK AND ACQUIRE GRANT WRITING SUPPORT AND PROJECT | |
738 | - | PLANNING SUPPORT FROM THE OFFICE OF THE GOVERNOR | |
739 | - | , AS DESCRIBED IN | |
740 | - | SECTION | |
741 | - | 24-75-232; | |
714 | + | EEK AND ACQUIRE GRANT WRITING SUPPORT AND PROJECT6 | |
715 | + | PLANNING SUPPORT FROM THE OFFICE OF THE GOVERNOR , AS DESCRIBED7 | |
716 | + | IN SECTION 24-75-232;8 | |
742 | 717 | (II) A | |
743 | - | PPLY FOR GRANTS FROM FEDERAL AND STATE GOVERNMENT | |
744 | - | SOURCES | |
745 | - | ; | |
718 | + | PPLY FOR GRANTS FROM FEDERAL AND STATE GOVERNMENT9 | |
719 | + | SOURCES;10 | |
746 | 720 | (III) U | |
747 | - | TILIZE THE REGIONAL GRANT NAVIGATOR | |
748 | - | ||
749 | - | ||
750 | - | ||
751 | - | ||
752 | - | ASSISTANCE | |
753 | - | : | |
721 | + | TILIZE THE REGIONAL GRANT NAVIGATOR PROGRAM11 | |
722 | + | ADMINISTERED THROUGH THE | |
723 | + | GOVERNOR'S OFFICE; AND12 | |
724 | + | (IV) C | |
725 | + | OORDINATE WITH THIRD PARTIES WITH EXPERTISE13 | |
726 | + | PERTAINING TO FEDERAL FUNDING APPLICATION TECHNICAL ASSISTANCE ,14 | |
727 | + | INCLUDING ASSISTANCE CONCERNING :15 | |
754 | 728 | (A) S | |
755 | - | CHOOL VENTILATION AND ENERGY EFFICIENCY VERIFICATION ; | |
729 | + | CHOOL VENTILATION AND ENERGY EFFICIENCY VERIFICATION ;16 | |
756 | 730 | (B) S | |
757 | - | USTAINABILITY PROJECT PLANNING; | |
731 | + | USTAINABILITY PROJECT PLANNING;17 | |
758 | 732 | (C) G | |
759 | - | RANT WRITING; | |
733 | + | RANT WRITING;18 | |
760 | 734 | (D) T | |
761 | - | ECHNICAL ASSISTANCE, SUCH AS ENGINEERING OR FEASIBILITY | |
762 | - | STUDIES | |
763 | - | , NEEDED TO IMPROVE OR MAKE THE CASE FOR A GRANT | |
764 | - | APPLICATION | |
765 | - | ; | |
735 | + | ECHNICAL ASSISTANCE, SUCH AS ENGINEERING OR19 | |
736 | + | FEASIBILITY STUDIES, NEEDED TO IMPROVE OR MAKE THE CASE FOR A20 | |
737 | + | GRANT APPLICATION;21 | |
766 | 738 | (E) C | |
767 | - | OMPLIANCE WITH FEDERAL LABOR STANDARDS ; | |
739 | + | OMPLIANCE WITH FEDERAL LABOR STANDARDS ;22 | |
768 | 740 | (F) I | |
769 | - | NCENTIVES FOR TAX CREDITS; | |
741 | + | NCENTIVES FOR TAX CREDITS;23 | |
770 | 742 | (G) P | |
771 | - | ROCUREMENT MATERIALS ASSOCIATED WITH THE | |
772 | - | " | |
773 | - | ||
774 | - | "INFRASTRUCTURE INVESTMENT AND JOBS ACT", PUB.L. 117-58; | |
743 | + | ROCUREMENT MATERIALS ASSOCIATED WITH THE FEDERAL24 | |
744 | + | "B | |
745 | + | UILD AMERICA, BUY AMERICA ACT", SECTION 70901 ET SEQ., OF THE25 | |
746 | + | FEDERAL "INFRASTRUCTURE INVESTMENT AND JOBS ACT", PUB.L. 117-58;26 | |
775 | 747 | (H) P | |
776 | - | ROJECT FINANCING EXPERTISE, SUCH AS CREATING | |
777 | - | ||
778 | - | ; | |
748 | + | ROJECT FINANCING EXPERTISE , SUCH AS CREATING AN27 | |
749 | + | 1307 | |
750 | + | -20- ON-BILL FINANCING AND REPAYMENT PROGRAM ;1 | |
779 | 751 | (I) C | |
780 | - | OMPLIANCE WITH LABOR STANDARDS OUTLINED IN FEDERAL | |
781 | - | FUNDING GUIDANCE | |
782 | - | ; AND | |
783 | - | (J) COMMUNITY BENEFIT PLAN DEVELOPMENT AND COMMUNITY | |
784 | - | BENEFIT AGREEMENT NEGOTIATION AND IMPLEMENTATION | |
785 | - | , SUCH AS BEST | |
786 | - | PRACTICES OR CONSULTANT FUNDS FOR COMMUNITY MEMBERS | |
787 | - | . | |
752 | + | OMPLIANCE WITH LABOR STANDARDS OUTLINED IN FEDERAL2 | |
753 | + | FUNDING GUIDANCE; AND3 | |
754 | + | (J) C | |
755 | + | OMMUNITY BENEFIT PLAN DEVELOPMENT AND COMMUNITY4 | |
756 | + | BENEFIT AGREEMENT NEGOTIATION AND IMPLEMENTATION , SUCH AS BEST5 | |
757 | + | PRACTICES OR CONSULTANT FUNDS FOR COMMUNITY MEMBERS .6 | |
788 | 758 | (b) I | |
789 | - | N APPLYING FOR A GRANT AS DESCRIBED IN SUBSECTION | |
790 | - | (10)(a)(II) OF THIS SECTION, A LOCAL EDUCATION PROVIDER SHALL ENSURE | |
791 | - | THAT EACH GRANT APPLICATION INCLUDES A STATEMENT ACKNOWLEDGING | |
792 | - | THAT THE LOCAL EDUCATION PROVIDER MUST COMPLY WITH APPLICABLE | |
793 | - | LABOR STANDARDS REQUIRED IN ORDER FOR THE LOCAL EDUCATION | |
794 | - | PROVIDER TO REMAIN COMPETITIVE FOR FEDERAL FUNDING SOURCES | |
795 | - | , | |
796 | - | PAGE 17-HOUSE BILL 24-1307 SPECIFICALLY GRANT PROGRAMS UNDER THE FEDERAL "INFRASTRUCTURE | |
797 | - | INVESTMENT AND JOBS ACT", PUB.L. 117-58, AND RECEIVE FULL | |
798 | - | PREFERENCE POINTS FOR PROGRAMS UNDER THE FEDERAL | |
799 | - | "INFLATION | |
800 | - | REDUCTION ACT," INCLUDED THEREIN, INCLUDING STANDARDS PERTAINING | |
801 | - | TO | |
802 | - | : | |
759 | + | N APPLYING FOR A GRANT AS DESCRIBED IN SUBSECTION7 | |
760 | + | (10)(a)(II) | |
761 | + | OF THIS SECTION, A LOCAL EDUCATION PROVIDER | |
762 | + | SHALL8 | |
763 | + | ENSURE THAT EACH GRANT APPLICATION INCLUDES A STATEMENT9 | |
764 | + | ACKNOWLEDGING THAT THE LOCAL EDUCATION PROVIDER MUST COMPLY10 | |
765 | + | WITH APPLICABLE LABOR STANDARDS REQUIRED IN ORDER FOR THE LOCAL11 | |
766 | + | EDUCATION PROVIDER TO REMAIN COMPETITIVE FOR FEDERAL FUNDING12 | |
767 | + | SOURCES, SPECIFICALLY GRANTS PROGRAMS UNDER THE FEDERAL13 | |
768 | + | "I | |
769 | + | NFRASTRUCTURE INVESTMENT AND JOBS ACT", PUB.L. 117-58, AND | |
770 | + | 14 | |
771 | + | RECEIVE FULL PREFERENCE POINTS FOR PROGRAMS UNDER THE FEDERAL15 | |
772 | + | "I | |
773 | + | NFLATION REDUCTION ACT," INCLUDED THEREIN , | |
774 | + | INCLUDING16 | |
775 | + | STANDARDS PERTAINING TO:17 | |
803 | 776 | (I) T | |
804 | - | HE FEDERAL "DAVIS-BACON ACT OF 1931", PUB.L. 71-798; | |
777 | + | HE FEDERAL "DAVIS-BACON ACT OF 1931", PUB.L. 71-798;18 | |
805 | 778 | (II) R | |
806 | - | EGISTERED APPRENTICESHIP PROGRAMS AND OTHER LABOR | |
807 | - | MANAGEMENT PARTNERSHIPS | |
808 | - | ; | |
779 | + | EGISTERED APPRENTICESHIP PROGRAMS AND OTHER LABOR19 | |
780 | + | MANAGEMENT PARTNERSHIPS ;20 | |
809 | 781 | (III) P | |
810 | - | ROJECT LABOR AGREEMENTS ; | |
782 | + | ROJECT LABOR AGREEMENTS ;21 | |
811 | 783 | (IV) C | |
812 | - | OMMUNITY WORKFORCE AGREEMENTS ; | |
784 | + | OMMUNITY WORKFORCE AGREEMENTS ;22 | |
813 | 785 | (V) C | |
814 | - | OMMUNITY BENEFIT AGREEMENTS ; AND | |
815 | - | (VI) PREVENTION OF WORKER MISCLASSIFICATION . | |
816 | - | (11) Notices of receipt of federal grant funding. A | |
817 | - | LOCAL | |
818 | - | EDUCATION PROVIDER THAT RECEIVES FEDERAL GRANT FUNDING FOR | |
786 | + | OMMUNITY BENEFIT AGREEMENTS ; AND23 | |
787 | + | (VI) P | |
788 | + | REVENTION OF WORKER MISCLASSIFICATION .24 | |
789 | + | (11) Notices of receipt of federal grant funding. A LOCAL25 | |
790 | + | EDUCATION PROVIDER THAT RECEIVES FEDERAL GRANT FUNDING FOR26 | |
791 | + | HVAC IMPROVEMENTS SHALL NOTIFY THE DEPARTMENT OF THE RECEIPT27 | |
792 | + | 1307 | |
793 | + | -21- OF THE FUNDING. THE DEPARTMENT SHALL PUBLISH ON ITS PUBLIC1 | |
794 | + | WEBSITE NOTIFICATIONS OF ALL FEDERAL GRANT FUNDING THAT IS2 | |
795 | + | AWARDED TO LOCAL EDUCATION PROVIDERS FOR HVAC IMPROVEMENTS.3 | |
796 | + | SECTION 3. In Colorado Revised Statutes, add 22-5-123 as4 | |
797 | + | follows:5 | |
798 | + | 22-5-123. BOCES - ventilation and energy efficiency6 | |
799 | + | verification and repair. O | |
800 | + | N AND AFTER THE EFFECTIVE DATE OF THIS7 | |
801 | + | SECTION, IF A BOCES UNDERTAKES HVAC INFRASTRUCTURE8 | |
802 | + | IMPROVEMENTS USING MONEY MADE AVAILABLE BY A FEDERAL9 | |
803 | + | GOVERNMENT SOURCE OR BY A FEDERAL GOVERNMENT SOURCE IN10 | |
804 | + | COMBINATION WITH A STATE GOVERNMENT SOURCE SPECIFICALLY FOR11 | |
805 | + | SUCH PURPOSE, THE BOCES SHALL COMPLY WITH THE REQUIREMENTS12 | |
806 | + | DESCRIBED IN SECTION 22-32-152 IN IMPLEMENTING THE HVAC13 | |
807 | + | INFRASTRUCTURE IMPROVEMENTS .14 | |
808 | + | SECTION 4. In Colorado Revised Statutes, add 22-30.5-121 as15 | |
809 | + | follows:16 | |
810 | + | 22-30.5-121. Charter schools - ventilation and energy17 | |
811 | + | efficiency verification and repair. O | |
812 | + | N AND AFTER THE EFFECTIVE DATE18 | |
813 | + | OF THIS SECTION, IF A CHARTER SCHOOL UNDERTAKES HVAC19 | |
814 | + | INFRASTRUCTURE IMPROVEMENTS USING MONEY MADE AVAILABLE BY A20 | |
815 | + | FEDERAL GOVERNMENT SOURCE OR BY A FEDERAL GOVERNMENT SOURCE21 | |
816 | + | IN COMBINATION WITH A STATE GOVERNMENT SOURCE SPECIFICALLY FOR22 | |
817 | + | SUCH PURPOSE, THE CHARTER SCHOOL SHALL COMPLY WITH THE23 | |
818 | + | REQUIREMENTS DESCRIBED IN SECTION 22-32-152 IN IMPLEMENTING THE24 | |
819 | 819 | HVAC | |
820 | - | IMPROVEMENTS SHALL NOTIFY THE DEPARTMENT OF THE RECEIPT OF THE | |
821 | - | FUNDING | |
822 | - | . THE DEPARTMENT SHALL PUBLISH ON ITS PUBLIC WEBSITE | |
823 | - | NOTIFICATIONS OF ALL FEDERAL GRANT FUNDING THAT IS AWARDED TO | |
824 | - | LOCAL EDUCATION PROVIDERS FOR | |
825 | - | HVAC IMPROVEMENTS. | |
826 | - | SECTION 3. In Colorado Revised Statutes, add 22-5-123 as | |
827 | - | follows: | |
828 | - | 22-5-123. BOCES - ventilation and energy efficiency verification | |
829 | - | and repair. O | |
830 | - | N AND AFTER THE EFFECTIVE DATE OF THIS SECTION , IF A | |
831 | - | BOCES UNDERTAKES HVAC INFRASTRUCTURE IMPROVEMENTS USING | |
832 | - | MONEY MADE AVAILABLE BY A FEDERAL GOVERNMENT SOURCE OR BY A | |
833 | - | FEDERAL GOVERNMENT SOURCE IN COMBINATION WITH A STATE | |
834 | - | GOVERNMENT SOURCE SPECIFICALLY FOR SUCH PURPOSE | |
835 | - | , THE BOCES SHALL | |
836 | - | COMPLY WITH THE REQUIREMENTS DESCRIBED IN SECTION | |
837 | - | 22-32-152 IN | |
838 | - | IMPLEMENTING THE | |
839 | - | HVAC INFRASTRUCTURE IMPROVEMENTS . | |
840 | - | SECTION 4. In Colorado Revised Statutes, add 22-30.5-121 as | |
841 | - | follows: | |
842 | - | PAGE 18-HOUSE BILL 24-1307 22-30.5-121. Charter schools - ventilation and energy efficiency | |
843 | - | verification and repair. O | |
844 | - | N AND AFTER THE EFFECTIVE DATE OF THIS | |
845 | - | SECTION | |
846 | - | , IF A CHARTER SCHOOL UNDERTAKES HVAC INFRASTRUCTURE | |
847 | - | IMPROVEMENTS USING MONEY MADE AVAILABLE BY A FEDERAL | |
848 | - | GOVERNMENT SOURCE OR BY A FEDERAL GOVERNMENT SOURCE IN | |
849 | - | COMBINATION WITH A STATE GOVERNMENT SOURCE SPECIFICALLY FOR SUCH | |
850 | - | PURPOSE | |
851 | - | , THE CHARTER SCHOOL SHALL COMPLY WITH THE REQUIREMENTS | |
852 | - | DESCRIBED IN SECTION | |
853 | - | 22-32-152 IN IMPLEMENTING THE HVAC | |
854 | - | INFRASTRUCTURE IMPROVEMENTS . | |
855 | - | SECTION 5. In Colorado Revised Statutes, add 22-30.5-531 as | |
856 | - | follows: | |
857 | - | 22-30.5-531. Institute charter schools - ventilation and energy | |
820 | + | INFRASTRUCTURE IMPROVEMENTS .25 | |
821 | + | SECTION 5. In Colorado Revised Statutes, add 22-30.5-531 as26 | |
822 | + | follows:27 | |
823 | + | 1307 | |
824 | + | -22- 22-30.5-531. Institute charter schools - ventilation and energy1 | |
858 | 825 | efficiency verification and repair. O | |
859 | - | N AND AFTER THE EFFECTIVE DATE OF | |
860 | - | THIS SECTION | |
861 | - | , IF AN INSTITUTE CHARTER SCHOOL UNDERTAKES HVAC | |
862 | - | INFRASTRUCTURE IMPROVEMENTS USING MONEY MADE AVAILABLE BY A | |
863 | - | FEDERAL GOVERNMENT SOURCE OR BY A FEDERAL GOVERNMENT SOURCE IN | |
864 | - | COMBINATION WITH A STATE GOVERNMENT SOURCE SPECIFICALLY FOR SUCH | |
865 | - | PURPOSE | |
866 | - | , THE INSTITUTE CHARTER SCHOOL SHALL COMPLY WITH THE | |
867 | - | REQUIREMENTS DESCRIBED IN SECTION | |
868 | - | 22-32-152 IN IMPLEMENTING THE | |
869 | - | HVAC INFRASTRUCTURE IMPROVEMENTS . | |
870 | - | SECTION 6. In Colorado Revised Statutes, add 22-80-120 as | |
871 | - | follows: | |
872 | - | 22-80-120. Ventilation and energy efficiency verification and | |
826 | + | N AND AFTER THE EFFECTIVE DATE2 | |
827 | + | OF THIS SECTION, IF AN INSTITUTE CHARTER SCHOOL UNDERTAKES HVAC3 | |
828 | + | INFRASTRUCTURE IMPROVEMENTS USING MONEY MADE AVAILABLE BY A4 | |
829 | + | FEDERAL GOVERNMENT SOURCE OR BY A FEDERAL GOVERNMENT SOURCE5 | |
830 | + | IN COMBINATION WITH A STATE GOVERNMENT SOURCE SPECIFICALLY FOR6 | |
831 | + | SUCH PURPOSE, THE INSTITUTE CHARTER SCHOOL SHALL COMPLY WITH THE7 | |
832 | + | REQUIREMENTS DESCRIBED IN SECTION 22-32-152 IN IMPLEMENTING THE8 | |
833 | + | HVAC | |
834 | + | INFRASTRUCTURE IMPROVEMENTS .9 | |
835 | + | SECTION 6. In Colorado Revised Statutes, add 22-80-120 as10 | |
836 | + | follows:11 | |
837 | + | 22-80-120. Ventilation and energy efficiency verification and12 | |
873 | 838 | repair. O | |
874 | - | N AND AFTER THE EFFECTIVE DATE OF THIS SECTION , IF THE | |
875 | - | SCHOOL UNDERTAKES | |
876 | - | HVAC INFRASTRUCTURE IMPROVEMENTS USING | |
877 | - | MONEY MADE AVAILABLE BY A FEDERAL GOVERNMENT SOURCE OR BY A | |
878 | - | FEDERAL GOVERNMENT SOURCE IN COMBINATION WITH A STATE | |
879 | - | GOVERNMENT SOURCE SPECIFICALLY FOR SUCH PURPOSE | |
880 | - | , THE SCHOOL SHALL | |
881 | - | COMPLY WITH THE REQUIREMENTS DESCRIBED IN SECTION | |
882 | - | 22-32-152 IN | |
883 | - | IMPLEMENTING THE | |
884 | - | HVAC INFRASTRUCTURE IMPROVEMENTS . | |
885 | - | SECTION 7. In Colorado Revised Statutes, 24-75-232, amend | |
886 | - | (1)(d) and (2)(d); and add (1)(d.5) and (5)(e) as follows: | |
887 | - | 24-75-232. "Infrastructure Investment and Jobs Act" cash fund | |
888 | - | - creation - allowable uses - report - legislative declaration - definitions | |
889 | - | PAGE 19-HOUSE BILL 24-1307 - repeal. (1) The general assembly finds and declares that: | |
890 | - | (d) In order for the state to be competitive for the highest range of | |
891 | - | funding available to it under the federal act, it is necessary for departments | |
892 | - | to have funds available as a nonfederal match, although due to still-evolving | |
893 | - | federal guidance the amounts needed and specific types of projects may not | |
894 | - | be known in time for this money to be appropriated in the annual general | |
895 | - | appropriation act; and | |
896 | - | (d.5) WITH THE PASSAGE OF THE "INFLATION REDUCTION ACT OF | |
897 | - | 2022" AND THE "BIPARTISAN INFRASTRUCTURE LAW", BILLIONS OF DOLLARS | |
898 | - | IN FEDERAL MONEY ARE AVAILABLE TO HELP PUBLIC SCHOOLS IMPROVE AIR | |
899 | - | QUALITY IN SCHOOLS | |
900 | - | , STUDENT PERFORMANCE, AND STAFF RETENTION; AND | |
901 | - | (2) As used in this section, unless the context otherwise requires: | |
902 | - | (d) "Local government" means a county, a municipality, a city and | |
903 | - | county, | |
904 | - | A LOCAL EDUCATION PROVIDER , or a special district. | |
905 | - | (5) (e) (I) T | |
906 | - | HE OFFICE SHALL USE EXISTING RESOURCES FUNDED BY | |
907 | - | THE FUND TO PROVIDE GRANT WRITING SUPPORT | |
908 | - | , ADMINISTRATIVE SUPPORT, | |
909 | - | AND PROJECT PLANNING PURSUANT TO SUBSECTION (1)(e)(V) OF THIS | |
910 | - | SECTION TO SCHOOL DISTRICTS | |
911 | - | , BOCES, THE COLORADO SCHOOL FOR THE | |
912 | - | DEAF AND THE BLIND | |
913 | - | , CHARTER SCHOOLS , AND INSTITUTE CHARTER | |
914 | - | SCHOOLS | |
915 | - | , INCLUDING SUCH ENTITIES THAT ARE UNDERTAKING HVAC | |
916 | - | INFRASTRUCTURE IMPROVEMENTS AS DESCRIBED IN SECTION 22-32-152. | |
917 | - | (II) A | |
918 | - | S PART OF THE REPORT ISSUED PURSUANT TO SUBSECTION (7)(a) | |
919 | - | OF THIS SECTION, THE OFFICE SHALL SUBMIT A REPORT TO THE JOINT BUDGET | |
920 | - | COMMITTEE AND THE CAPITAL DEVELOPMENT COMMIT TEE CONCERNING THE | |
921 | - | NUMBER OF APPLICANTS FOR MATCHING FUNDS FROM LOCAL EDUCATION | |
922 | - | PROVIDERS REVIEWED BY THE OFFICE BEFORE | |
923 | - | OCTOBER 2, 2025. THE | |
924 | - | REPORT MUST INCLUDE THE AMOUNT OF REQUESTED MATCHING FUNDS | |
925 | - | , THE | |
926 | - | RECOMMENDED AMOUNT OF MATCHING FUNDS | |
927 | - | , AND AN EXPLANATION FOR | |
928 | - | THE DIFFERENCE | |
929 | - | , IF ANY, BETWEEN THE REQUESTED AMOUNTS AND THE | |
930 | - | RECOMMENDED AMOUNTS | |
931 | - | . | |
932 | - | (III) F | |
933 | - | OR THE PURPOSES OF THIS SUBSECTION (5)(e), THE OFFICE MAY | |
934 | - | USE EXISTING MONEY APPROPRIATED FROM THE FUND TO PROVIDE GRANT | |
935 | - | WRITING SUPPORT | |
936 | - | , ADMINISTRATIVE SUPPORT, AND PROJECT PLANNING | |
937 | - | PAGE 20-HOUSE BILL 24-1307 PURSUANT TO SUBSECTION (1)(e)(V) OF THIS SECTION TO REVIEW THE WORK | |
938 | - | OF APPLICANTS AND TO CONNECT APPLICANTS WITH THIRD PARTIES WITH | |
939 | - | EXPERTISE PERTAINING TO FEDERAL FUNDING APPLICATION TECHNICAL | |
940 | - | ASSISTANCE | |
941 | - | , INCLUDING ASSISTANCE CONCERNING : | |
839 | + | N AND AFTER THE EFFECTIVE DATE OF THIS SECTION , IF THE13 | |
840 | + | SCHOOL UNDERTAKES HVAC INFRASTRUCTURE IMPROVEMENTS USING14 | |
841 | + | MONEY MADE AVAILABLE BY A FEDERAL GOVERNMENT SOURCE OR BY A15 | |
842 | + | FEDERAL GOVERNMENT SOURCE IN COMBINATION WITH A STATE16 | |
843 | + | GOVERNMENT SOURCE SPECIFICALLY FOR SUCH PURPOSE , THE SCHOOL17 | |
844 | + | SHALL COMPLY WITH THE REQUIREMENTS DESCRIBED IN SECTION18 | |
845 | + | 22-32-152 | |
846 | + | IN IMPLEMENTING THE HVAC INFRASTRUCTURE19 | |
847 | + | IMPROVEMENTS.20 | |
848 | + | SECTION 7. In Colorado Revised Statutes, 24-75-232, amend21 | |
849 | + | (1)(d) and (2)(d); and add (1)(d.5) and (5)(e) as follows:22 | |
850 | + | 24-75-232. "Infrastructure Investment and Jobs Act" cash23 | |
851 | + | fund - creation - allowable uses - report - legislative declaration -24 | |
852 | + | definitions - repeal. (1) The general assembly finds and declares that:25 | |
853 | + | (d) In order for the state to be competitive for the highest range of26 | |
854 | + | funding available to it under the federal act, it is necessary for27 | |
855 | + | 1307 | |
856 | + | -23- departments to have funds available as a nonfederal match, although due1 | |
857 | + | to still-evolving federal guidance the amounts needed and specific types2 | |
858 | + | of projects may not be known in time for this money to be appropriated3 | |
859 | + | in the annual general appropriation act; and4 | |
860 | + | (d.5) WITH THE PASSAGE OF THE "INFLATION REDUCTION ACT OF5 | |
861 | + | 2022" AND THE "BIPARTISAN INFRASTRUCTURE LAW" BILLIONS OF6 | |
862 | + | DOLLARS IN FEDERAL MONEY ARE AVAILABLE TO HELP PUBLIC SCHOOLS7 | |
863 | + | IMPROVE AIR QUALITY IN SCHOOLS, STUDENT PERFORMANCE, AND STAFF8 | |
864 | + | RETENTION; AND9 | |
865 | + | (2) As used in this section, unless the context otherwise requires:10 | |
866 | + | (d) "Local government" means a county, a municipality, a city and11 | |
867 | + | county, A LOCAL EDUCATION PROVIDER , or a special district.12 | |
868 | + | (5) (e) (I) THE OFFICE SHALL USE EXISTING RESOURCES FUNDED BY13 | |
869 | + | THE FUND TO PROVIDE GRANT WRITING SUPPORT, ADMINISTRATIVE14 | |
870 | + | SUPPORT, AND PROJECT PLANNING PURSUANT TO SUBSECTION (1)(e)(V) OF15 | |
871 | + | THIS SECTION TO SCHOOL DISTRICTS, BOCES, THE COLORADO SCHOOL16 | |
872 | + | FOR THE DEAF AND THE BLIND , CHARTER SCHOOLS, AND INSTITUTE17 | |
873 | + | CHARTER SCHOOLS, INCLUDING SUCH ENTITIES THAT ARE UNDERTAKING18 | |
874 | + | HVAC | |
875 | + | INFRASTRUCTURE IMPROVEMENTS AS DESCRIBED IN SECTION19 | |
876 | + | 22-32-152.20(II) AS PART OF THE REPORT ISSUED PURSUANT TO SUBSECTION21 | |
877 | + | (7)(a) | |
878 | + | OF THIS SECTION, THE | |
879 | + | OFFICE SHALL SUBMIT A REPORT TO THE JOINT22 | |
880 | + | BUDGET COMMITTEE AND THE CAPITAL DEVELOPMENT COMMITTEE23 | |
881 | + | CONCERNING THE NUMBER OF APPLICANTS FOR MATCHING FUNDS FROM24 | |
882 | + | LOCAL EDUCATION PROVIDERS REVIEWED BY THE OFFICE BEFORE25 | |
883 | + | OCTOBER 2, 2025. THE REPORT MUST INCLUDE THE AMOUNT OF26 | |
884 | + | REQUESTED MATCHING FUNDS, THE RECOMMENDE D AMOUNT OF27 | |
885 | + | 1307 | |
886 | + | -24- MATCHING FUNDS, AND AN EXPLANATION FOR THE DIFFERENCE, IF ANY,1 | |
887 | + | BETWEEN THE REQUESTED AMOUNTS AND THE RECOMMENDED AMOUNTS.2 | |
888 | + | (III) FOR THE PURPOSES OF THIS SUBSECTION (5)(e), THE OFFICE3 | |
889 | + | MAY USE EXISTING MONEY APPROPRIATED FROM THE FUND TO PROVIDE4 | |
890 | + | GRANT WRITING SUPPORT, ADMINISTRATIVE SUPPORT, AND PROJECT5 | |
891 | + | PLANNING PURSUANT TO SUBSECTION (1)(e)(V) OF THIS SECTION TO6 | |
892 | + | REVIEW THE WORK OF APPLICANTS AND TO CONNECT APPLICANTS WITH7 | |
893 | + | THIRD PARTIES WITH EXPERTISE PERTAINING TO FEDERAL FUNDING8 | |
894 | + | APPLICATION TECHNICAL ASSISTANCE , INCLUDING ASSISTANCE9 | |
895 | + | CONCERNING:10 | |
942 | 896 | (A) S | |
943 | - | CHOOL VENTILATION AND ENERGY EFFICIENCY VERIFICATION ; | |
897 | + | CHOOL VENTILATION AND ENERGY EFFICIENCY VERIFICATION ;11 | |
944 | 898 | (B) S | |
945 | - | USTAINABILITY PROJECT PLANNING; | |
899 | + | USTAINABILITY PROJECT PLANNING;12 | |
946 | 900 | (C) G | |
947 | - | RANT WRITING; | |
901 | + | RANT WRITING;13 | |
948 | 902 | (D) T | |
949 | - | ECHNICAL ASSISTANCE, SUCH AS ENGINEERING OR FEASIBILITY | |
950 | - | STUDIES | |
951 | - | , NEEDED TO IMPROVE OR MAKE THE CASE FOR A GRANT | |
952 | - | APPLICATION | |
953 | - | ; | |
903 | + | ECHNICAL ASSISTANCE , SUCH AS ENGINEERING OR14 | |
904 | + | FEASIBILITY STUDIES, NEEDED TO IMPROVE OR MAKE THE CASE FOR A15 | |
905 | + | GRANT APPLICATION;16 | |
954 | 906 | (E) C | |
955 | - | OMPLIANCE WITH FEDERAL LABOR STANDARDS ; | |
907 | + | OMPLIANCE WITH FEDERAL LABOR STANDARDS ;17 | |
956 | 908 | (F) I | |
957 | - | NCENTIVES FOR TAX CREDITS; | |
909 | + | NCENTIVES FOR TAX CREDITS;18 | |
958 | 910 | (G) P | |
959 | - | ROCUREMENT MATERIALS ASSOCIATED WITH THE | |
960 | - | " | |
961 | - | ||
962 | - | "INFRASTRUCTURE INVESTMENT AND JOBS ACT", PUB.L. 117-58; | |
911 | + | ROCUREMENT MATERIALS ASSOCIATED WITH THE FEDERAL19 | |
912 | + | "B | |
913 | + | UILD AMERICA, BUY AMERICA ACT", SECTION 70901 ET SEQ., OF THE20 | |
914 | + | FEDERAL "INFRASTRUCTURE INVESTMENT AND JOBS ACT", PUB.L. 117-58;21 | |
963 | 915 | (H) P | |
964 | - | ROJECT FINANCING EXPERTISE, SUCH AS CREATING AN ON-BILL | |
965 | - | FINANCING AND REPAYMENT PROGRAM | |
966 | - | ; | |
916 | + | ROJECT FINANCING EXPERTISE , SUCH AS CREATING AN22 | |
917 | + | ON-BILL FINANCING AND REPAYMENT PROGRAM ;23 | |
967 | 918 | (I) C | |
968 | - | OMPLIANCE WITH LABOR STANDARDS OUTLINED IN FEDERAL | |
969 | - | FUNDING GUIDANCE | |
970 | - | ; AND | |
971 | - | (J) COMMUNITY BENEFIT PLAN DEVELOPMENT AND COMMUNITY | |
972 | - | BENEFIT AGREEMENT NEGOTIATION AND IMPLEMENTATION | |
973 | - | , SUCH AS BEST | |
974 | - | PRACTICES OR CONSULTANT FUNDS FOR COMMUNITY MEMBERS | |
975 | - | . | |
976 | - | (IV) I | |
977 | - | F THERE ARE APPROVED APPLICATIONS FOR HVAC | |
978 | - | INFRASTRUCTURE IMPROVEMENT PROJECTS AT SCHOOL PROJECTS AS | |
979 | - | DESCRIBED IN SECTION | |
980 | - | 22-32-152, THE OFFICE MAY SEEK A SUPPLEMENTAL | |
981 | - | APPROPRIATION FROM THE FUND | |
982 | - | . | |
983 | - | SECTION 8. Safety clause. The general assembly finds, | |
984 | - | determines, and declares that this act is necessary for the immediate | |
985 | - | PAGE 21-HOUSE BILL 24-1307 preservation of the public peace, health, or safety or for appropriations for | |
986 | - | the support and maintenance of the departments of the state and state | |
987 | - | institutions. | |
988 | - | ____________________________ ____________________________ | |
989 | - | Julie McCluskie Steve Fenberg | |
990 | - | SPEAKER OF THE HOUSE PRESIDENT OF | |
991 | - | OF REPRESENTATIVES THE SENATE | |
992 | - | ____________________________ ____________________________ | |
993 | - | Robin Jones Cindi L. Markwell | |
994 | - | CHIEF CLERK OF THE HOUSE SECRETARY OF | |
995 | - | OF REPRESENTATIVES THE SENATE | |
996 | - | APPROVED________________________________________ | |
997 | - | (Date and Time) | |
998 | - | _________________________________________ | |
999 | - | Jared S. Polis | |
1000 | - | GOVERNOR OF THE STATE OF COLORADO | |
1001 | - | PAGE 22-HOUSE BILL 24-1307 | |
919 | + | OMPLIANCE WITH LABOR STANDARDS OUTLINED IN FEDERAL24 | |
920 | + | FUNDING GUIDANCE; AND25 | |
921 | + | (J) C | |
922 | + | OMMUNITY BENEFIT PLAN DEVELOPMENT AND COMMUNITY26 | |
923 | + | BENEFIT AGREEMENT NEGOTIATION AND IMPLEMENTATION , SUCH AS BEST27 | |
924 | + | 1307 | |
925 | + | -25- PRACTICES OR CONSULTANT FUNDS FOR COMMUNITY MEMBERS .1 | |
926 | + | (IV) IF THERE ARE APPROVED APPLICATIONS FOR HVAC2 | |
927 | + | INFRASTRUCTURE IMPROVEMENT PROJECTS AT SCHOOL PROJECTS AS3 | |
928 | + | DESCRIBED IN SECTION 22-32-152, THE OFFICE MAY SEEK A4 | |
929 | + | SUPPLEMENTAL APPROPRIATION FROM THE FUND .5 | |
930 | + | SECTION 8. Safety clause. The general assembly finds,6 | |
931 | + | determines, and declares that this act is necessary for the immediate7 | |
932 | + | preservation of the public peace, health, or safety or for appropriations for8 | |
933 | + | the support and maintenance of the departments of the state and state9 | |
934 | + | institutions.10 | |
935 | + | 1307 | |
936 | + | -26- |