Utah 2025 2025 Regular Session

Utah House Bill HB0313 Substitute / Bill

Filed 02/05/2025

                    02-05 16:47	1st Sub. (Buff) H.B. 313
Thomas W. Peterson proposes the following substitute bill:
1 
State Construction and Electrical Standards Amendments
2025 GENERAL SESSION
STATE OF UTAH
Chief Sponsor: Thomas W. Peterson
Senate Sponsor:
2 
 
3 
LONG TITLE
4 
General Description:
5 
This bill modifies the State Construction Code.
6 
Highlighted Provisions:
7 
This bill:
8 
▸ amends the State Construction Code to:
9 
● align with updated standards in the International Residential Code (IRC);
10 
● align with the updated standards in the National Electric Code (NEC); and
11 
▸ makes technical changes.
12 
Money Appropriated in this Bill:
13 
None
14 
Other Special Clauses:
15 
None
16 
Utah Code Sections Affected:
17 
AMENDS:
18 
15A-2-103, as last amended by Laws of Utah 2024, Chapter 505
19 
15A-3-105, as last amended by Laws of Utah 2024, Chapter 505
20 
15A-3-202, as last amended by Laws of Utah 2024, Chapter 505
21 
15A-3-206, as last amended by Laws of Utah 2024, Chapter 505
22 
15A-3-601, as last amended by Laws of Utah 2024, Chapter 15
23 
 
24 
Be it enacted by the Legislature of the state of Utah:
25 
Section 1.  Section 15A-2-103 is amended to read:
26 
15A-2-103 . Specific editions adopted of construction code of a nationally
27 
recognized code authority.
28 
(1) Subject to the other provisions of this part, the following construction codes are
29 
incorporated by reference, and together with the amendments specified in Chapter 3,
1st Sub. H.B. 313 1st Sub. (Buff) H.B. 313	02-05 16:47
30 
Statewide Amendments Incorporated as Part of State Construction Code, and Chapter 4,
31 
Local Amendments Incorporated as Part of State Construction Code, are the
32 
construction standards to be applied to building construction, alteration, remodeling, and
33 
repair, and in the regulation of building construction, alteration, remodeling, and repair
34 
in the state:
35 
(a) the 2021 edition of the International Building Code, including Appendices C and J,
36 
issued by the International Code Council;
37 
(b) the 2021 edition of the International Residential Code, issued by the International
38 
Code Council;
39 
(c) Appendix AQ of the 2021 edition of the International Residential Code, issued by the
40 
International Code Council;
41 
(d) the 2021 edition of the International Plumbing Code, issued by the International
42 
Code Council;
43 
(e) the 2021 edition of the International Mechanical Code, issued by the International
44 
Code Council;
45 
(f) the 2021 edition of the International Fuel Gas Code, issued by the International Code
46 
Council;
47 
(g) the [2020] 2023 edition of the National Electrical Code, issued by the National Fire
48 
Protection Association;
49 
(h) the 2021 edition of the International Energy Conservation Code, issued by the
50 
International Code Council;
51 
(i) the 2021 edition of the International Existing Building Code, issued by the
52 
International Code Council;
53 
(j) subject to Subsection 15A-2-104(2), the HUD Code;
54 
(k) subject to Subsection 15A-2-104(1), Appendix AE of the 2021 edition of the
55 
International Residential Code, issued by the International Code Council;
56 
(l) subject to Subsection 15A-2-104(1), the 2005 edition of the NFPA 225 Model
57 
Manufactured Home Installation Standard, issued by the National Fire Protection
58 
Association;
59 
(m) subject to Subsection (3), for standards and guidelines pertaining to plaster on a
60 
historic property, as defined in Section 9-8a-302, the U.S. Department of the Interior
61 
Secretary's Standards for Rehabilitation and Guidelines for Rehabilitating Historic
62 
Buildings; [and]
63 
(n) the residential provisions of the 2021 edition of the International Swimming Pool
- 2 - 02-05 16:47	1st Sub. (Buff) H.B. 313
64 
and Spa Code, issued by the International Code Council; and
65 
(o) Modular Building Institute Standards 1200 and 1205, issued by the International
66 
Code Council, except as modified by provisions of this title governing modular units.
67 
(2) Consistent with Title 65A, Chapter 8, Management of Forest Lands and Fire Control,
68 
the Legislature adopts the 2006 edition of the Utah Wildland Urban Interface Code,
69 
issued by the International Code Council, with the alternatives or amendments approved
70 
by the Utah Division of Forestry, Fire, and State Lands, as a construction code that may
71 
be adopted by a local compliance agency by local ordinance or other similar action as a
72 
local amendment to the codes listed in this section.
73 
(3) The standards and guidelines described in Subsection (1)[(n) ] (m) apply only if:
74 
(a) the owner of the historic property receives a government tax subsidy based on the
75 
property's status as a historic property;
76 
(b) the historic property is wholly or partially funded by public money; or
77 
(c) the historic property is owned by a government entity.
78 
Section 2.  Section 15A-3-105 is amended to read:
79 
15A-3-105 . Amendments to Chapters 10 through 12 of IBC.
80 
(1) In IBC, Section 1010.2.4, number (2), the following is added at the end of the sentence:
81 
"Blended assisted living facilities shall comply with Section 1010.2.14.1."
82 
(2) A new IBC Section 1010.2.14.1 is added as follows: "1010.2.14.1 Blended assisted
83 
living facilities. In occupancy Group I-1, Condition 2 or Group I-2, a Type-II assisted
84 
living facility licensed by the Department of Health and Human Services for residents
85 
with Alzheimer's or dementia, and having a controlled egress locking system to prevent
86 
operation from the egress side shall be permitted to also house residents without a
87 
clinical need for their containment where all of the following provisions are met:
88 
(a) locks in the means of egress comply with all IBC requirements for controlled egress
89 
doors;
90 
(b) all residents without a clinical need for their containment shall have the keys, codes,
91 
or other means necessary to exit the facility, in a manner that is determined by the
92 
facility operator and communicated to the resident or their legal representative;
93 
(c) residents or their legal representative acknowledge in writing that they understand
94 
and agree to living in a facility where egress is controlled; and
95 
(d) the number of residents housed in a smoke compartment with controlled egress shall
96 
not be greater than 30."
97 
(3) In IBC, Section 1011.5.2, exception 3 is deleted and replaced with the following: " 3.  In
- 3 - 1st Sub. (Buff) H.B. 313	02-05 16:47
98 
Group R-3 occupancies, within dwelling units in Group R-2 occupancies, and in Group
99 
U occupancies that are accessory to a Group R-3 occupancy, or accessory to individual
100 
dwelling units in Group R-2 occupancies, the maximum riser height shall be 8 inches
101 
(203 mm) and the minimum tread depth shall be 9 inches (229 mm).  The minimum
102 
winder tread depth at the walk line shall be 10 inches (254 mm), and the minimum
103 
winder tread depth shall be 6 inches (152 mm).  A nosing not less than 0.75 inch (19.1
104 
mm) but not more than 1.25 inches (32 mm) shall be provided on stairways with solid
105 
risers where the tread depth is less than 10 inches (254 mm)."
106 
(4) In IBC, Section 1011.11, a new exception 6 is added as follows: " 6.  In occupancies in
107 
Group R-3, as applicable in Section 101.2 and in occupancies in Group U, which are
108 
accessory to an occupancy in Group R-3, as applicable in Section 101.2, handrails shall
109 
be provided on at least one side of stairways consisting of four or more risers."
110 
(5) IBC, Section 1025, is deleted.
111 
(6) IBC, Section 1104.4, exception 1.5 is deleted.
112 
Section 3.  Section 15A-3-202 is amended to read:
113 
15A-3-202 . Amendments to Chapters 1 through 5 of IRC.
114 
(1) In IRC, Section R101.2, Exception, the words "where provided with an automatic
115 
sprinkler system complying with Section P2904" are deleted.
116 
(2) In IRC, Section R102, a new Section R102.7.2 is added as follows: "R102.7.2 Physical
117 
change for bedroom window egress.  A structure whose egress window in an existing
118 
bedroom is smaller than required by this code, and that complied with the construction
119 
code in effect at the time that the bedroom was finished, is not required to undergo a
120 
physical change to conform to this code if the change would compromise the structural
121 
integrity of the structure or could not be completed in accordance with other applicable
122 
requirements of this code, including setback and window well requirements."
123 
(3) In IRC Section R105.2, under Building, the following changes are made:
124 
(a) Number 3 is deleted and replaced with the following: "3. Retaining walls retaining
125 
less than 4 feet (1219mm) of unbalanced fill, unless supporting a surcharge or
126 
requiring design per Section R404.4."
127 
(b) Number 10 is deleted and replaced with the following: "10. Decks that are not more
128 
than 30 inches (762mm) above grade at any point and not requiring guardrails, that
129 
do not serve exit door required by Section R311.4."
130 
(4) In IRC, Section R105.2, a new exception is added: "11. Grade level, non-connected
131 
conex boxes, less than 350 square feet, used for storage only."
- 4 - 02-05 16:47	1st Sub. (Buff) H.B. 313
132 
(5) In IRC, Section R108.3, the following sentence is added at the end of the section: "The
133 
building official shall not request proprietary information."
134 
(6) IRC, Section 109.1.5, is deleted and replaced with the following: "R109.1.5 Other
135 
inspections. In addition to the inspections listed in R109.1.1 through R109.1.4, the
136 
building official shall have the authority to inspect the proper installation of insulation.
137 
R109.1.5.1 Weather-resistant exterior wall envelope inspections. An inspection shall be
138 
made of the weather-resistant exterior wall envelope as required by Section R703.1 and
139 
flashings as required by Section R703.4 to prevent water from entering the
140 
weather-resistive barrier.R109.1.5.2 Fire-resistance-rated construction inspection. Where
141 
fire-resistance-rated construction is required between dwelling units or due to location
142 
on property, the building official shall require an inspection of such construction after
143 
lathing or gypsum board or gypsum panel products are in place, but before any plaster is
144 
applied, or before board or panel joints and fasteners are taped and finished."
145 
(7) In IRC, Section R202, the following definition is added: "ACCESSORY DWELLING
146 
UNIT: A habitable living unit created within the existing footprint of a primary
147 
owner-occupied single-family dwelling."
148 
(8) In IRC, Section R202, the definition for "Approved" is modified by adding the words
149 
"or independent third-party licensed engineer or architect and submitted to the building
150 
official" after the word "official."
151 
(9) In IRC, Section R202, the definition for "Approved Agency" is modified by replacing
152 
the word "and" with "or."
153 
(10) In IRC, Section 202, the definition for "Approved Source" is modified by adding the
154 
words "or licensed engineer or architect" after the word "official."
155 
(11) In IRC, Section R202, the following definition is added: "CERTIFIED BACKFLOW
156 
PREVENTER ASSEMBLY TESTER: A person who has shown competence to test
157 
Backflow prevention assemblies to the satisfaction of the authority having jurisdiction
158 
under Utah Code, Subsection 19-4-104(4)."
159 
(12) In IRC, Section R202, the definition of "Cross Connection" is deleted and replaced
160 
with the following: "CROSS CONNECTION.  Any physical connection or potential
161 
connection or arrangement between two otherwise separate piping systems, one of
162 
which contains potable water and the other either water of unknown or questionable
163 
safety or steam, gas, or chemical, whereby there exists the possibility for flow from one
164 
system to the other, with the direction of flow depending on the pressure differential
165 
between the two systems (see "Backflow, Water Distribution")."
- 5 - 1st Sub. (Buff) H.B. 313	02-05 16:47
166 
(13) In IRC, Section 202, the following definition is added: "DUAL SOURCE
167 
CONNECTION. A pipe that is installed so that either the nonpotable (i.e. secondary)
168 
irrigation water or the potable water is connected to a pressurized irrigation system at
169 
one time, but not both at the same time; or a pipe that is installed so that either the
170 
potable water or private well water is connected to a residence at one time, but not both
171 
at the same time. The potable water supply line shall be protected by a reduced pressure
172 
backflow preventer."
173 
(14) In IRC, Section 202, the following definition is added: "ENERGY STORAGE
174 
SYSTEM (ESS). One or more devices, assembled together, that are capable of storing
175 
energy for supplying electrical energy at a future time."
176 
(15) In IRC, Section 202, in the definition for gray water a comma is inserted after the word
177 
"washers"; the word "and" is deleted; and the following is added to the end: "and clear
178 
water wastes which have a pH of 6.0 to 9.0; are non-flammable; non-combustible;
179 
without objectionable odors; non-highly pigmented; and will not interfere with the
180 
operation of the sewer treatment facility."
181 
(16) In IRC, Section R202, the definition of "Potable Water" is deleted and replaced with
182 
the following: "POTABLE WATER.  Water free from impurities present in amounts
183 
sufficient to cause disease or harmful physiological effects and conforming to the Utah
184 
Code, Title 19, Chapter 4, Safe Drinking Water Act, and Title 19, Chapter 5, Water
185 
Quality Act, and the regulations of the public health authority having jurisdiction."
186 
(17) IRC, Figure R301.2 (3), is deleted and replaced with R301.2 (3) as follows:
187 	"TABLE R301.2 (3)188 
GROUND SNOW LOADS FOR SELECTED LOCATIONS IN UTAH
189 
City/Town County Ground Snow Load (lb/ft2)Elevation (ft)
190 
Beaver	Beaver 35	5886
191 
Brigham City Box Elder 42	4423
192 
Castle Dale Emery 32	5669
193 
Coalville Summit 57	5581
194 
Duchesne Duchesne 39	5508
195 
Farmington Davis 35	4318
196 
Fillmore Millard 30	5138
197 
Heber City Wasatch 60	5604
- 6 - 02-05 16:47	1st Sub. (Buff) H.B. 313
198 	Junction Piute 27	6030199 
Kanab	Kane 25	4964
200 
Loa	Wayne 37	7060
201 
Logan	Cache 43	4531
202 
Manila	Daggett 26	6368
203 
Manti	Sanpete 37	5620
204 
Moab	Grand 21	4029
205 
Monticello San Juan 67	7064
206 
Morgan	Morgan 52	5062
207 
Nephi	Juab 39	5131
208 
Ogden	Weber 37	4334
209 
Panguitch Garfield 41	6630
210 
Parowan Iron 32	6007
211 
Price	Carbon 31	5558
212 
Provo	Utah 31	4541
213 
Randolph Rich 50	6286
214 
Richfield Sevier 27	5338
215 
St. George Washington 21	2585
216 
Salt Lake City Salt Lake 28	4239
217 
Tooele	Tooele 35	5029
218 
Vernal	Uintah 39	5384
219 
Note: To convert lb/ft2 to kN/m2, multiply by 0.0479. To convert feet to meters, multiply by 0.3048.1.
Statutory requirements of the Authority Having Jurisdiction are not included in this state ground snow
load table.
2. For locations where there is substantial change in altitude over the city/town, the load applies at and
below the cited elevation, with a tolerance of 100 ft (30 m).
3. For other locations in Utah, see Bean, B., Maguire, M., Sun, Y. (2018), "The Utah Snow Load
Study," Utah State University Civil and Environmental Engineering Faculty Publications, Paper 3589,
http://utahsnowload.usu.edu/, for ground snow load values."
- 7 - 1st Sub. (Buff) H.B. 313	02-05 16:47
220 
(18) IRC, Section R301.6, is deleted and replaced with the following: "R301.6 Utah Snow
221 
Loads.  The snow loads specified in Table R301.2(5b) shall be used for the jurisdictions
222 
identified in that table.  Otherwise, for other locations in Utah, see Bean, B., Maguire,
223 
M., Sun, Y. (2018), "The Utah Snow Load Study," Utah State University Civil and
224 
Environmental Engineering Faculty Publications, Paper 3589,
225 
http://utahsnowload.usu.edu/, for ground snow load values."
226 
(19) In IRC, Section R302.2, the following sentence is added at the end of the paragraph:
227 
"When an access/maintenance agreement or easement is in place, plumbing, mechanical
228 
ducting, schedule 40 steel gas pipe, and electric service conductors including feeders,
229 
are permitted to penetrate the common wall at grade, above grade, or below grade."
230 
(20) In IRC, Section R302.3, a new exception 3 is added as follows: "3. Accessory dwelling
231 
units separated by walls or floor assemblies protected by not less than 1/2-inch (12.7
232 
mm) gypsum board or equivalent on each side of the wall or bottom of the floor
233 
assembly are exempt from the requirements of this section."
234 
(21) In IRC, Section R302.5.1, the last sentence is deleted.
235 
(22) IRC, Section R302.13, is deleted.
236 
(23) In IRC, Section R303.4, the following exception is added: "Exception: Dwelling units
237 
tested in accordance with Section N1102.4.1.2 (R402.4.1.2) which has an air tightness of
238 
3.0 ACH (50) or greater do not require mechanical ventilation."
239 
(24) In IRC, Section R310.1, all words in the last sentence after "or to a yard or court", are
240 
deleted, and Exception 3 of this section is deleted.
241 
(25) In IRC, Section R310.7, in the exception, the words "or accessory dwelling units" are
242 
added after the words "sleeping rooms".
243 	(26) IRC, Sections R311.7.45 through R311.7.5.3, are deleted and replaced with the following:
244 
"R311.7.45.1 Stair treads and risers. R311.7.5.1 Riser height.  The maximum riser height shall
245 
be 8 inches (203 mm).  The riser shall be measured vertically between leading edges of the
246 
adjacent treads.  The greatest riser height within any flight of stairs shall not exceed the
247 
smallest by more than 3/8 inch (9.5 mm).
248 
      R311.7.5.2 Tread depth.  The minimum tread depth shall be 9 inches (228 mm).  The
249 
tread depth shall be measured horizontally between the vertical planes of the foremost
250 
projection of adjacent treads and at a right angle to the tread's leading edge.  The greatest tread
251 
depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm).
252 
Winder treads shall have a minimum tread depth of 10 inches (254 mm) measured as above at
253 
a point 12 inches (305 mm) from the side where the treads are narrower.  Winder treads shall
- 8 - 02-05 16:47	1st Sub. (Buff) H.B. 313
254 
have a minimum tread depth of 6 inches (152 mm) at any point.  Within any flight of stairs, the
255 
greatest winder tread depth at the 12-inch (305 mm) walk line shall not exceed the smallest by
256 
more than 3/8 inch (9.5 mm).
257 
      R311.7.5.3 Nosing.  The radius of curvature at the leading edge of the tread shall be no
258 
greater than 9/16 inch (14.3 mm).  A nosing not less than 3/4 inch (19 mm) but not more than
259 
1 1/4 inches (32 mm) shall be provided on stairways with solid risers.  The greatest nosing
260 
projection shall not exceed the smallest nosing projection by more than 3/8 inch (9.5 mm)
261 
between two stories, including the nosing at the level of floors and landings.  Beveling of
262 
nosing shall not exceed 1/2 inch (12.7 mm).  Risers shall be vertical or sloped from the
263 
underside of the leading edge of the tread above at an angle not more than 30 degrees (0.51
264 
rad) from the vertical.  Open risers are permitted, provided that the opening between treads
265 
does not permit the passage of a 4-inch diameter (102 mm) sphere.
266 
      Exceptions.
267 
      1.  A nosing is not required where the tread depth is a minimum of 10 inches (254 mm).
268 
      2.  The opening between adjacent treads is not limited on stairs with a total rise of 30
269 
inches (762 mm) or less."
270 
(27) IRC, Section R312.2, is deleted.
271 
(28) IRC, Sections R313.1 through R313.2.1, are deleted and replaced with the following:
272 
"R313.1 Design and installation.  When installed, automatic residential fire sprinkler
273 
systems for townhouses or one- and two-family dwellings shall be designed and
274 
installed in accordance with Section P2904 or NFPA 13D."
275 
(29) In IRC, Section R314.2.2, the words "accessory dwelling units," are added after the
276 
words "Where alterations, repairs."
277 
(30) In IRC, Section R315.2.2, the words "accessory dwelling units," are added after the
278 
words "Where alterations, repairs."
279 
(31) In IRC, Section 315.3, the following words are added to the first sentence after the
280 
word "installed": "on each level of the dwelling unit and."
281 	(32) A new IRC, Section R328.12, is added as follows:
282 
      "R328.12 Signage. A sign located on the exterior of the dwelling shall be installed at a
283 
location approved by the authority having jurisdiction which identifies the battery chemistry
284 
included in the ESS. This sign shall be of sufficient durability to withstand the environment
285 
involved and shall not be handwritten."
286 
(33) In IRC, Section 403.1.3.5.3, an exception is added as follows: "Exception: Vertical
287 
steel in footings shall be permitted to be located while concrete is still plastic and before
- 9 - 1st Sub. (Buff) H.B. 313	02-05 16:47
288 
it has set. Where vertical steel resists placement or the consolidation of concrete around
289 
steel is impeded, the concrete shall be vibrated to ensure full contact between the vertical
290 
steel and concrete."
291 
(34) In IRC, Section R403.1.6, a new Exception 3 is added as follows: "3.  When anchor
292 
bolt spacing does not exceed 32 inches (813 mm) apart, anchor bolts may be placed with
293 
a minimum of two bolts per plate section located not less than 4 inches (102 mm) from
294 
each end of each plate section at interior bearing walls, interior braced wall lines, and at
295 
all exterior walls."
296 
(35) In IRC, Section R403.1.6.1, a new exception is added at the end of Item 2 and Item 3
297 
as follows: "Exception: When anchor bolt spacing does not exceed 32 inches (816 mm)
298 
apart, anchor bolts may be placed with a minimum of two bolts per plate section located
299 
not less than 4 inches (102 mm) from each end of each plate section at interior bearing
300 
walls, interior braced wall lines, and at all exterior walls."
301 
(36) In IRC, Section R404.1, a new exception is added as follows: "Exception: As an
302 
alternative to complying with Sections R404.1 through R404.1.5.3, concrete and
303 
masonry foundation walls may be designed in accordance with IBC Sections 1807.1.5
304 
and 1807.1.6 as amended in Section 1807.1.6.4 and Table 1807.1.6.4 under these rules."
305 
(37) In IRC, Section R405.1, a second exception is added as follows: "Exception: When a
306 
geotechnical report has been provided for the property, a drainage system is not required
307 
unless the drainage system is required as a condition of the geotechnical report. The
308 
geotechnical report shall make a recommendation regarding a drainage system."
309 
(38) In IRC, Section R506.2.3, the words "10-mil (0.010 inch; 0.25 mm)" are deleted and
310 
replaced with "6-mil (0.006 inch; 0.152 mm)" and the words "conforming to ASTM
311 
E1745 Class A requirements" are deleted.
312 
(39) In IRC, Section 507.2.1, Wood materials. The following sentence is added after the
313 
words, "in accordance with section R317," "field applied weather resistant barrier
314 
applied to the top of untreated material,".
315 
Section 4.  Section 15A-3-206 is amended to read:
316 
15A-3-206 . Amendments to Chapters 36, 37, 39, and 44 and Appendix F of IRC.
317 
(1) In IRC, Section E3601.6.2, a new exception is added as follows: "Exception: An
318 
occupant of an accessory dwelling unit is not required to have access to the disconnect
319 
serving the dwelling unit in which they reside."
320 
(2) IRC, Section E3606.5, is deleted.
321 	(3) IRC, Section E3601.7, is deleted and replaced with the following:
- 10 - 02-05 16:47	1st Sub. (Buff) H.B. 313
322 
"3601.7 Maximum number of disconnects. The service disconnecting means shall consist of
323 
not more than six switches or six sets of circuit breakers mounted in a single enclosure or in a
324 
group of separate enclosures."
325 
(4) In IRC, Section E3705.4.4, the following sentences are deleted:
326 
"Where more than two NM cables containing two or more current-carrying
327 
conductors are installed, without maintaining space between the cables, through the
328 
same opening in wood framing should be sealed with thermal insulation, caulk or
329 
sealing foam. The allowable ampacity of each conductor shall be adjusted in accordance
330 
with Table E3705.3 and the provisions of Section E3701.3. Exception. may not apply."
331 	(5) IRC, Section E3901.4.2, is deleted and replaced with the following:
332 
      "E3901.4.2 Island and Peninsular Countertops and Work Spaces. Receptacle outlets, if
333 
installed to serve an island or peninsular countertop or work surface, shall be installed in
334 
accordance with E3901.4.3. If a receptacle outlet is not provided to serve an island or
335 
peninsular countertop or work surface, provisions shall be provided at the island or peninsula
336 
for future addition of a receptacle outlet to serve the island or peninsular countertop or work
337 
surface."
338 	[(5)] (6) IRC, Section E3901.4.3, is deleted and replaced with the following:
339 
      "E3901.4.3 Receptacle Outlet Location. [Receptacle] When installed, receptacle outlets
340 
shall be located in one or more of the following:
341 
      1. On or above, but not more than 20 inches (508 mm) above a countertop or work
342 
surface.
343 
      2. In a countertop using receptacle outlet assemblies listed for use in countertops.
344 
      3. In a work surface using receptacle outlet assemblies listed for use in work surface or
345 
listed for use in countertops.
346 
      Receptacle outlets rendered not readily accessible by appliances fastened in place,
347 
appliance garages, sinks, or range tops as covered in the exception to Section E3901.4.1 or
348 
appliances occupying assigned spaces shall not be considered as these required outlets.
349 
      4. Under the countertop not more than 14 inches from the bottom leading edge of the
350 
countertop."
351 
[(6)] (7) In IRC, Section 3902.1, after the word "125-volt" add "single phase 15 and 20
352 
ampere" and strike the words "through 250 volt."
353 
[(7)] (8) In IRC, Section 3902.2, after the word "125-volt" add "single phase 15 and 20
354 
ampere" and strike the words "through 250 volt."
355 
[(8)] (9) In IRC, Section 3902.3, after the word "125-volt" add "single phase 15 and 20
- 11 - 1st Sub. (Buff) H.B. 313	02-05 16:47
356 
ampere" and strike the words "through 250 volt."
357 
[(9)] (10) In IRC, Section 3902.4, after the word "125-volt" add "single phase 15 and 20
358 
ampere" and strike the words "through 250 volt."
359 
[(10)] (11) In IRC, Section 3902.5, after the word "125-volt" add the words "single phase 15
360 
and 20 ampere in unfinished portions of the basement shall have ground-fault
361 
circuit-interrupter protection for personnel" and delete the rest of the section.
362 
[(11)] (12) In IRC, Section 3902.6, after the word "125-volt" add "single phase 15 and 20
363 
ampere" and strike the words "through 250 volt."
364 
[(12)] (13) In IRC, Section 3902.7, after the word "125-volt" add "single phase 15 and 20
365 
ampere" and strike the words "through 250 volt."
366 
[(13)] (14) In IRC, Section 3902.8, after the word "125-volt" add "single phase 15 and 20
367 
ampere" and strike the words "through 250 volt."
368 
[(14)] (15) In IRC, Section 3902.9, after the word "125-volt" add "single phase 15 and 20
369 
ampere" and strike the words "through 250 volt."
370 
[(15)] (16) IRC, Section 3902.10, is deleted.
371 
[(16)] (17) In IRC, Section 3902.12, after the word "125-volt" add "single phase 15 and 20
372 
ampere" and strike the words "through 250 volt."
373 
[(17)] (18) In IRC, Section 3902.13, after the word "125-volt" add "single phase 15 and 20
374 
ampere" and strike the words "through 250 volt."
375 
[(18)] (19) IRC, Section 3902.15, Crawl space lighting outlets, is deleted.
376 
[(19)] (20) IRC, Section 3902.16, Equipment requiring servicing, is deleted.
377 
[(20)] (21) IRC Section 3902.17, Outdoor outlets, is deleted.
378 
[(21)] (22) IRC, Section 3902.19, Location of arc-fault circuit interrupters, is deleted.
379 
[(22)] (23) IRC, Section E3902.20, Arc-fault circuit interrupter protection, is deleted.
380 
[(23)] (24) IRC, Section E3902.21, Arc-fault circuit interrupter protection for branch circuit
381 
extensions or modification, is deleted.
382 
[(24)] (25) IRC, Section 4002.11, is deleted and replaced with the following: "4002.11
383 
Bathtub and Shower Space. Receptacles shall not be installed within or directly over a
384 
bathtub or shower stall."
385 
[(25)] (26) IRC, Chapter 44, is amended by deleting the standard for "ANCE."
386 
[(26)] (27) In IRC, Chapter 44, the standard for ASHRAE is amended by changing
387 
"34-2013" to "34-2019."
388 
[(27)] (28) In IRC, Chapter 44, the standard for CSA, is amended by changing the:
389 
(a) standard reference number "UL/CSA/ANCE 60335-2-40-2012" to "UL/CSA
- 12 - 02-05 16:47	1st Sub. (Buff) H.B. 313
390 
60335-2-40-2019"; and
391 
(b) title "Standard for Household and Similar Electrical Appliances, Part 2: Particular
392 
Requirements for Motor-Compressors" to "Standard for Household and Similar
393 
Electrical Appliances, Part 2-40, Requirements for Electric Heat Pumps, Air
394 
Conditioners and Dehumidifiers-3rd Edition."
395 
[(28)] (29) In IRC, Chapter 44, the standard for UL, is amended by changing the:
396 
(a) standard reference number "1995-2011" to "1995-2015";
397 
(b) standard reference number "UL/CSA/ANCE 60335-2-40-2012" to "UL/CSA
398 
60335-2-40-2019"; and
399 
(c) title "Standard for Household and Similar Electrical Appliances, Part 2: Particular
400 
Requirements for Motor-Compressors" to "Standard for Household and Similar
401 
Electrical Appliances, Part 2-40, Requirements for Electric Heat Pumps, Air
402 
Conditioners and Dehumidifiers-3rd Edition."
403 	[(29)] (30) In IRC, Chapter 44, the standard for ANSI/RESNET/ICC 201-2019 Section 4.4.4 is
404 
added as follows: "4.4.4. Air Source Heat Pumps and Air Conditioners. For Heat Pumps and
405 
Air Conditioners with the more recent Manufacturers Equipment Performance Ratings (HSPF2
406 
or SEER2) available, and HSPF and SEER are not available, these ratings shall be converted
407 
to HSPF and SEER values by dividing HSPF2 or SEER2 by the conversion factors in Table
408 
4.4.4.1(1).  If the type of equipment is not determined, the conversion shall default to the
409 
Ducted Split System factors.  All calculations, including Equation 4.1-1a shall use HSPF or
410 
SEER values as made available by the Manufacturer or converted as specified in this section.
411 
Table 4.4.4.1(1) SEER2 and HSPF2 Conversion Factors3.
412 	Equipment Type	SEER2/SEEREER/EER4 HSPF/HSPF413 
Ductless Systems	1.00 1.00 0.90
414 
Ducted Split System	0.95 0.95 0.85
415 
Ducted Package System	0.95 0.95 0.84
416 
Small Duct High Velocity System	1.00 not applicable0.85
417 
Ducted Space-Constrained Air Conditioner 0.97 not applicablenot applicable
418 
Ducted Space-Constrained Heat Pump	not applicable0.85"
419 	[(30)] (31) IRC, Chapter 44, is amended by adding the following reference standard:
420 
421 	"Standard reference numberTitle	Referenced in code
section number
- 13 - 1st Sub. (Buff) H.B. 313	02-05 16:47
422 	USC-FCCCHR 10th
Edition Manual of Cross
Connection Control
Foundation for Cross-Connection Control and
Hydraulic Research University of Southern
California Kaprielian Hall 300 Los Angeles
CA 90089-2531
Table P2902.3"
423 
[(31)] (32) IRC, Chapter 44, is amended by adding the following reference standard: "UL
424 
9540-20: Energy Storage Systems and Equipment; R328.1, R328.2, and R328.6."
425 
[(32)] (33)(a) When passive radon controls or portions thereof are voluntarily installed,
426 
the voluntary installation shall comply with Appendix F of the IRC.
427 
(b) An additional inspection of a voluntary installation described in Subsection [(27)(a) ] 
428 
(28)(a) is not required.
429 
Section 5.  Section 15A-3-601 is amended to read:
430 
15A-3-601 . General provisions.
431 
      The following are adopted as amendments to the NEC to be applicable statewide:
432 
(1) The IRC provisions are adopted as the residential electrical standards applicable to
433 
residential installations under the IRC.  All other installations shall comply with the
434 
adopted NEC.
435 
(2) In NEC, Section 210.8(A), the words "through 250-volt" are deleted.
436 
(3) In NEC, Section 210.8(A) number (5), the word "Basements" is deleted and replaced
437 
with the following:
438 
"Unfinished portions or areas of the basement not intended as habitable rooms."
439 
(4) In NEC, Section 210.8(A), number (6), the following is added after the word "Kitchens":
440 
"where the receptacles are installed to serve the countertop surfaces."
441 
(5) In NEC, Section 210.8(A), number (7) is deleted.
442 
(6) In NEC, Section 210.8(D), numbers (8) through (12) are deleted.
443 
(7) NEC, Section 210.8(F), is deleted.
444 	[(5)] (8) NEC, Sections 210.52(C) number (2) and number (3) are deleted and replaced with the
445 
following:
446 
      "210.52(C)(2) Island and peninsular countertops and Work Surfaces. Receptacle outlets,
447 
if installed to serve an island or peninsular countertop or work surface, shall be installed in
448 
accordance with 210.52(C)(3). If a receptacle outlet is not provided to serve an island or
449 
peninsular countertop or work surface, provisions shall be provided at the island or peninsula
450 
for future addition of a receptacle outlet to serve the island or peninsular countertop or work
451 
surface.
452 
      210.2(C)(3) Receptacle outlet location. Receptacle outlets shall be located in one or
- 14 - 02-05 16:47	1st Sub. (Buff) H.B. 313
453 
more of the following:
454 
(a) On or above, but not more than 500 mm (20 inches) above a countertop or work
455 
surface.
456 
(b) In a countertop using receptacle assemblies listed for use in countertops.
457 	(c) In a work surface using receptacle outlet assemblies listed for use in work surfaces or listed
458 
for use in countertops.
459 
      Receptacle outlets rendered not readily accessible by appliances fastened in place,
460 
appliance garages, sinks, or range tops as covered in the exception to 210.52(C)(1), occupying
461 
assigned spaces shall not be considered as these required outlets.
462 
      Exception: In dwelling units designed to be accessible to persons with disabilities,
463 
receptacles shall be permitted to be installed not more than 300 mm (12 inches) below the
464 
countertop or work surface. Receptacles installed below a countertop or work surface shall not
465 
be located where the countertop or work surface extends more than 150 mm (6 inches) beyond
466 
its support or base."
467 
[(6)] (9) NEC, Section 210.12, is deleted.
468 
[(7)] (10) NEC, Section 210.65, is deleted.
469 
(11) NEC, Section 215.18, is deleted.
470 
(12) NEC, Section 225.42 is deleted.
471 
[(8)] (13) NEC, Section 230.67, is deleted.
472 	[(9)] (14) NEC, Section 230.71, is deleted and replaced with the following:
473 
"230.71 Maximum Number of Disconnects.
474 
(A) General. The service disconnecting means for each service permitted by 230.2, or for
475 
each set of service-entrance conductors permitted by 230.40, Exception No. 1, 3, 4, or 5 shall
476 
consist of not more than six switches or sets of circuit breakers, or a combination of not more
477 
than six switches and sets of circuit breakers, mounted in a single enclosure, in a group of
478 
separate enclosures, or in or on a switchboard or in switchgear. There shall be not more than
479 
six sets of disconnects per service grouped in any one location. For the purpose of this section,
480 
disconnecting means installed as part of listed equipment and used solely for the following
481 
shall not be considered a service disconnecting means:
482 
(1) Power monitoring equipment;
483 
(2) Surge-protective device(s);
484 
(3) Control circuit of the ground-fault protection system; or
485 
(4) Power-operable service disconnecting.
486 
(B) Single-Pole Units. Two or three single-pole switches or breakers, capable of individual
- 15 - 1st Sub. (Buff) H.B. 313	02-05 16:47
487 
operation, shall be permitted on multiwire circuits, one pole for each ungrounded conductor, as
488 
one multipole disconnect, provided they are equipped with identified handle ties or a master
489 
handle to disconnect all conductors of the service with no more than six operations of the hand.
490 
(C) Beginning on July 1, 2027, Section 230.71(B) is no longer in effect."
491 
[(10)] (15) NEC, Section 314.27(C), is deleted and replaced with the following: "314.27(C)
492 
Boxes at Ceiling-Suspended (Paddle) Fan Outlets. Outlet boxes or outlet box systems
493 
used as the sole support of a ceiling-suspended (paddle) fan shall be listed, shall be
494 
marked by their manufacturer as suitable for this purpose, and shall not support
495 
ceiling-suspended (paddle) fans that weigh more than 32 kg (70 lb). For outlet boxes or
496 
outlet box systems designed to support ceiling-suspended (paddle) fans that weigh more
497 
than 16 kg (35 lb), the required marking shall include the maximum weight to be
498 
supported."
499 
(16) In NEC, Section 334.24, the last sentence is deleted and replaced with the following:
500 
"For flat cables, the minor diameter dimension of the cable shall be used to determine
501 
the bending radius when bending on the flat side of the cable. For all other bends, the
502 
major diameter dimension shall be used."
503 
[(11) NEC, Section 406.9(C), is deleted and replaced with the following: "406.9(C) Bathtub
504 
and Shower Space. Receptacles shall not be installed within or directly over a bathtub or
505 
shower stall."]
506 
(17) In NEC, Section 334.80, the second paragraph is deleted.
507 
(18) In NEC, Section 338.24, the last sentence is deleted and replaced with the following:
508 
"For flat cables, the minor diameter dimension of the cable shall be used to determine
509 
the bending radius when bending on the flat side of the cable. For all other bends, the
510 
major diameter dimension shall be used."
511 
(19) In NEC, Section 406.9(B) number (2),  the following words are deleted:
512 
"be listed weather-resistant type, and installation shall".
513 
(20) NEC, Section 700.3(A) is deleted and replaced with the following:
514 
"700.3(A) Conductor Witness Test.
515 
The authority having jurisdiction shall conduct or witness a test of the complete
516 
system upon installation and periodically afterward."
517 
Section 6.  Effective Date.
518 
This bill takes effect on May 7, 2025.
- 16 -